![background image](http://html1.mh-extra.com/html/eaton/cutler-hammer-mp1-series/cutler-hammer-mp1-series_instructions-manual_4022836010.webp)
Page 6
I.L.15.01.T.K
.
Effective June 2000
Figure 3
-
Typical Power Panel for 200-1200A models
4.3 Table 1 - SYSTEMS COORDINATION INFORMATION –
WITHSTAND, CLOSING & INTERRUPTING RATINGS
Ratings when used with upstream
breaker (kA)
Ratings when used with upsteam
fuse (kA)
ATS
Ampere
Rating
240V
480V
600V
Max Fuse
Rating
Fuse
Type
600V
30
100
65
25
200
J,T
200
70
100
65
25
200
J,T
200
100
100
65
25
200
J,T
200
150
100
65
25
400
J,T
200
225
100
65
35
400
J,T
200
300
100
65
35
400
J,T
200
400
100
65
35
600
J,T
200
600
65
50
25
800/1200
J,T
100/200
800
65
50
25
1200/1600
L
100/200
1000
65
50
25
1600
L
200
1200
65
50
25
1600
L
200