![Eaton Cutler-Hammer Digitrip RMS 610 Instruction Leaflet Download Page 3](http://html1.mh-extra.com/html/eaton/cutler-hammer-digitrip-rms-610/cutler-hammer-digitrip-rms-610_instruction-leaflet_3827016003.webp)
3
Instruction Leaflet
I. L. 29-886B
Effective August 2011
Instructions for Digitrip RMS 610 Trip Unit
eaton corporation
www.eaton.com
important Safety instructions
WARNING
DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON
EQUIPMENT WHILE IT IS ENERGIZED. DEATH OR SEVERE PERSONAL
INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT.
ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING
WITH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED
SAFETY PROCEDURES. EATON CORPORATION IS NOT LIABLE FOR THE
MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS.
It is strongly urged that the User observe all recommendations,
warnings and cautions relating to the safety of personnel and equip-
ment, as well as all general and local health and safety laws, codes,
and procedures .
The recommendations and information contained herein are based
on experience and judgment, but should not be considered to be
all-inclusive or covering every application or circumstance which
may arise . If you have any questions or need further information
or instructions, please contact your local representative, or the
Customer Support Center for the type of circuit breaker you have .
Figure 1. Digitrip RMS 610 Trip Unit Type LSIG with Rating Plug.
Green LED's
Light to Identify
Which Value Is
Presently Being
Displayed in
Window
Catalog Number
LED's light "Red"
to indicate cause
of trip
Time-Current
Curve for Ground
Protection
SPB Rating Plug
View Settings in
Window
Adjust Protection Settings
for Desired Values with
Rotary Switches
Trip Unit Operation Status
"Blinking Green"=OK (See
Section 1 .1 .1)
R-Frame Rating Plug
Press and Release "Trip
Reset" Push Button to
Reset Trip Unit
Press and Release "Test"
Push Button to Initiate
Self-Test (See Section 4)
Press and release "STEP" Push button
to Display Value of Next Parameter in
Window
4-Character
Display Window
Keyed
Receptacle
for Auxiliary
Power Module
Connector (See
Section 1 .5)
Time-Current curve for
Phase Protection
DS Rating Plug