Instructional Literature

Page

 

12

Effective: May 2005

Arcflash Reduction Maintenance Switch

Application and Installation

Figure 24. Warning and Circuit Active Labels installed on the 

Mounting Surface.

Step 2: Final Wiring and Breaker Preparation

Figure 25. Overview: Final Wiring of the RSM, Mode Selector 

Switch, Indicator Light, and Battery Holder.

A. Plug the female connector on the mode selector switch bat-

tery harness onto the male receptacle at the back of the bat-

tery holder.  Open the battery holder door and install the 

battery.

Figure 26. Connecting the Battery Holder to the Mode Selector 

Switch Battery Harness.

B. If the breaker was removed from the cell to install the Arc-

flash Reduction Maintenance Switch, temporarily place the 

breaker back into the cell.

C. Route the mode selector switch harness from the switch loca-

tion to the RSM making sure it is away from any moving parts 

within the breaker.  In routing the harness, be sure to leave a 

service loop in the harness to facilitate racking the breaker in 

to and out of the cell.  If the mode selector switch was 

mounted to the cell door, also provide a service loop at hinge 

to allow the door to fully open and close.

CAUTION

MAKE SURE THE BREAKER IS IN THE RACKED-OUT POSITION AND 

REMAINS DE-ENERGIZED UNTIL FINAL WIRING IS COMPLETED.

CAUTION

DO NOT PERFORM ANY MAINTENANCE: INCLUDING BREAKER 

CHARGING, CLOSING, TRIPPING, OR ANY OTHER FUNCTION WHICH 

COULD CAUSE SIGNIFICANT MOVEMENT OF THE BREAKER WHILE 

IT IS ON THE EXTENSION RAILS.  DOING SO MAY CAUSE THE 

BREAKER TO SLIP FROM THE RAILS AND FALL, POTENTIALLY 

CAUSING SEVERE PERSONAL INJURY TO THOSE IN THE VICINITY

.

CAUTION

DO NOT LEAVE THE BREAKER IN AN INTERMEDIATE POSITION IN 

THE SWITCHGEAR CELL.  ALWAYS LEAVE IT IN THE CONNECTED, 

DISCONNECTED, OR (OPTIONAL) TEST POSITION.  FAILURE TO DO 

SO COULD LEAD TO IMPROPER POSITIONING OF THE BREAKER 

AND FLASHOVER, CAUSING DEATH, SERIOUS PERSONAL INJURY, 

AND / OR PROPERTY DAMAGE

Summary of Contents for CUTTLER-HAMMER Arcflash Reduction Maintenance...

Page 1: ...th the closing springs charged Trip open the breaker and be sure the stored energy springs are discharged before performing any work The breaker may trip open or the charging springs may discharge cau...

Page 2: ...t currents that flow through the circuit breaker associated with the Arcflash Reduction Mainte nance Switch This setting choice normally does not change unless there are future system modifications th...

Page 3: ...12 16 kA 10 pickup range of 10 94 to 13 38 kA 3 Setting 5 9 1600 A 9 44 kA 10 pickup range of 8 50 to 10 38 kA 4 Setting 4 0 1600 A 6 40 kA 10 pickup range of 5 76 to 7 04 kA 5 Setting 2 5 1600 A 4 00...

Page 4: ...T 7 SDPU 6 9600A SDT 0 2 I 2 T Out Manufacturer CUTLER HAMMER Description Digitrip RMS 510 910 Frame Model 1600 A Sensor Trip 1600 0 A Plug 1600 0 A Settings Phase LDPU 1 1600A LDT 7 SDPU 6 9600A SDT...

Page 5: ...it Kit A Trip the breaker and remove it from the cell Move the breaker to a clean well lit work area Note It is the responsibility of the installer to insure that the breaker and all original componen...

Page 6: ...efore 06 05 P N 256P726H04 follow the procedures detailed in Appendix A to install an updated DS Interface Board See Fig ure 5 to help identify which DS Interface Board is installed in the breaker Fig...

Page 7: ...nance Switch Components Installed on a Non DS Breaker Note The Arcflash Reduction Maintenance Switch can be installed on any Retrofitted breaker using an Eaton 10 series Digitrip trip unit 510 610 810...

Page 8: ...er Each installation of the Arcflash Reduction Maintenance Switch mode selector switch indicator light and battery holder may vary due to the type of breaker type of cell or components options mounted...

Page 9: ...that the harness connecting the mode selector switch to the indicator light is short so the indicator light must be installed in close proximity to the mode selector switch Mark the center of the moun...

Page 10: ...rface D Using the battery holder as a template mark then drill four 4 0 109 holes in the mounting surface to accept the battery holder mounting screws Figure 17 Marking the Battery Holder Mounting Hol...

Page 11: ...y with the indicator light housing The con tact block assembly is self locking Insert the contact block assembly into the indicator light until the locking click is heard Ensure it is locked into plac...

Page 12: ...on to the RSM making sure it is away from any moving parts within the breaker In routing the harness be sure to leave a service loop in the harness to facilitate racking the breaker in to and out of t...

Page 13: ...ce and away from any moving parts within the breaker F For more information on the RSM wiring and additional cus tomer connections refer to the wiring and connections draw ing Figure 29 G Disconnect t...

Page 14: ...evice clear all newly installed components and harnesses Step 4 Activating the RSM A To activate the RSM turn the mode selector switch to the Maintenance Mode position Close the LOTO cover then follow...

Page 15: ...variety of breakers with which the Arcflash Reduction Maintenance Switch Installation can be used some excess hardware may remain when the Arcflash Reduction Maintenance Switch Retrofit is complete SE...

Page 16: ...the 2 112 40 0 25 thread cutting pan head screws supplied B Note the connection point of each harness to the DS Interface Board positions P1 through P10 Mark each harness for reconnection later in th...

Page 17: ...it Mounting Frame Figure 34 New DS Interface Board Installed on the Trip Unit Mounting Frame G Using the remaining screws spacers and lock nuts removed in Step D or the supplied 112 40 hardware secure...

Page 18: ...erature Page 18 Effective May 2005 Arcflash Reduction Maintenance Switch Application and Installation Appendix B Sample Text Data Sheet SETTING MULT PICKUP R1 9 8 X R2 7 6 X R3 5 9 X R4 4 0 X R5 2 5 X...

Page 19: ...IL01906001E For more information visit www EatonElectrical com Instructional Literature Effective May 2005 Page 19 Arcflash Reduction Maintenance Switch Application and Installation Notes...

Page 20: ...d to be all inclusive or cover ing all contingencies If further information is required Eaton should be consulted NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WAR RANTIES OF FITNESS FOR A PARTICULAR P...

Reviews: