background image

I.L. 17403

Page 9

Effective 9/04

Interposing Relay

START

STOP

3

2

LOW VOLTAGE RELEASE WITH

TWO-WIRE PUSHBUTTON

 START-STOP OPERATION

Fig. 11   Two-Wire Control

Fig. 12    Two-Wire Control with IMPACC

TWO-WIRE CONTROL

Wire as shown in Figure 11 or 12. Install a #16 or #18

AWG stranded wire jumper from 3 to P. Keep strip length

to not more than 1/4 inch. 

Be sure to have jumper clear

power terminal.

 Attach and route twisted pair or shielded

wires to a remote reset/trip indicator module where pro-

vided.

Without Communications

Wire control devices in the same manner as conventional

motor controllers. Add the jumper.

With Communications

Attach a WPONI communications module and connect it

to the INCOM network daisy-chain fashion as shown in

Figures 4 and 12.
When wired as shown in Figure 12 with two-wire control,

the motor cannot be started or stopped via IMPACC. The

motor starter can only be reset and data obtained via

IMPACC where two-wire control is used.

Automatic reset should not be used with two-wire

control circuit where automatic starting of the motor

may be hazardous.

3

C

GENERIC

PILOT

CIRCUIT

(PLC)

RELAY

P and/or

P

5300C76D

5300C76C

Summary of Contents for Cutler-Hammer W200

Page 1: ...lent to the horsepower ratings shown in Table I are shown in Table II TABLE I MAXIMUM HORSEPOWER RATINGS 60HZ Controller Three Phase Horsepower At Size 200V 230V 460V 575V 3 25 30 50 50 4 40 50 100 100 PROGRAMMED FEATURES Advantage NEMA Size 3 starters and contactors are assembled with identical parts except for the circuit board to which the control wires are attached These circuit boards differ ...

Page 2: ...ressure contact kiss position when the control voltage is low or dips It prevents coil energization when the control voltage is too low for pro per pickup and yet maintains the armature sealed to the magnet with reduced current when adequate control voltage is present Maximum benefit of this low voltage response feature is obtained where the control voltage 110VAC 50HZ or 120VAC 60HZ is supplied b...

Page 3: ...and the star ter has the catalog suffix Y7 ground protection omitted the LED will blink twice every second but no trip will occur The internal trip indicator is visible only with the enclosure door open OVERLOAD SETTINGS The cutout in the arc box cover that provides access to the DIP switch is designed to accept a snap in clear plastic window Insert the window after initial DIP switch settings Fig...

Page 4: ...range of motor FLA in Column A that includes the FLA of OVERLOAD POSITION POSITION CLASS 7 6 10 0 0 20 0 1 30 1 0 NONE 1 1 Fig 3 DIP Switch Terminals and Reset TABLE IV SIZE 3 CURRENT RANGE ALL SETTINGS NOT SHOWN ARE EQUIVALENT TO 00000 Replace the arc box cover securely after making selections Column A Column B Service Factor Service Factor DIP Switch Trip Setting Rating Positions 1 15 to 1 25 1 ...

Page 5: ...Remote reset Consult the factory for information regarding other networks that may be used with WPONI and WPONIDNA modules CONTROL OPTIONS An Advantage non reversing motor controller may be used with two wire control or any one of three three wire control schemes The four point 3 P E C terminal block shown in Figure 3 is attached to the shock mounted circuit board and will give approximately 1 16 ...

Page 6: ...liampere leakage current will require a 3K 6 watt resistor in series with the P terminal and a 1K 2 watt resistor connected from the P to the C terminal Consult with your local Culter Hammer sales office re garding other leakage current values If both excessive latching and leakage currents exist it may be necessary to use an interposing relay Fig 5 Conventional Holding Circuit Three Wire Fig 6 Co...

Page 7: ...ined without an external auxiliary contact and jumper by using the internal holding circuit Wire as shown in Figure 7 or 8 Attach and route twisted pair or shielded wires to a remote reset trip indicator module where provided Without Communications Wire control devices in the same manner as conventional motor controllers except omit the holding circuit interlock With Communications Attach a WPONI ...

Page 8: ...M network daisy chain fashion as shown in Figures 4 and 10 Where IMPACC control is used the sel ected switch must be a type that breaks one circuit before making the other when switching from NORMAL to JOG When wired as shown in Figure 10 the motor can be started and stopped via IMPACC provided the selector switch is in the NORMAL position When the selector switch is in the JOG position the motor ...

Page 9: ...or module where pro vided Without Communications Wire control devices in the same manner as conventional motor controllers Add the jumper With Communications Attach a WPONI communications module and connect it to the INCOM network daisy chain fashion as shown in Figures 4 and 12 When wired as shown in Figure 12 with two wire control the motor cannot be started or stopped via IMPACC The motor start...

Page 10: ...HMCP CL Type CB CL4 Current Limiter Thermal Mag 150A 100 000A 100 000A 600V HFD CL Plus CL5 600R63A Marked GMCP 42 000A 240V GMCP Magnetic Only 25 000A 480V Type CB2 100A Marked HMCP 100 000A 480V HMCP 50 000A 600V 100A Marked HMCPE 100 000A 480V HMCPE TABLE VI SIZE 3 SHORT CIRCUIT RATINGS TABLE NOTES 1 Instantaneous Adjustable Trip 2 Circuit Breaker 3 Inverse Time Circuit Breaker 4 Instantaneous ...

Page 11: ...or to pick up c Terminals E and C must be energized to obtain a tripped indication d An overload relay in a tripped condition caused by a phase loss or a ground fault must be reset with control power ON e Each DIP switch handle must be in the full ON or full OFF postion A Type WCMU central monitoring unit can be of great assistance in troubleshooting TABLE VIII AUXILIARY CONTACTS AND TIE POINTS Ca...

Page 12: ...96 volts for Model E or later may be supplied to terminals 3 and P for remote control TABLE IX AUXILIARY CONTACT RATINGS Voltage Make Break NEMA A600 120 600VAC 7200VA 720VA 28 120VAC 60A 6A NEMA Q300 28 300VDC 69VA 69VA TABLE X RENEWAL PARTS Description Order Replacement Contacts Size 3 WCK33 Replacement Contacts Size 4 WCK43 Replacement Coil 110 120V 1A48101G01 Replacement Circuit Board See Tabl...

Page 13: ...he Model Designation can be determined by the 1st character of the Model listed on the nameplate label on the front of the device i e A B C D F P or R II Category CB replacement circuit board III Function C contactor O overload relay S starter IV Size 3 size 3 4 size 4 V Control voltage and frequency F 110 120 volts 60 Hz N 110 volts 50 Hz VI Suffix to indicate modifications that alter the charact...

Page 14: ...e arc box cover screws to 12 18 lb in Magnet Armature Assembly Self alignment and permanent air gap features of the mag net make replacement unnecessary Mating pole face sur faces should be kept clean MAINTENANCE TURN OFF POWER This industrial type control is designed to be installed op erated and maintained by adequately trained workmen These instructions to not cover all details variations or co...

Reviews: