25
Instruction Leaflet IL
66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
EATON CORPORATION www.eaton.com
I.L. 66A7638H03
Effective September 2007
25
Analog
Input
Type
Description
Scan
Level
0
Data
I
A
Interleaved
1
Data
I
B
Interleaved
2
Data
I
C
Interleaved
3
Data
V
NA
Interleaved
4
Data
V
NB
Interleaved
5
Data
V
NC
Interleaved
6
Data
V
TA
Interleaved
7
Data
V
TB
Interleaved
8
Data
V
TC
Interleaved
9
Data
V
PA
Interleaved
10
Data
V
PB
Interleaved
11
Data
V
PC
Interleaved
12
Data
V
P1d
Interleaved
13
Data
V
P1q
Interleaved
14
Data
Real Power (kW)
Interleaved
15
Data
Reactive Power (kVars)
Interleaved
16
Data
PF (%)
Interleaved
17
Data
Temperature (
o
C)
Interleaved
Counter
Input
Type
Description
Scan
Level
0
Data
Primary / Secondary / Cause
Poll
1
Data
INCOM Product ID
Poll
2
Data
Firmware Version / Revision
Timed3
Control
Output
Latch ON
Latch OFF
0
Open Circuit Breaker and Block Open
Clear Block Open
1
Protective Close
Clear Protective Close
2
Reset Pumping Fault
-----