background image

Effective 7/1/2003

Page 11

I.L. 70C1037H04

associated rating plug must match the current sensor

rating specified on the plug label. The current sensor rating

can be viewed through openings in the back of the breaker.

2.5  Current Sensors (Magnum Frames greater than 3200A)

The six (3-pole) or eight (4-pole) current sensors installed

in the circuit breaker are located on the lower conductors.

The poles are paralleled and the corresponding current

sensors are also paralleled (see Figure 2.3). For example,

a 4000A breaker phase rating has two 2000:1 current

sensors wired in parallel, which provides an overall ratio of

4000:2. The auxiliary current transformers have a ratio of

20:1 for this size breaker which further steps down the

rated current to 100 milliamperes and is equivalent to

100% (

I

n) to the Digitrip.

3.0  PRINCIPLES OF OPERATION

3.1  General

All models of trip units are designed for industrial circuit

breaker environments where the ambient temperatures can

range from –20

°

 C to +85

°

 C but rarely exceed 70

°

 to 75

°

C. If, however, temperatures in the neighborhood of the trip

unit exceed this range, the trip unit performance may be

degraded. In order to insure that the tripping function is not

compromised due to an over-temperature condition, the

microcomputer chip has a built-in over-temperature

protection feature, factory set to trip the breaker if the chip

temperature is excessive. If over-temperature is the reason
for the trip the red Long Delay Time LED will flash.

The Digitrip uses the Eaton custom-designed 

CHip

(Cutler Hammer Integrated Processor) chip, an integrated

circuit that includes a microcomputer to perform its

numeric and logic functions. The principles of operation of

the trip unit are shown in Figure 3.1.

All sensing and tripping power required to operate the

protection function is derived from the current sensors in

the circuit breaker. The secondary currents from these

sensors provide the correct input information for the

protection functions, as well as tripping power, whenever

the circuit breaker is carrying current. These current

signals develop analog voltages across the current viewing

resistors. The resulting analog voltages are digitized by the

CHip

™ (Cutler Hammer Integrated Processor) chip.

The microcomputer continually digitizes these signals.

This data is used to calculate true RMS current values,

which are then continually compared with the protection

function settings and other operating data stored in the

memory. The software then determines whether to initiate

protection functions, including tripping the breaker through

the Trip Actuator.

Table 2.2 Ground (Earth) Fault Current Settings

2.4  Current Sensors (Magnum Frames less than or equal to

3200A)

The three (3-pole) or four (4-pole) primary current sensors

are installed internally in the circuit breaker on the lower

conductors of the breaker. The current sensor rating

defines the breaker rating (

I

n). For example, 2000A:1A

sensors are used on a 2000A rated breaker. There are four

auxiliary current transformers with a ratio of 10:1 which

further step down the rated current to 100 milliamperes,

which is equivalent to 100% (

I

n) to the Digitrip.

The primary current sensors produce an output proportional

to the load current and furnish the Digitrip  with the informa-

tion and energy required to trip the circuit breaker when

functional protection settings are exceeded.

If a set of current sensors with a different ratio are installed

in the field, the rating plug must also be changed. The

Ground Fault Current Settings

(Amperes)

1

Installed

Sensor and

Rating Plug

(Amperes) 

I

n

.25

.30

.35

.40

.50

.60

.75

1.0

100

25

30

35

40

50

60

75

100

200

50

60

70

80

100

120

150

200

250

63

75

88

100

125

150

188

250

300

75

90

105

120

150

180

225

300

400

100

120

140

160

200

240

300

400

600

150

180

210

240

300

360

450

600

630

158

189

221

252

315

378

473

630

800

200

240

280

320

400

480

600

800

1000

250

300

350

400

500

600

750 1000

1200

300

360

420

480

600

720

900 1200

1250

312

375

438

500

625

750

938

1250

1600

400

480

560

640

800

960

1200 1600

2

2000

500

600

700

800

1000

1200

1500

2

2000

2

2500

625

750

875

1000

1250

1500

1875 2500

3000

750

900

1050

1200

1500

2

1800

2

2250

2

3000

2

3200

800

960

1120

1200

1600

2

1920

2

2400

2

3200

2

4000

3

1000

1200

1400

2

1600

2

2000

2

2400

2

3000

2

4000

2

5000

3

1250

2

1500

2

1750

2

2000

2

2500

2

3000

2

3750

2

5000

2

6000

1500

2

1800

2

2100

2

2400

2

3000

2

3600

2

4500

2

6000

2

6300

3

1575

1890

2205

2520

3150

3780

4725 6300

1. Tolerance on settings are ±10% of values shown.
2. On Models 520 LSIG, 520M and 520MC LSIG, the shaded values are set to a

maximum   trip value of 1200 amperes for NEC.

3. See Section 2.5.

Courtesy of NationalSwitchgear.com

Summary of Contents for Cutler-Hammer Magnum Digitrip 220+

Page 1: ...9 2 Remote Master Computer 24 4 9 3 INCOM Network Interconnections 24 5 0 Test Procedures 25 5 1 General 25 5 2 When to Test 25 5 3 Functional Field Testing 25 5 3 1 Field Test Kit 25 5 3 2 Handheld...

Page 2: ...d can be replaced or upgraded in the field by the customer This instruction book specifically covers the application of Digitrip Trip Units see Figure 1 1 installed in Magnum and Magnum DS Breakers Th...

Page 3: ...Delay Time I2t at 6 x Ir Protection Long Delay Thermal Memory 0 4 1 0 x In 2 24 Seconds Yes 0 4 1 0 x In 2 24 Seconds Yes 0 4 1 0 x In 2 24 Seconds Yes 0 4 1 0 x In 2 24 Seconds Yes Short Short Delay...

Page 4: ...Alarm NA X X X Remote Messages Trip Long Delay Trip X X X X Short Delay Trip X X X X Instantaneous Trip X X X X Ground Trip NA X NA X Over temperature Trip X X X X Plug Trip plug problem X X X X MCR...

Page 5: ...1 and 520MC CLSI model Fig 3 4 1 can be used on 3 pole or 4 pole circuit breakers for the protection of the neutral circuit Only these four models can provide neutral protec tion although models MLSI...

Page 6: ...e door to release the rating plug from the trip unit To remove the trip unit from the circuit breaker deflect the spring clip to release the unit from the steel mounting plate Pull the unit to disenga...

Page 7: ...splay data until load current reaches approxi mately 30 1 phase or 10 3 phase of the In rating 1 6 2 Ground Alarm A second function of the module is to provide either a ground trip or ground alarm onl...

Page 8: ...hest value that can be presented is 9999 Any fault currents greater than this value will be shown as HI Pushing the Reset pushbutton will clear this data Also related to the phase value after a trip e...

Page 9: ...INJURY Figure 2 1 Tripping Circuit for a Typical Magnum Breaker Partial OBSERVE POLARITY MARKINGS ON THE TRIP AC TUATOR LEADSAND CONNECT THEM PROPERLY USING THE INSTRUCTIONS PROVIDED 2 2 Low Energy Tr...

Page 10: ...ION IF THE SENSOR CONNECTIONSARE INCORRECT A NUISANCE TRIP MAY OCCUR ALWAYS OBSERVE THE POLARITY MARKINGS ON THE INSTALLATION DRAW INGS TO INSURE CORRECT GROUND FAULT EQUIP MENT PERFORMANCE CONDUCT FI...

Page 11: ...ed Processor chip The microcomputer continually digitizes these signals This data is used to calculate true RMS current values which are then continually compared with the protection function settings...

Page 12: ...1 3 3 2 2 1 1 K2 8 B 4 Load Notes B 6 K1 4 K1 3 10 1 10 1 AUX CT K2 9 K2 1 K2 7 B 5 B 7 K1 5 K1 2 Black Trip Actuator LB LC LA K1 6 K1 7 K1 8 K1 9 1 1 1 Source Load K2 8 K2 9 B 4 B 6 20 1 AUX CTs 20 1...

Page 13: ...at the PC board donut transformer to sense ground fault via element R 5 Do not jumper on secondary contacts B 6 B 7 This will defeat all ground fault protection in application for 4 pole breaker Grou...

Page 14: ...Effective 7 1 2003 Page 14 I L 70C1037H04 Figure 2 6 Source Ground Fault Sensing Scheme for 3200A Frame Figure 2 7 Source Ground Fault Sensing Scheme for 4000A Frame Courtesy of NationalSwitchgear com...

Page 15: ...N N Digitrip Ground Sensor Breaker M2 trips since this is the only breaker seeing the I fault via element R No jumper on B 6 B 7 terminals all breakers are programmed for standard Residual Ground Faul...

Page 16: ...o cycles following an initial circuit breaker closing operation The Making Current Release will trip the circuit breaker instantaneously and flash the Instantaneous LED 3 4 Zone Interlocking 520 famil...

Page 17: ...See Section 3 3 Trip Actuator LED Pulse Circuit Battery 3V Ground Alarm Power Supply Optional for 520M Required for 520MC FET Trip See Section 1 2 Trip LED Rating Plug Integrated Processor C ip H TM...

Page 18: ...Effective 7 1 2003 Page 18 I L 70C1037H04 Figure 3 2 1 Digitrip 220 PLI Figure 3 2 3 Digitrip 520 LSIG Figure 3 2 2 Digitrip 520 LSI Figure 3 2 4 Digitrip 520i WLSIG Courtesy of NationalSwitchgear com...

