background image

21

Instruction Book    

IB182942EN   July 2018   www.eaton.com

DST-2-VR

+

VR-Series

+

 Replacement Circuit Breaker

breaker as viewed from the primary bushing side of the circuit 

breaker.

Sttp 5e: 

Loosen the outer jam nut on the 

SURE CLOSE

 spring and 

turn the inner nut clockwise to compress the spring an additional 

.25 inch. Measure and record the length of the compressed 

length of the spring. It should never be compressed to less 

than 3.00 inches. Charge the circuit breaker’s stored energy 

mechanism using the “maintenance tool” and close the circuit 

breaker by depressing the “PUSH TO CLOSE” operator.

Sttp 6e: 

With the circuit breaker still out of the cell and in the closed 

position, measure the output of the MOC drive as described in 

Step 3. The MOC drive force should exceed the MOC cell force 

requirement by a minimum of 10 lbf. If not, repeat Steps 4 - 6 

until the required margin is achieved. Do not compress the spring 

beyond 3.00 inches as referenced in Figure 5.1 and Step 5.

Sttp 7e: 

Manually charge and close the circuit breaker 2-3 times 

to stabilize the reactions of the circuit breaker components. 

Close the circuit breaker and measure the MOC output force 

as described in Step 3. If the force margin remains adequate, 

proceed to the next step. If not, repeat adjustment Steps 

4 - 6. Tighten the jam nut (Figure 5.1) when adjustments are 

completed.

Sttp 8e: 

Insert into the cell following the instructions for the correct 

vintage (See Section 4).

Sttp 9e: 

Operate the circuit breaker to verify the MOC operator force 

is sufficient when driving all the MOC system components.

Sttp 10e: 

Repeat Steps 3 - 8 until acceptable operation is achieved.

Sttp 11e: 

Anytime an adjustment is made, make sure the new 

compressed spring length (measured in the open position) is 

recorded if different from the dimension as received from the 

factory.

Sttp 12e: 

After an adjustment is made, always verify that all nuts are 

secured in place, prior to returning to service.

5.3   MANUAL OPERATION CHECK

Manual operational checks must be performed before the breaker 

is connected to an energized circuit. Tests must be performed with 

the breaker withdrawn from the cell or in the disconnect position. 

While the breaker is withdrawn or in the disconnect position, place 

the maintenance tool into the manual charge socket opening and 

charge the closing springs with about 36 up and down strokes of 

the handle. When charging is complete, the closing crank goes over 

center with an audible “click” and the springs Charged / Discharged 

Indicator shows “Charged”. Remove the maintenance tool.

 NOTICE

IF THE SPRINGS ARE TO BE CHARGED ON A CLOSED BREAKER, NO 

CLICK IS HEARD AT THE END OF CHARGING OPERATION. DISCONTINUE 

CHARGING AND REMOVE THE MAINTENANCE TOOL AS SOON AS 

“CHARGED” FLAG IS FULLY VISIBLE. CONTINUE ATTEMPTS TO FURTHER 

CHARGE MAY RESULT IN DAMAGE TO THE MECHANISM.

 WARNING

ALWAYS REMOVE THE MAINTENANCE TOOL AFTER CHARGING THE 

SPRING. FAILURE TO REMOVE THE MAINTENANCE TOOL FROM THE 

BREAKER COULD CAUSE INJURY TO PERSONNEL AND/OR EQUIPMENT 

DAMAGE IF THE BREAKER WAS TO CLOSE.

Close and trip the breaker by pushing the close lever then the trip 

lever (Figure Set 3.3).

5.4   VACUUM INTERRUPTER INTEGRITY

Using a dry lint-free cloth or a paper towel, clean all the insulating 

surfaces of the pole units. Conduct a vacuum interrupter integrity 

check as described in Section 6.

5.5   LOW FREQUENCY WITHSTAND TEST (INSULATION 

CHECK)

Check breaker primary and secondary insulation per Section 6.

5.6   CONTACT EROSION AND WIPE

Manually charge the closing springs and close the breaker. Check 

contact erosion and wipe as described in Section 6.

5.7   PRIMARY CIRCUIT RESISTANCE

Check the primary circuit resistance as described in Section 6. The 

resistance should not exceed the values specified. Record the values 

obtained for future reference.

5.8   ELECTRICAL OPERATIONS CHECK

After going through the above steps, the breaker is now ready to be 

operated electrically. It is preferred that this check be made with the 

breaker in the Test position in the breaker compartment.
Since the Type DST-2-VR

+

 Circuit Breaker is for use in existing DST-2 

Metal-Clad Switchgear, installation procedures are similar. If it is 

necessary to reference anything in the breaker compartment, refer 

to the original instruction books supplied with the assembly.

 WARNING

EXAMINE THE INSIDE OF THE CELL BEFORE INSERTING THE BREAKER 

FOR EXCESSIVE DIRT OR ANYTHING THAT MIGHT INTERFERE WITH THE 

BREAKER TRAVEL.

 WARNING

KEEP HANDS OFF THE TOP EDGE OF THE FRONT BARRIER WHEN PUSHING 

A BREAKER INTO A CELL. FAILURE TO DO SO COULD RESULT IN BODILY 

INJURY, IF FINGERS BECOME WEDGED BETWEEN THE BREAKER AND 

THE CELL. USE THE HANDLES PROVIDED ON THE FRONT OF THE BREAKER 

FACEPLATE, OR USE BOTH FULLY OPENED HANDS FLAT ON THE FRONT OF 

THE FACEPLATE.

These checks can be performed with the breaker in its withdrawn 

or disconnect position and connecting the breaker to a test cabinet 

or to the switchgear cell’s secondary receptacle using the special 

extension cable designed for this purpose and described in  

 

Section 3.
Perform electrical operations checks. Close and trip the circuit 

breaker electrically several times to verify that the operation is 

reliable and consistent. Check that the operation of the spring 

charging motor is reasonably prompt and that the motor makes no 

unusual noise.

 WARNING

DO NOT PERFORM ELECTRICAL OPERATION CHECKS WITH THE BREAKER 

IN THE “CONNECT” POSITION BECAUSE OF THE POSSIBILITY OF 

CONNECTING DE-ENERGIZED LOAD CIRCUITS TO THE ELECTRICAL POWER 

SOURCE, RESULTING IN DEATH, PERSONNEL INJURY OR EQUIPMENT 

DAMAGE

5.9   MECHANICAL INTERLOCK (FLOOR TRIP) OPERATIONAL 

CHECKS

Check the operation of the mechanical interlock (floor trip) by 

observing the main contact status and closing spring status as the 

breaker is moved between the disconnect and test position. The 

breaker should discharge its closing springs when moved between 

Summary of Contents for DST-2-VR+ Series

Page 1: ...Instruction Book IB182942EN DST 2 VR VR Series Replacement Circuit Breaker DST 2 VR 250 2000A Shown July 2018 Supersedes March 2018 Effective...

Page 2: ...ions of this equipment do not purport to be covered by these instructions If further information is desired by purchaser regarding his particular installation operation or maintenance of particular eq...

Page 3: ...ERATION CHECK 21 5 4 VACUUM INTERRUPTER INTEGRITY 21 5 5 LOW FREQUENCY WITHSTAND TEST INSULATION CHECK 21 5 6 CONTACT EROSION AND WIPE 21 5 7 PRIMARY CIRCUIT RESISTANCE 21 5 8 ELECTRICAL OPERATIONS CH...

Page 4: ...portant that this installation and maintenance instruction booklet be read and followed closely to achieve optimum performance and a long useful circuit breaker life in its application 1 1 VISUAL INST...

Page 5: ...Latching Momentary Capabilities kV MVA Amps K Low Freq kV RMS Impulse kV Peak I kA RMS KI kA RMS kA RMS Peak DST 2 7 5 500 DST 2 7 5 VR 500 8 25 500 1200 2000 1 25 36 95 33 41 66 111 DST 2 15 500 DST...

Page 6: ...on com DST 2 VR VR Series Replacement Circuit Breaker Table 2 DST 2 VR Dimensions Circuit Breaker Type Existing Circuit Breaker Rated Continuous Current at 60 Hz Amps A B C D E F DST 2 VR 1200 2000 65...

Page 7: ...est coupler engaged Failure to disconnect the test coupler could result in an electrical shock leading to death severe personal injury equipment damage and or improper operation Do not work on a close...

Page 8: ...and other components If damaged or loss is detected file claims immediately with the carrier and notify an Eaton representative Tools and Accessories Maintenance Tool Style 94C9506G01 This tool is us...

Page 9: ...ition before placing it in to storage The circuit breaker is shipped with its contacts open and closing springs discharged The indicators on the front cover should confirm this Insert the end of the m...

Page 10: ...w of DST 2 VR Front External View 1 Lock Out Tag Out 5 Manual Charging Socket 9 Push To Close Button 2 Levering In Access 6 Spring Charged Discharged Indicator 10 Interlock Pedal 3 Handle 7 Operations...

Page 11: ...T 2 VR VR Series Replacement Circuit Breaker Figure 3 3 b Rear External View of DST 2 VR Rear External View 1 Lifting Points 4 Anti Rotation Self Adjuster Optional 2 Secondary Disconnects 5 Ground Con...

Page 12: ...t is assembled at the factory as a unit to assure correct dimensional relationships between working components Three interrupter assemblies are used per circuit breaker Each vacuum interrupter assembl...

Page 13: ...ER CONTACTS ARE CLOSED OR THE CLOSING SPRINGS ARE CHARGED THE CIRCUIT BREAKER CONTACTS MAY OPEN OR THE CLOSING SPRINGS DISCHARGE CAUSING CRUSHING INJURY DISCHARGE THE SPRINGS AND OPEN THE CIRCUIT BREA...

Page 14: ...This is the anti pump function 4 4 1 TIMING The opening and closing times for the circuit breakers vary depending upon the control voltage power rating environment and test equipment Differences in ti...

Page 15: ...est and Connect positions OPERATION C and NO C and NC C and NO C and NO C and NC C and NO Brown Switch Black Switch Black Switch Brown Switch SWITCH TERMINAL LS1 bb LS2 aa LS2 bb LC PS1 PS2 Circuit Br...

Page 16: ...ring system tripping and spring release interlocks perform the following a Set the breaker mechanically trip free during the first 4 inches of travel into the cell and whenever the breaker receives a...

Page 17: ...Cover Removed VR Series Circuit Breaker Element Mechanism 1 LH Closing Spring 5 Spring Release Assembly 9 Manual Charge Socket 2 Latch Check Switch To Rear of Motor Cutoff Switch 6 Shunt Trip Assembly...

Page 18: ...eaker Closed Springs Charged 2 1 3 4 5 6 7 8 9 10 11 12 13 14 Closing Cam and Trip Linkage 1 Spring Release Close Latch 6 Ratchet Wheel 11 Anti Close Interlock 2 Pole Shaft 7 Spring Crank 12 Motor Rat...

Page 19: ...2 Main Link 6 Cam Shaft 10 Trip Latch Reset Spring 3 Operating Rod 7 Banana Link 11 Shunt Trip Lever 4 Pole Shaft 8 Trip latch 12 Shunt Trip Coil 4 1 2 3 5 6 7 8 9 10 11 12 4 8 a Circuit Breaker Open...

Page 20: ...a cell containing an MOC until after the switch has been properly adjusted WARNING MEASUREMENTS AND ADJUSTMENTS SHOULD NEVER BE ATTEMPTED IN AN ENERGIZED STRUCTURE IF THE STRUCTURE CANNOT BE DE ENERGI...

Page 21: ...YS REMOVE THE MAINTENANCE TOOL AFTER CHARGING THE SPRING FAILURE TO REMOVE THE MAINTENANCE TOOL FROM THE BREAKER COULD CAUSE INJURY TO PERSONNEL AND OR EQUIPMENT DAMAGE IF THE BREAKER WAS TO CLOSE Clo...

Page 22: ...n The test position can be verified by the inability to move the breaker in or out the Interlock Pedal is in the up position and the cell label test is visible on the floor of the cell in front of the...

Page 23: ...onnect position can be verified by the inability to move the breaker in or out the Interlock Pedal is up and has released the trip mechanism and the cell label operating is visible on the floor of the...

Page 24: ...s DISCHARGED and that the main contact status indicator reads OPEN Manually trip close and trip the breaker as needed to obtain this status Note N The motor cutoff switch is located on the lower cover...

Page 25: ...so that the circuit breaker could be closed It must be returned to the fully withdrawn condition prior to insertion in the circuit breaker compartment b From the withdrawn position align the center g...

Page 26: ...al of the circuit breaker Note N For Canadian versions with separate disconnect and test positions it will stop at the test position Electrical and mechanical tests of the circuit breaker can be perfo...

Page 27: ...and retest or replace Insulation Integrity Main circuit to ground Withstand 15kV 60Hz for 1 Minute 5kV Rating Hi pot Tester Clean and retest or replace Control circuit to ground Charging Motor discon...

Page 28: ...ommended that the equipment be capable of delivering 25 milliamperes for one minute The current delivery capability of 25 mA ac applies when all three vacuum interrupters are tested in parallel If ind...

Page 29: ...ressed in micro ohms Repeat for the remaining two poles The resistance should not exceed the factory test levels more than 200 as stated in IEEE C37 09 Factory test levels are recorded on the circuit...

Page 30: ...ol Mounting Testing Locations by Circuit Breaker Type CIRCUIT BREAKER DESIGNATION APPROXIMATE MECHANISM CHASSIS WIDTH INCH LOWER MOUNTING HOLE LOWER MOUNTING HOLE MARKER PLACEMENT HOLE VR Series 18 A1...

Page 31: ...a sheet of paper that can be kept as a record of the test Record the date of the test person conducting the test circuit breaker serial number and the operations counter on the tape or paper Figures 6...

Page 32: ...Marker Interface Cam Marker CloSure Tool TM 15 O 15 O Figure 6 13 Determining the Distance Traveled Figure 6 14 Illustrative Testing Tape Sample Figure 6 12 Evaluate the CloSure Performance Date of Br...

Page 33: ...nt requires maintenance only once every ten years or ten thousand operations which ever comes first After a ten year service interval or when ten thousand operations have been reached contact your loc...

Page 34: ...urned Motor Cut Off Contacts open or burned Trip Coil Assembly Clapper fails to reset Closing sound but no close Pole Shaft Not open fully Trip Latch Reset Spring Damaged or missing Trip Bar D Shaft F...

Page 35: ...SWITCH Circuit Breaker Auxiliary Switch 94C9525G13 5 POSITION SWITCH Circuit Breaker Position Switch PS1 94C9525H06 6 POSITION SWITCH Circuit Breaker Position Switch PS2 94C9525H07 7 LATCH CHECK SWITC...

Page 36: ...ulevard Cleveland OH 44122 United States Eaton com 2018 Eaton All Rights Reserved Printed in USA Publication No IB182942EN July 2018 Eaton is a registered trademark All trademarks are property of thei...

Reviews: