Page 16
I.L.15.01.T.K
.
Effective June 2000
10. Summary of Options
Option
#
Features
Standard/Optional
1
TDNE - Time delay Normal to Emergency
Standard
2
TDES - Time delay Engine Start
Standard
3
TDEN - Time delay Emergency to Normal
Standard
4
TDEC - Time delay Engine Cool-down
Standard
5B
1
Φ
Undervoltage/Underfrequency
Standard
5C
1
Φ
Overvoltage/Overfrequency
Optional - Programmed
5D
1
Φ
Undervoltage
Optional - Programmed
5E
1
Φ
Overvoltage
Optional - Programmed
5F
3
Φ
Undervoltage
Optional - Programmed
5G
3
Φ
Overvoltage
Optional - Programmed
5J
3
Φ
Undervoltage/Underfrequency
Optional – Programmed
5K
3
Φ
Overvoltage/Overfrequency
Optional – Programmed
6D
Maintained 2-Position Test Selector (Auto/Test)
Standard - External Contact
6H
Maintained 4 –Position Test Selector (Auto/Test/Man./Eng.
Start)
Optional - External Contact
8C
Bypass Time Delay Normal to Emergency
Optional - External Contact
8D
Bypass Time Delay Emergency to Normal
Optional - External Contact
8M
Bypass Time Delay Global (Both Directions)
Optional - External Contact
10
Preferred Source
(MP1-E Only)
Optional – External Contact
12C
Normal Position
Standard (On faceplate)
12D
Emergency Position
Standard (On faceplate)
12G
Normal Source Available
Standard (On faceplate)
12H
Emergency Source Available
Standard (On faceplate)
16B
Normal Side and Emergency Side
Optional - External Contact
16E
Emergency Side Only
Optional - External Contact
16N
Normal Side Only
Optional - External Contact
23C
No Load Exercise
Standard
23D
Load Exercise with Failsafe
Standard
26A
3
Φ
Undervoltage
Standard
26B
1
Φ
Undervoltage
Optional – Programmed
26C
3
Φ
Overvoltage
Optional – Programmed
26D
1
Φ
Overvoltage
Optional – Programmed
26E
1
Φ
Underfrequency
Optional – Programmed
26D
Area Protection
Optional – External Contact
26F
1
Φ
Overfrequency Monitor
Optional – Programmed
26H
1
Φ
Undervoltage / Underfrequency
Optional – Programmed
29J
Manual Return to Normal
(MP1-E Only)
Optional – External Contact
32A
Time Delay Neutral Global (Both Directions)
Optional – Programmed
32B
Time Delay Neutral – (Only on Transfer)
Optional – Programmed
32C
Time Delay Neutral – (Only on Retransfer)
Optional – Programmed
35A
Pretransfer (From Norm. to Emerg. Only)
(MP1-E Only)
Optional - Programmed
35B
Pretransfer (From Emergency to Normal)
(MP1-E Only)
Optional - Programmed
35C
Pretransfer (Global – Both Directions)
(MP1-E Only)
Optional - Programmed