Page 19: ...tive 7 1 2003 Page 19 I L 70C1037H04 Figure 3 3 1 Digitrip 520M MLSI Figure 3 3 3 Digitrip 520M MLSIG Figure 3 3 2 Digitrip 520M MLSIA Figure 3 3 4 Digitrip 520Mi MWLSIG Courtesy of NationalSwitchgear...

Page 20: ...ive 7 1 2003 Page 20 I L 70C1037H04 Figure 3 4 1 Digitrip 520MC CLSI Figure 3 4 2 Digitrip 520MC CLSIA Figure 3 4 3 Digitrip 520MC CLSIG Figure 3 4 4 Digitrip 520MC CWLSIG Courtesy of NationalSwitchge...

Page 21: ...S 4 1 General Before placing any circuit breaker in operation set each trip unit protection setting to the values specified by the engineer responsible for the installation The number of settings that...

Page 22: ...er The action of the LTM must be considered when performing multiple Long Delay Time tests See Section 5 4 4 4 Short Delay Current Setting There are 8 available Short Delay Current Settings as illustr...

Page 23: ...Settings 4 9 INCOM Digitrip 520MC Models only INCOM communication to a host computer or a BIM is possible with the Digitrip 520MC unit The address range is 001 through 999 The factory default address...

Page 24: ...e it and display it in a useful manner Following an over current trip operation the sequence of coded data varies slightly The cause of trip the value the phase or ground current responsible for the t...

Page 25: ...he Magnum Test KitAdapter 8779C02G04 can be used to test the trip unit and breaker 5 0 TEST PROCEDURES 5 1 General WARNING DO NOT ATTEMPT TO INSTALL TEST OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT I...

Page 26: ...rd in the Test Kit and serve to power up the display on the 520M trip unit LED s A and B function to represent sufficient battery voltage from both the single Lithium cell and the six Alkaline batteri...

Page 27: ...ved from the Cell Apply the same current as described above through any two phases of the breaker The breaker should not trip and the alarm indicator if one is supplied should not operate Repeat the t...

Page 28: ...d then replace battery See Figure 6 1 This will activate the battery Check the battery status by depressing the battery test pushbutton 6 2 Battery Check The battery is a long life lithium camera type...

Page 29: ...tion of the protection function of the breaker without affecting its short circuit current capability For the Digitrip 520 family of trip units this is implemented by changing the current sensors and...

Page 30: ...TTINGS Circuit No Address Breaker Shop Order Reference PER UNIT MULTIPLIERS Rating Plug Amperes In Ir Continuous Ampere Rating LDS x In Trip Function Per Unit Setting Multi Ampere Equivalent Setting T...

Page 31: ...uit No Address Breaker Shop Order Reference Settings Reference Trip Function Orig 0 Rev 1 Rev 2 Rev 3 Instantaneous Long Delay Setting Long Delay Time Short Setting Short Time Ground Fault Setting Gro...

Page 32: ...orm GROUND FAULT TEST RECORD FORM Ground Fault Test Record should be retained by those in charge of the building s electrical installation in order to be available to the authority having jurisdiction...

Page 33: ...to the feeder trip unit the feeder will send a restraint interlocking signal to Z1 Main and feeder trip units will begin to time out and in the event that the branch breaker does not clear the fault t...

Page 34: ...m power conductors DO NOT GROUND any Zone Interlocking wiring The maximum distance between two farthest breakers on different zones from the ZO downstream to ZI upstream terminals is 250 feet 76m A ma...

Page 35: ...lfunctioning Replace trip unit There actually is a ground fault Find location of the fault On 4 wire residual systems the neutral current sensor may not have the correct ratio or be properly connected...

Page 36: ...ently adding Aux Power and then depress Reset pushbutton to fully clear trip buffer See also Note in Section 5 3 2 2 Light load Check breaker ordering information Refer to Sections 1 6 and 1 6 1 LCD D...

Page 37: ...Effective 7 1 2003 Page 37 I L 70C1037H04 Appendix C Typical Breaker Master Connection Diagram Courtesy of NationalSwitchgear com...

Page 38: ...mon and SHielD Three Baud rates of 1200 9600 or 19200 are selectable via programming switch for the MODBUS network The INCOM Baud rate is fixed at 9600 Baud B 2 B 1 1 Magnum Breaker 2 B 2 B 1 Magnum B...

Page 39: ...RRANTIES EXPRESSED OR IMPLIED INCLUD ING WARRANTIES OF FITNESS FORAPARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM THE COURSE OF DEALING OR US AGE OF TRADE ARE MADE REGARDING THE INFO...

Page 40: ...Effective 7 1 2003 Page 40 I L 70C1037H04 Cutler Hammer Pittsburgh PAU S A Effective 7 1 2003 Printed in U S A Courtesy of NationalSwitchgear com...

Reviews: