Arcflash Reduction Maintenance Switch 

Application and Installation

1.3 Example Calculation

The following is a calculation example for a 1600 A circuit breaker 

with a 1600 A sensor.  The time current graph (Figure 2) shows 

the circuit breaker settings before and after the Arcflash Reduc-

tion Maintenance Switch installation.
In this example, the following power system conditions exist:

Bolted fault current through the reductive 

device to fault location

= 40.00  kA

Arcing fault current calculated using 

IEEE Std. 1584

TM

-2002 = 19.98 

kA

85% of arcing fault current per

IEEE Std. 1584

TM

-2002

= 16.98 kA

Running load current through circuit breaker

= 1.12  kA

Transient motor in-rush current through breaker 

(6 × 1.6 × 480 A)

= 4.80  kA

Total running load + transient motor in-rush load = 5.92  kA

Setting choices for the RS are: 2.5 ×, 4.0 ×, 5.9 ×, 7.6 × or 

9.8 × rating plug value with a pickup tolerance of 

±

 10%.

1. Setting 9.8 × 1600 A =15.68 kA± 10% =pickup range of 

14.11 to 17.25 kA.

2. Setting 7.6 × 1600 A =12.16 kA± 10% =pickup range of 

10.94 to 13.38 kA.

3. Setting 5.9 × 1600 A =9.44 kA ± 10% =pickup range of 

8.50 to 10.38 kA.

4. Setting 4.0 × 1600 A =6.40 kA ± 10% =pickup range of 

5.76 to 7.04 kA.

5. Setting 2.5 × 1600 A =4.00 kA ± 10% =pickup range of 

3.60 to 4.40 kA. 

In this example, there are two appropriate setting choices (either 

5.9 [R3] × or 7.6 [R2] ×).  Either of these settings are above the 

total plus transient load (5.92 kA) and below the minimum arcing 

current (16.98 kA).  Either of these settings reduces the incident 

energy from 10.7 to 2.2 cal/cm

2

 (refer to the Table 2).

Table 2. Example Calculations for All RS Positions.

Note: 

* Arcing current low tolerances (85%) used.

REDUCTION

SETTING

BUS

kV

REDUCTIVE

DEV.

BOLTED

FAULT

kA

REDUCTIVE

DEV.

ARCING

FAULT

kA

TRIP /

DELAY

TIME

sec

ARCFLASH

BOUNDARY

in. (mm)

WORKING

DISTANCE

in. (mm)

INCIDENT

ENERGY

cal/cm

2

NFPA70E

PPE

CLASS

INACTIVE

0.48

40.00

19.98

0.24

106 (2692)

24 (610)

10.7

Class 3

[R5]

0.48

40.00

19.98

0.05

37 (940)

24 (610)

2.23

Class 1

[R4]

0.48

40.00

19.98

0.05

37 (940)

24 (610)

2.23

Class 1

[R3]

0.48

40.00

19.98

0.05

37 (940)

24 (610)

2.23

Class 1

[R2]

0.48

40.00

19.98

0.05

37 (940)

24 (610)

2.23

Class 1

[R1]

0.48

40.00

16.98

0.24

94 (2388)

24 (610)

8.97

Class 3*

BCS Switchgear Inc.

Switchgear | Circuit Breakers | Parts | Tech Support

bcsswitchgear.com | 888.599.0486

Need Help? 888.599.0486

Summary of Contents for CUTTLER-HAMMER Arcflash Reduction Maintenance...

Page 1: ...th the closing springs charged Trip open the breaker and be sure the stored energy springs are discharged before performing any work The breaker may trip open or the charging springs may discharge cau...

Page 2: ...t currents that flow through the circuit breaker associated with the Arcflash Reduction Mainte nance Switch This setting choice normally does not change unless there are future system modifications th...

Page 3: ...12 16 kA 10 pickup range of 10 94 to 13 38 kA 3 Setting 5 9 1600 A 9 44 kA 10 pickup range of 8 50 to 10 38 kA 4 Setting 4 0 1600 A 6 40 kA 10 pickup range of 5 76 to 7 04 kA 5 Setting 2 5 1600 A 4 00...

Page 4: ...T 7 SDPU 6 9600A SDT 0 2 I 2 T Out Manufacturer CUTLER HAMMER Description Digitrip RMS 510 910 Frame Model 1600 A Sensor Trip 1600 0 A Plug 1600 0 A Settings Phase LDPU 1 1600A LDT 7 SDPU 6 9600A SDT...

Page 5: ...it Kit A Trip the breaker and remove it from the cell Move the breaker to a clean well lit work area Note It is the responsibility of the installer to insure that the breaker and all original componen...

Page 6: ...efore 06 05 P N 256P726H04 follow the procedures detailed in Appendix A to install an updated DS Interface Board See Fig ure 5 to help identify which DS Interface Board is installed in the breaker Fig...

Page 7: ...nance Switch Components Installed on a Non DS Breaker Note The Arcflash Reduction Maintenance Switch can be installed on any Retrofitted breaker using an Eaton 10 series Digitrip trip unit 510 610 810...

Page 8: ...er Each installation of the Arcflash Reduction Maintenance Switch mode selector switch indicator light and battery holder may vary due to the type of breaker type of cell or components options mounted...

Page 9: ...that the harness connecting the mode selector switch to the indicator light is short so the indicator light must be installed in close proximity to the mode selector switch Mark the center of the moun...

Page 10: ...rface D Using the battery holder as a template mark then drill four 4 0 109 holes in the mounting surface to accept the battery holder mounting screws Figure 17 Marking the Battery Holder Mounting Hol...

Page 11: ...y with the indicator light housing The con tact block assembly is self locking Insert the contact block assembly into the indicator light until the locking click is heard Ensure it is locked into plac...

Page 12: ...on to the RSM making sure it is away from any moving parts within the breaker In routing the harness be sure to leave a service loop in the harness to facilitate racking the breaker in to and out of t...

Page 13: ...ce and away from any moving parts within the breaker F For more information on the RSM wiring and additional cus tomer connections refer to the wiring and connections draw ing Figure 29 G Disconnect t...

Page 14: ...evice clear all newly installed components and harnesses Step 4 Activating the RSM A To activate the RSM turn the mode selector switch to the Maintenance Mode position Close the LOTO cover then follow...

Page 15: ...variety of breakers with which the Arcflash Reduction Maintenance Switch Installation can be used some excess hardware may remain when the Arcflash Reduction Maintenance Switch Retrofit is complete SE...

Page 16: ...the 2 112 40 0 25 thread cutting pan head screws supplied B Note the connection point of each harness to the DS Interface Board positions P1 through P10 Mark each harness for reconnection later in th...

Page 17: ...it Mounting Frame Figure 34 New DS Interface Board Installed on the Trip Unit Mounting Frame G Using the remaining screws spacers and lock nuts removed in Step D or the supplied 112 40 hardware secure...

Page 18: ...erature Page 18 Effective May 2005 Arcflash Reduction Maintenance Switch Application and Installation Appendix B Sample Text Data Sheet SETTING MULT PICKUP R1 9 8 X R2 7 6 X R3 5 9 X R4 4 0 X R5 2 5 X...

Page 19: ...IL01906001E For more information visit www EatonElectrical com Instructional Literature Effective May 2005 Page 19 Arcflash Reduction Maintenance Switch Application and Installation Notes...

Page 20: ...d to be all inclusive or cover ing all contingencies If further information is required Eaton should be consulted NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WAR RANTIES OF FITNESS FOR A PARTICULAR P...

Reviews: