IL01906001E
For more information visit: www.EatonElectrical.com
Instructional Literature
Effective: May 2005
Page
13
Arcflash Reduction Maintenance Switch
Application and Installation
Figure 27. Routing of the Mode Selector Switch Harness and the
Service Loop.
D. Plug the male connector on the end of the mode selector
switch harness into the receptacle on the right side of the
RSM
.
Figure 28. Mode Selector Switch Harness Connected to the RSM.
E. Using the tie mounts and wire ties supplied, secure the mode
selector switch harness and battery harness to keep them in
place and away from any moving parts within the breaker.
F. For more information on the RSM wiring and additional cus-
tomer connections, refer to the wiring and connections draw-
ing (Figure 29).
G. Disconnect the mode selector switch harness from the RSM
and remove the breaker from the cell.
Figure 29. Arcflash Reduction Maintenance Switch Wiring and Connections.
SERVICE
LOOPS
LED
9V
ARCFLASH REDUCTION MAINTENANCE SWITCH WIRING SCHEMATIC
1 - RED 1
2 - BLACK 1
3 - WHITE 2
4 - BLACK 2
W2
B1
R1
B2
CUSTOMER NORMALLY OPEN
CUSTOMER COMMON
MOMENTARY
CONTACT
NOTE: THIS IS A DEDICATED
CIRCUIT. TAMPERING WITH OR
IMPROPER USE OF THIS
CIRCUIT COULD RESULT IN
DISABLING OF THE ARCFLASH
REDUCTION MAINTENANCE
SWITCH DEVICE AND/OR TRIP
UNIT RESULTING IN DEATH,
PERSONAL INJURY, OR
PROPERTY DAMAGE.