Intelligent Technologies Modbus to QCPort Adapter Manual
January 2006
MN05002002E (C)
For more information visit
www.eatonelectrical.com
Page 64
Modbus Adapter Configuration (holding register area)
Description Modbus
Register
Size
(Reg)
Usage Read/
Write
Modbus Adapter
Serial Number
7505
2
This devices serial number
R
Modbus Adapter
Hardware Revision
7507
1
This devices hardware revision
number
R
Modbus Adapter
Firmware Revision
7508
1
Major firmware ware revision
R
Modbus Adapter
Firmware Build
7509
1
Minor firmware Build
R
Catalog Number
7510
16
ASCII text product description
R
Connection Timeout 7526
1
milli-second connection timeout. 0 =
disabled (default), increments of
200ms (automatically rounds up to
the nearest 2000ms)
R/W
TCP/IP Configuration (holding register area)
Description Modbus
Register
Size
(Reg)
Usage Read/
Write
MAC ID
7527
3
48 bit Hardware address
R
Address
7530
2
The current active IP address
HH.HL.LH.LL
Word 7530 - HH HL
Word 7531 - LH LL
R/W
Address mode
7532
1
0 – 192.168.10.1
1 – Static (will save current IP
address)
2 – Bootp (default)
R/W
Subnet Mask
7533
2
The current active subnet mask
HH.HL.LH.LL
Word 7533 - HH HL
Word 7534 - LH LL
R/W
Default Gateway
7535
2
The currently set default Gateway
HH.HL.LH.LL
Word 7535 - HH HL
Word 7536 - LH LL
R/W
Connection Limit
7537
1
Number of Modbus socket
connections allowed
R/W
Modbus TCP Slave
Address
7538
1
The MBAP header unit ID which this
Modbus Adapter will respond to
(default 1)
R/W