Replacement instructions
for CX with CX Plus controller
Instruction Leaflet
IL159026EN
Effective February 2022
Main screen
Measurement Mode
U Voltage ULL (V)
▼
U Voltage ULN (V)
▼
I Current (A)
▼
P active power (W)
▼
Q reactive power (VAR)
▼
∆ Q reactive power to target
▼
S apparent power (VA)
▼
THD U
▼
Har U (3rd harmonic U)
▼
Har U (5th harmonic U)
▼
Har U (7th harmonic U)
.
.
.
Har U (19th harmonic U)
▼
COS Phi (displacement power factor)
▼
PF (kW/kVA)
▼
APF (average power factor)
▼
F (frequency)
▼
t (temperature)
▼
thi (maximum temperature)
▼
OPh (operation hours)
Manual Mode
1 (Step 1)
▼
ON
▼
OFF
▼
2 (Step 2)
▼
ON
▼
OFF
▼
3 (Step 3)
▼
ON
▼
OFF
.
.
.
13 (Step 13)
▼
ON
▼
OFF
▼
14 (Step 14)
▼
ON
▼
OFF
Basic Programming Mode
(100 level menu)
Un (nominal voltage ULL)
▼
CT (CT ratio)
▼
PT (PT or VT ratio)
▼
Ai (automatic initializing)
▼
PFC (power factor control on/off)
▼
CP1 (target power factor)
▼
St (switching time delay)
▼
Out (outputs)
a
Setup
Advanced Programming Mode
(200–600 level menus)
push
▼
key for 3–5 seconds
Note:
Pressing the down arrow will take the
user back to the top of the list.
Note:
Pressing the down arrow again after 14
(Step 14) will take the user back to 1 (Step 1).
Manual screen
Setup screen
Basic programming screen
a
Firmware version dependent.
Note:
Pressing the down arrow key after Out
will take the user back to the top of the list.
Push the right arrow
key for 3–5 seconds.
Push the right arrow
key for 3–5 seconds.
INFO
Push the right arrow
key for 1 second.
Figure 4. Menu map