26
Instruction Leaflet IL
66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
EATON CORPORATION www.eaton.com
I.L. 66A7638H03
Effective September 2007
26
Configuration Tag 4:
MPCV Relay with No Setpoints and No Remote Control
Command
Number
INCOM
Command
Command
Description
Scan
Level
0
300
Fast Status
Poll
1
300 with 3C8
Fast Status & Flags Buffer
Poll
2
305
Current Buffer
Interleaved
3
3CD
MPCV Transformer And Network Voltages
Interleaved
4
30F N=3B
MPCV Phasing Voltage Phasors Buffer
Interleaved
5
308
Power Buffer (1)
Interleaved
6
309
Power Buffer (2)
Interleaved
7
3CA
MPCV Temperature Buffer
Interleaved
8
3C9
Setpoints Buffer
Timed3
Binary
Input
Type
Description
Scan
Level
0
Status
Device On-Line
Virtual
1
Status
Open (S7-S6 state = 00)
Poll
2
Status
Closed (S7-S6 state = 01)
Poll
3
Status
Tripped (S7-S6 state = 10)
Poll
4
Status
Alarm (S7-S6 state = 11)
Poll
5
Status
Breaker Closed
Poll
6
Status
Remote Trip
Poll
7
Status
Protective Remote Close
Poll
8
Status
Aux #2 Active
Poll
9
Status
Aux #3 Active
Poll
10
Status
Aux #4 Active
Poll
11
Status
Protector Failed To Open Alarm
Poll
12
Status
Protector Failed To Close Alarm
Poll
13
Status
Aux #2 In Alarm
Poll
14
Status
Aux #3 In Alarm
Poll
15
Status
Aux #4 In Alarm
Poll
16
Status
Breaker Pumping
Poll