Power Circuit Breakers Type DSII and 
SPB with OPTIM Trip Units

 

Electronic Trip Units

 

Programming and Monitoring

 

Stand Alone

 

Digitrip OPTIM 750 and 1050 electronic trip 
units are programmable by the use of a Hand 
held programmer called a Digitrip OPTIMiz-
er. The Digitrip OPTIMizer accesses, displays 
and configures trip settings and information. 
The portable programmer plugs into the 
front of the trip unit and is powered by a nine 
volt battery.  A telephone type cord stretches 
up to eight feet away from the breaker.

 

Sub-Network

 

Digitrip OPTIM 750 and 1050 electronic 
trip units can also be connected as part of a 
sub-network system to a panel mounted user 
interface device called a Breaker Interface 
Module (BIM). A Breaker Interface Module 
accesses, configures, and displays OPTIM 
trip unit information and for Digitrip RMS 810 
and 910 trip units and  Energy Sentinels. The 
BIM communicates with up to 50 devices. 
The BIM, like the AEMII, is normally mounted 
on the front of an electrical assembly. 

 

Field Bus System 

 

Digitrip OPTIM 750 and 1050 electronic trip 
units can be connected into a field bus sys-
tem which is called IMPACC. All control, 
monitoring and configuration of the trip units 
can be carried out from a central personal 
computer. See page 641 of this catalog for 
more information on IMPACC.

 

Field Testing

 

System maintenance is an extremely impor-
tant part of any distribution system and the 
capability to test electronic trip units is an es-
sential requirement.

Digitrip OPTIM 750 and 1050 electronic trip 
units have an integral test capability and do 
not require a special external test set. Both 
phase and ground, trip and no trip, testing 
can be carried out with the breaker in the 
connected cell position using an OPTIMizer, 
a BIM or IMPACC.

An Auxiliary Power Module can be provided 
for bench testing Digitrip OPTIM 750 and 
1050 electronic trip units, or when the 
breaker is disconnected from the cell. The 
Auxiliary Power Module operates from a 
120 Vac supply and provides control power 
to test the trip unit.

 

Typical Specifications

 

Digitrip OPTIMizer

 

Hand-Held Programmer

The OPTIMizer plugs into the front of 
the trip unit and is powered by a nine 
volt battery. The Digitrip OPTIMizer 
hand held programmer accesses, dis-
plays, and configures information 
from OPTIM Trip Units.

Breaker Interface Module

Panel Mounted User Interface

The Breaker Interface Module can be 
mounted directly on the assembly or 
at a remote location and can be used 
to access, configure, and display infor-
mation from OPTIM Trip Units.

IMPACC Communications

Programming and Other Capabilities from a 
Personal Computer

All OPTIM programming, configura-
tion, advance warning, diagnostic, 
monitoring, and control capabilities 
can be accessed from a central person-
al computer using IMPACC Series III 
software.

Other software packages are available, 
including a Trip Curve Package that dis-
plays, configures, and coordinates 
time-current protection curves for OP-
TIM Trip Units and other devices that 
can be included on an IMPACC System.

Custom Billing Software, a stand alone 
application specific software package, 
provides the capabilities to determine 
energy usage data by individual depart-
ments or tenants in a facility...and then 
creates “electric bills” based on this data.

Waveform and harmonic display soft-
ware is capable of performing a wave-
form capture of phase currents A, B, C 
as well as neutral or ground. In addi-
tion, total harmonic distortion (THD) 
and individual harmonic contents can 
be displayed.

Summary of Contents for Digitrip OPTIM 750

Page 1: ...PTIM for power breakers are avail able in three configurations Long time short time and instanta neous LSI Long time short time instantaneous and ground fault protection LSIG Long time short time inst...

Page 2: ...a long delay setting Ir moves the whole curve including the short time portion to provide closer protection for bus and cables Depen dent curve shaping provides a wider range of available settings OPT...

Page 3: ...trip occurs OPTIM remembers the heating effect of this overload In the event that the current levels again exceed the pickup set point before the circuit has had time to cool from the original pickup...

Page 4: ...harmon ics and other related parameters with a high level of accuracy Current Monitoring OPTIM 750 and 1050 Digitrip OPTIM 750 and 1050 trip units are ca pable of monitoring currents in individual ph...

Page 5: ...no trip testing can be carried out with the breaker in the connected cell position using an OPTIMizer a BIM or IMPACC An Auxiliary Power Module can be provided for bench testing Digitrip OPTIM 750 an...

Page 6: ...Westinghouse Dig itrip OPTIM trip units for SPB or DS circuit breakers with the following features Interchangeable rating plugs shall establish the continuous trip ratings of each circuit breaker Rat...

Page 7: ...ional auxiliary power module to allow the breaker trip unit to be bench tested with a 120 volt external power source A hand held programming unit shall be pro vided to set change the network communica...

Reviews: