background image

DCF-3000 Installation, Operation & Maintenance 

 

DOM0000007, Revision A 

Page 6 of 7 

 

Maintenance 

To service the DCF-3000 filter unit, isolate it from the process air and 
electrical supply using proper lockout/tagout plant procedures. 
Depressurize and de-energize all sources of power. Utilize proper 
application of PPE for the process conditions. 

 

WARNING:

 

Equipment should be shut down and 

isolated from energy sources and other equipment 
before any inspection or servicing to prevent risk of 
shock or process fluid leakage. 

 

FAILURE TO FOLLOW THIS WARNING MAY LEAD TO DEATH, 
SEVERE INJURY OR PROPERTY DAMAGE. 

Maintenance Schedule 

Frequency of inspection is at the discretion of the customer and may 
need to be increased or decreased accordingly. The wear of certain 
items depends on how often the filter is used and the abrasiveness of 
the product being filtered. 

Weekly 

 

Inspection for leakage around the actuator shaft seal. 
To eliminate weeping, tighten that packing as necessary by 
tuning star wheel (Figure 1, item 6 or 13) clockwise. If the 
packing (Figure 1, item 7 or 15), has reach maximum 
adjustment and or leaking persists after adjustment disassemble 
the unit and replace the packing. 

Monthly 

 

Inspect the cleaning discs for excessive wear. Remove the 
cleaning discs and inspect. 

 

Remove the actuator lid assembly and inspect the inside of the 
filter element. Inspect the inside of the filter element for 
excessive wear. The lid seal (Figure 1, item 11)   should be 
replaced to maintain a proper seal. If the element is removed 
from the housing, the seals (Figure 2, item 7)   should be 
replaced to maintain a proper seal. Over time, gaskets will take 
on a permanent “set”. 

 

Inspect the actuator assembly. When the actuator begins to fail, 
the differential pressure will rise. This occurs because the 
actuator cannot sufficiently drive the cleaning disc assembly. 
Remove the actuator assembly and check for air leakage 
around the gland seal. Check for any side to side movement in 
the actuator shaft. If either of these problems exist, the actuator 
can be rebuilt (Figure 2, item 2)   Inspect the actuator shaft for 
damage or excessive wear. If damage exists to the shaft, the 
actuator shaft must be replaced.  

 

Troubleshooting 

Symptoms 

A

 

Actuator doesn’t operate properly 

B

 

Purge valve will not operate properly 

C

 

Leakage at lid seal 

D

 

Reduction in flow rate or high differential pressure 

E

 

Drop in filtrate quality 

Possible Faults 

A

 

Actuator doesn’t operate properly 
1

 

No power 

a

 

Check safety switch position. 

b

 

Check to see if the filter system is receiving adequate 
power. 

c

 

Check to see if the filter system is set to the proper 
voltage. 

d

 

Check all wiring connections. 

2

 

No air supply 

a

 

Check to see if the filter system is receiving adequate 
air. 

b

 

Check for air leaks. 

c

 

If included check to see if the air bleed valve is 
closed and the air block valve is open.  

d

 

Check to see if the airlines are connected to the 
correct ports. 

3

 

Actuator seals have worn out 

a

 

Check the air filter and water separator for operation. 

b

 

Replace the actuator 

4

 

Actuator installed improperly 

a

 

Confirm the element hold-down plates are properly 
installed and are securing the actuator. 

5

 

Faulty solenoid valve 

a

 

Check to see whether the manual override button on 
the solenoid valve actuates the cylinder. 

6

 

Actuator cleaning disc carrier is seized. 

a

 

Inspect and clean actuator assembly of built-up 
solids. 

7

 

Cleaning disc not cleaning the filter screen 

a

 

Inspect and clean the filter screen. 

b

 

Inspect and replace the cleaning disc. 

B

 

Purge valve will not operate properly 

1

 

No power 

a

 

Check to see if the filter system is receiving adequate 
power. 

b

 

Check to see if the filter system is set to the proper 
voltage. 

c

 

Check all wiring connections. 

2

 

No air 

a

 

Check to see if the filter system is receiving adequate 
air. 

b

 

Check for air leaks. 

c

 

Check to see if the air bleed valve is closed and the 
air block valve is open. 

d

 

Check to see if the airlines are connected to the 
correct ports. 

3

 

Damaged rotary Actuator seals 

a

 

Order a factory repair kit and replace the seals. 

4

 

Faulty solenoid valve 

a

 

Check to see whether the manual override button on 
the solenoid valve actuates the cylinder 

5

 

Damaged purge valve 

a

 

Replace or rebuild purge valve 

6

 

Debris caught in purge valve 

a

 

Remove debris from purge valve 

C

 

Leakage at lid seal 

1

 

Loose lid nuts/bolts 

a

 

Tighten lid/nut bolts. 

2

 

Dirty lid sealing surfaces 

a

 

Clean lid sealing surfaces 

3

 

Damaged sealing surfaces 

a

 

Repair or replace filter station 

4

 

Damaged lid O-ring 

a

 

Remove and replace with factory lid O-ring 

 
 

 
 
 

Summary of Contents for DCF-3000

Page 1: ...which travels across the surface of the screen These contaminants are deposited in a collection chamber at the bottom of the filter vessel where they are periodically purged out of the bottom port of...

Page 2: ...ice is required Pressure gauges are also recommended on all process connections 2 Connect the drain line customer supplied to the filter unit purge valve To avoid restricting purge flow the drain line...

Page 3: ...erential pressure between the inlet and outlet pressures should be used to determine stroking and purging rates Normal operation should exhibit low differential pressure of 3 5 psi that is maintained...

Page 4: ...removing two screws Figure 2 item 6 of element hold down plates Figure 2 item 5 and inspect the filter element for damage Damage may consist of deformation dents holes or blockage 10 Clean the element...

Page 5: ...010 250 59262 015 380 59263 024 610 59264 030 760 59265 045 1140 PACKING KITS MATERIAL STANDARD PACKING Figure 1 item 7 FLUID SEAL PACKING Figure 1 item 15 PART NO PART NO URETHANE 42958 45406 TEFLON...

Page 6: ...must be replaced Troubleshooting Symptoms A Actuator doesn t operate properly B Purge valve will not operate properly C Leakage at lid seal D Reduction in flow rate or high differential pressure E Dro...

Page 7: ...TIAL DAMAGES OR CONTINGENT LIABILITIES OUR MAXIMUM LIABILITY SHALL NOT IN ANY EVENT EXCEED THE CONTRACT PRICE FOR THE PRODUCT If you are interested in ordering spare parts or having service performed...

Reviews: