 WARNING

APPLYING ABNORMALLY HIGH VOLTAGE ACROSS A PAIR 

OF CONTACTS IN VACUUM MAY PRODUCE X-RADIATION. 

THE RADIATION MAY INCREASE WITH THE INCREASE 

IN VOLTAGE AND/OR DECREASE IN CONTACT SPACING. 

X-RADIATION PRODUCED DURING THIS TEST WITH 

RECOMMENDED VOLTAGE AND NORMAL CONTACT 

SPACING IS EXTREMELY LOW AND WELL BELOW 

MAXIMUM PERMITTED BY STANDARDS. HOWEVER, AS 

A PRECAUTIONARY MEASURE AGAINST POSSIBILITY OF 

APPLICATION OF HIGHER THAN RECOMMENDED VOLTAGE 

AND/OR BELOW NORMAL CONTACT SPACING, IT IS 

RECOMMENDED THAT ALL OPERATING PERSONNEL STAND 

AT LEAST ONE METER AWAY IN FRONT OF THE CIRCUIT 

BREAKER.

Vacuum Interrupter Integrity Test

otee:

N

Roll over each high potential test diagram configuration above to see the  
correct lead connection to the equipment.

otee:

N

The secondary disconnect must be grounded during test.

Vacuum interrupters used in Type VR-Series circuit 

breakers are highly reliable interrupting elements. 

Satisfactory performance of these devices is dependent 

upon the integrity of the vacuum in the interrupter and 

the internal dielectric strength. Both of these parameters 

can be readily checked by a one minute ac high potential 

test, using the appropriate test voltage in the following 

table.

Circuit breaker Rated Maximum 

Voltage

Vacuum Interrupter Integrity 

Test Voltage

ac 60Hz

Up to and including 15.0 kV

27 kV

 WARNING

DC HI-POTENTIAL TESTS ARE NOT RECOMMENDED BY EATON. DO NOT APPLY 

DC AT ANY LEVEL TO VR-SERIES POWER CIRCUIT BREAKERS.

With the circuit breaker open and securely sitting on the floor, connect 

all top/front primary studs (bars) together and the high potential machine 

lead. Connect all bottom/rear studs together. Do not ground them to 

the circuit breaker frame. Start the machine at zero potential, increase to 

appropriate test voltage and maintain for one minute.
Successful withstand indicates that all interrupters have satisfactory 

vacuum level. If there is a breakdown, the defective interrupter or 

interrupters should be identified by an individual test and replaced before 

placing the circuit breaker in service.
After the high potential unit is removed, discharge any electrical charge  

that may be retained. This charge is particularly true from the center shield 

of vacuum interrupters. To avoid any ambiguity in the ac high potential 

test due to leakage or displacement (capacitive) current, the test unit 

should have sufficient volt-ampere capacity. It is recommended that the 

equipment be capable of delivering 25 milliamperes for one minute.
The current delivery capability of 25 mA ac and 5 mA dc apply when 

all three VI’s are tested in parallel. If individual VI’s are tested, current 

capability may be one third of these values.

Vacuum Interrupter Integrity Testing Configuration

OS

Lead

C B A

G/R

Lead

OS

Lead

C B A

G/R

Lead

OS

Lead

C B A

G/R

Lead

OS

Lead

C B A

G/R

Lead

OS

Lead

C B A

G/R

Lead

OS

Lead

C B A

G/R

Lead

OS

Lead

C B A

G/R

Lead

OS

Lead

C B A

G/R

Lead

OS

Lead

C B A

G/R

Lead

OS

Lead

C B A

G/R

Lead

OS Lead

     =   Output Signal Lead

G/R Lead

    =   Ground / Return Lead

4

EATON

   |   Visual Instruction Booklet Essentials   |   DST-2-VR - 18WR Element   |   May 2017  

Summary of Contents for DST-2-VR

Page 1: ...For VR Series Circuit Breakers This is a user interactive supplemental booklet This material is intended to enhance the technical information included in the instruction booklet for the vacuum replace...

Page 2: ...on and maintenance of medium voltage circuits and equipment should be permitted to work on these circuit breakers Always remove the circuit breaker from the enclosure before performing any maintenance...

Page 3: ...m Interrupter Assembly Each interrupter is assembled at the factory as a unit to assure correct dimensional relationships between working components The interrupter assembly consists of a vacuum inter...

Page 4: ...ENTIAL TESTS ARE NOT RECOMMENDED BY EATON DO NOT APPLY DC AT ANY LEVEL TO VR SERIES POWER CIRCUIT BREAKERS With the circuit breaker open and securely sitting on the floor connect all top front primary...

Page 5: ...L BELOW MAXIMUM PERMITTED BY STANDARDS HOWEVER AS A PRECAUTIONARY MEASURE AGAINST POSSIBILITY OF APPLICATION OF HIGHER THAN RECOMMENDED VOLTAGE AND OR BELOW NORMAL CONTACT SPACING IT IS RECOMMENDED TH...

Page 6: ...BOTTOM terminal of the phase being tested 8 Press the TEST button on the DLRO Once the TEST button is pressed 100A dc will flow through the phase being tested If the circuit breaker is not closed the...

Page 7: ...ent speed for interruption Stroke is the gap between fixed and moving contacts of a vacuum interrupter with the circuit breaker open The circuit breaker mechanism provides a fixed amount of motion to...

Page 8: ...d the motor eccentric These bearings are packed at the factory with a top grade slow oxidizing grease which normally should be effective for many years They should not be disturbed unless there is def...

Page 9: ...bracket and tighten Do not over tighten Fish wires through to terminal block Connect wires to terminal block TB1 and TB2 Install tie wraps to hold wire bundle Mechanically and electrically test the c...

Page 10: ...k the threads Remove the two screws on the right hand motor support plate using a 9 64in Allen wrench Remove the motor plate from the side sheet for the 5kV circuit breaker Remove the motor Verify the...

Page 11: ...afety Precautions Read and understand the instruction manual for specific instructions before attempting any maintenance repair or testing on the circuit breaker The user is cautioned to observe all r...

Page 12: ...VR Series Circuit Breaker DST 2 5 VR 350 2000A 12 EATON Visual Instruction Booklet Essentials DST 2 VR 18WR Element May 2017...

Page 13: ...VR Series Circuit Breaker DST 2 15 VR 1200A 13 EATON Visual Instruction Booklet Essentials DST 2 VR 18WR Element May 2017...

Page 14: ...nts and engineering services Eaton is positioned through its global solutions to answer today s most critical electrical power management challenges Eaton is a power management company with 2015 sales...

Reviews: