2.11.13 Repair and maintenance switch
Repair and maintenance switches disconnect all the poles (all the phases) in
the connection cable to a motor. This prevents voltage from being applied
and the motor from being started by accident during repair and maintenance
work.
The DS7 soft starter has a two-phase circuit with semiconductor elements in
the power section, one phase is always connected through directly.
Because of this, all the poles (all three phases) in two-phase controlled soft
starters should always be disconnected from mains voltage in the stop state
– with a contactor connected in series on the mains side, for example.
If a control system does not provide this potential isolation, it is advisable
to connect the motor through a repair or maintenance switch.
DANGER
In both the disabled and stop states of the soft starter when the
mains voltage is present (terminals 1L1, 3L2, 5L3), there is also
a dangerous voltage present at the output terminals (2T1, 4T2,
6T3) and therefore also on the motor cables and connection
terminals of the motor (U, V, W)!
Size 1 and 2 (4 - 32 A)
Size 3 and 4 (41 – 200 A)
Figure 33: Dangerous voltage
M
3 ~
1L1
3L2
5L3
2T1
4T2
6T3
M
3 ~
1L1
3L2
5L3 PE
PE
2T1
4T2
6T3
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...