Configuration Tag 22:
DT3000
Command
Number
INCOM
Command
Command
Description
Scan
Level
0
300
Fast Status
Poll
1
300 with 3C8
Fast Status & Flags Buffer
Poll
2
305
Current Buffer
Interleaved
3
30F N=2
Peak Demand Currents Buffer
Interleaved
4
3C9
Setpoints Buffer
Timed3
Binary
Input
Type
Description
Scan
Level
0
Status
Device On-Line
Virtual
1
Status
Open (S7-S6 state = 00)
Poll
2
Status
Closed (S7-S6 state = 01)
Poll
3
Status
Tripped (S7-S6 state = 10)
Poll
4
Status
LDPU Alarm (S7-S6 state = 11)
Poll
5
Status
Breaker Closed
Poll
6
Status
Remote Trip
Poll
7
Status
Time Overcurrent - Long Delay - Trip (LDFLG)
Poll
8
Status
Short Delay Trip (SDFLG)
Poll
9
Status
Instantaneous Trip (INSTFLG)
Poll
10
Status
Discriminator Trip (DISCFLG)
Poll
11
Status
Ground Fault (GNDFLG)
Poll
12
Status
High Load Alarm (HLFLG)
Poll
13
Status
Long Delay Protection In Progress (LDPUFLG)
Poll
14
Status
Breaker Trip (TRIPFLG)
Poll
15
Status
RAM Error (RAMFLG)
Poll
16
Status
EEROM Error (EEROMFLG)
Poll
17
Status
Phase Long Delay Zone Interlock In (PHASE_ZIN)
Poll
18
Status
Override Trip (OVERFLG)
Poll
19
Status
Ground Long Delay Zone Interlock In (GND_ZIN)
Poll
20
Status
External Trip, via INCOM (EXTFLG)
Poll
21
Status
Program Mode (Pgm_Mode)
Poll
22
Status
Test Mode (Test_Mode_Flg)
Poll
23
Status
Ground Long Delay Has Picked-Up (GLDPUFLG)
Poll
24
Status
Phase Short Delay Has Picked-Up (PSDPUFLG)
Poll
25
Status
Ground Short Delay Has Picked-Up (GSDPUFLG)
Poll