Instruction Leaflet 

I. L. 29-886B

Effective August 2011

 Instructions for Digitrip RMS 610 Trip Unit

 

 

eaton corporation

 www.eaton.com

Figure 7. Digitrip RMS 610 Type LSG.

Figure 8. Digitrip RMS 610 Type LSIG.

NOTICE

AFTER EACH TRIP OPERATION (WHETHER DUE TO OVERCURRENT 

PROTECTION OR REMOTE CONTROL) THE AUTOMATIC LOCKOUT-AFTER-

TRIP FEATURE OF THE DIGITRIP RMS 610 TRIP UNIT MAINTAINS THE 

CIRCUIT BREAKER IN A "TRIP-FREE" CONDITION, PROVIDED 120 VAC 

CONTROL POWER REMAINS AVAILABLE TO THE POWER / RELAY MODULE.  

THE TRIP UNIT MUST BE RESET BEFORE THE CIRCUIT BREAKER CAN BE 

CLOSED AGAIN. THE RESET CAN BE ACCOMPLISHED EITHER LOCALLY BY 

PRESSING AND RELEASING THE "TRIP RESET' PUSH BUTTON (SEE FIGURE 

1).

After an over-current trip operation, the following information is 

stored in the Trip Unit memory:

• 

the cause of trip;

• 

the values of currents at time of trip .

1.1.3  Discriminator (High Initial Current Release)  

        (For Types LS and LSG Trip Units Only)

When the Digitrip RMS 610 Trip Unit is not equipped with an 

adjustable instantaneous protection setting, i .e . types LS or LSG, a 

DlScriminator circuit (or high initial current release) is provided .  The 

non-adjustable release is pre-set at eleven (11) times the installed 

rating plug current (I

n

) .  The DlScriminator is enabled for approximate-

ly ten (10) cycles following the initial current flow through the circuit 

breaker, provided the load current exceeds approximately 10% of the 

circuit breaker frame (or current sensor) rating .  Whenever the load 

current falls below 10% the discriminator is rearmed .  The release, 

once rearmed will remain enabled until the load current passing 

through the circuit breaker has exceeded the 10% value for 10 

cycles .  The DlScriminator trips the circuit breaker, instantaneously 

the "OVERRIDE / DIS" LED will light "RED", and the Display will read 

"DISC"

 .

In the event the breaker is not intended to trip out on a circuit 

whose current could initially be higher than 11 x I

n

, it is possible to 

make the DlScriminator inactive .
If a circuit breaker would close onto a high short-circuit current, 

when the DlScriminator is inactive, type 

LS

 or 

LSG

 Trip Units will 

rely on the short-time delay function before tripping . If the fault 

current exceeds the short-time withstand current capability of the 

circuit breaker, the OverRlDe protection function will trip the breaker 

without delay (see Section 1 .1 .4) .  Also, please see Section 1 .1 .5 for 

other exceptions when Zone lnterlocking is employed .
The DlScriminator (high initial current release) can be made inactive 

by turning the "

OVERRIDE/

" setting switch (nearest the bottom edge 

of the Trip Unit) from the "

DIS

" position, to the "[blank]" position (see 

Figures 4 and 7) .

otee:

N

This switch has eight (8) positions, and seven (7) of the positions show 

"DIS" in the window, ONLY ONE position shows "[blank]" .

otee:

N

When the "OVERRIDE/"window shows "[blank]", the only fast-acting  

high short-circuit protection available is the OVERRIDE (Fixed  

Instantaneous) (see Section 1 .1 .4 .) .

Summary of Contents for Cutler-Hammer Digitrip RMS 610

Page 1: ...Effective August 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 886B Instructions for Digitrip RMS 610 Trip Unit...

Page 2: ...Replacing the Back up Battery 20 5 References 20 5 1 Digitrip RMS Trip Assemblies 20 5 2 Type DS Low Voltage AC Power Circuit Breakers 20 5 3 Type DS II Low Voltage AC Power Circuit Breakers 20 5 4 Ty...

Page 3: ...considered to be all inclusive or covering every application or circumstance which may arise If you have any questions or need further information or instructions please contact your local representa...

Page 4: ...rs provide the correct input information for the protector func tions as well as tripping power whenever the circuit breaker is carrying current These signals develop analog voltages across the approp...

Page 5: ...ate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 610 Trip Unit is availab...

Page 6: ...1 1 Ground Fault Protection Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1...

Page 7: ...Effective August 2011 Instructions for Digitrip RMS 610Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 610 Type Ll Figure 4 Digitrip RMS 610 Type LS Figure 5 Digitrip RMS 610 Type LSI...

Page 8: ...current exceeds approximately 10 of the circuit breaker frame or current sensor rating Whenever the load current falls below 10 the discriminator is rearmed The release once rearmed will remain enabl...

Page 9: ...the other breaker F can not cause breaker M to trip caution IF ZONE INTERLOCKING IS NOT TO BE USED I E STANDARD TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECT...

Page 10: ...Phase B Current lb kA Phase C Current lc kA X X X X X X X X X X X X X X X X X X Ground Current lg kA Neutral Current ld kA n n n X X X 1 2 1 1 Local Messages Table 3 DISC DISCriminator GNDT GrouND Tri...

Page 11: ...mory error Protection functions still operate but may be up to 12 out of tolerance Replace trip unit at first opportunity 1 2 2 1 SDT Short Time Delay Trip Breaker tripped because phase current exceed...

Page 12: ...still function to protect the circuit but the calibration may be degraded by a few percent The Time Current Curve tolerances may be exceed ed in some cases by as much as 12 It is not necessary to tri...

Page 13: ...60 640 680 720 760 800 A Plug In 1600 A LDPU Ir 800 960 1120 1280 1360 1440 1520 1600 A Note N Rating plugs from Digitrip models 500 600 700 800 CANNOT be used with model 610 Trip Units The connection...

Page 14: ...as appli cable Even without available external control power once the load cur rent through the circuit breaker exceeds approximately 20 40 if single phase of the frame current sensor rating the green...

Page 15: ...Rating of the cir cuit breaker Instantaneous and ground current settings are defined in multiples of In To illustrate the effect of each protection curve setting simulated Time Current curves are pict...

Page 16: ...Curve referenced in Section 5 Figure 14 Short Delay Current Settings Available Settings 12 15 20 24 I Seconds at 6 Times 6 x Long Time Delay Sec at 6 x Ir Ir 4 I r Long Delay Setting 2 4 7 10 S1 and...

Page 17: ...0 1200 5000 1200 1200 1200 1200 1200 1200 1200 1200 Tolerances on settings are 10 of values shown Refer to Type DS Type SPB or Series C R Frame supplemental instruction leaflets given in Section 5 for...

Page 18: ...ts of the Trip Unit and two settings GF and GFT are provided for testing the ground element Figure 19 Integral Test Panel Lower Right Corner of Trip Unit caution A SETTING OF EITHER 6T OR GFT WILL TRI...

Page 19: ...lly affect ground fault test results but if Ground Fault tests are repeated quickly the GTM can make the breaker appear to trip too soon Note N To STOP a TEST initiated via the integral test panel PRE...

Page 20: ...F THE 120 VAC CONTROL POWER TO THE POWER RELAY MODULE IS LOST THEN AFTER AN OVER CURRENT OR SHORT CIRCUIT TRIP NO LEDS WILL BE LIGHTED RED TO INDICATE THE REASON FOR THE TRIP The replacement battery s...

Page 21: ...the event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will init...

Page 22: ...power to the load circuit Note N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message wou...

Page 23: ...23 Instruction Leaflet I L 29 886B Effective August 2011 Instructions for Digitrip RMS 610Trip Unit eaton corporation www eaton com Notes...

Page 24: ...between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the con...

Reviews: