2
Instruction Leaflet
IL159026EN
Effective February 2022
Replacement instructions
for CX with CX Plus controller
EATON
www.eaton.com
6.
Press the up or down keys to scroll through submenus.
7.
Pressing the right key (enter) allows selection, entering the
Edit Mode, or accepts the edited values.
8.
In the Edit Mode, the left key (escape) or right key scroll left and
right to allow setting of the appropriate digit.
9.
Outside of Edit Mode, the left key exits to the next higher level.
10.
Press and hold the left key for approximately 3 seconds to
silence any alarms.
11.
Upon power on the controller displays the existing power factor
value (X.XX i) and enters the Automatic Control Mode.
a.
The “I” at the end indicates an inductive power factor and
would be appropriate for most installations.
b.
A “c” at the end indicates capacitive power factor and
suggests reactive power export and may not be appropriate.
Refer to the troubleshooting guide for resolution steps.
12.
Set up the basic parameters in the controller.
13.
From the main screen, press the down key to step through the
“INFO”, “MANUAL”, and “SETUP” modes.
14.
When “SETUP” is shown, press the right key to enter the
Menu 100.
15.
Press the right key and program and/or verify the
following values:
Un
Nominal voltage (factory programmed; customer
may verify)
Ct
CT-ratio (factory set to 600, which corresponds to 3000:5
current transformer ratio. Changing the CT ratio will
change the capacitor step sizes in 402 and those values
will have to be reprogrammed.
Pt
PT-ratio (factory programmed)
Ai
Start of automatic initialization (factory programmed)
PFC PF-control ON/OFF/HOLD (factory programmed)
CP1 Target-PF (customer to program)
St
Switching time delay (factory programmed; customer
may verify)
Out Output type of each stage (Auto/Alarm/Fixed Off/Fixed On)
(factory programmed; customer may verify)
16.
Once the Menu 100 is programmed, press the left key three
times to return to the main screen that displays the existing PF.
17.
From the main screen, press the left key to enter the
Measurement Mode to verify the measured values. See the
menu map for a list of designated parameters.
18.
Press the left key to return to the main screen that displays the
existing PF.
19.
To verify the capacitor bank is working, activate the controller in
Manual Control Mode and cycle through all the available steps.
ote:
N
The steps will switch on only after the factory-set capacitor stage
discharge time has elapsed.
20.
After each manual operation of the stage, the PF should change
in the right direction (for example, 0.70 i >> 0.78 i >> 0.85 i…).
21.
If the PF changes in the right direction, the capacitor bank
has been correctly commissioned. If not, please refer to the
troubleshooting guide.
22.
To switch the controller in Manual and Control Mode, press the
down key to step through the “INFO” mode to “MANUAL” mode.
23.
Press and hold the right key for approximately 3 seconds until “1”
displays, indicating the stage number 1 is available for control.
ote:
N
In Manual Mode, the controller freezes the stages in their existing
state (ON, OFF, or HOLD). Therefore, it is important to ensure that at the
end of this step, the controller is returned to the Automatic Control Mode
by pressing the left key to return to the main screen that displays the
existing PF.
24.
After activating all available steps, one should make note of the
displayed PF values, as that reading should be greater than or
equal to the target PF desired.
25.
If the displayed PF (with the electrical system fully loaded and
all steps energized) is less than the target PF, then the selected
capacitor bank is not sized adequately to raise the PF to the
desired value. The customer should either upgrade the capacity
of the capacitor bank or the target PF value should be decreased
to prevent “PF alarms”.