Eaton Cutler-Hammer Digitrip RMS 610 Instruction Leaflet Download Page 19

19

Instruction Leaflet 

I. L. 29-886B

Effective August 2011

 Instructions for Digitrip RMS 610 Trip Unit

 

 

eaton corporation

 www.eaton.com

1. 

Before starting any test sequence

check the Unit Status 

(Green LED) in the lower right corner of the Trip Unit (see Figure. 

1 and 19) to be sure it is blinking on and off about once each sec-

ond, which indicates that the Trip Unit is functioning normally.

 

 In 

the event the Unit Status LED is not blinking, install an Auxiliary 

Power Module (APM) (see Figure 11), or if you have already 

installed one, check to see that it is connected correctly (see 

Section 1 .5) .

2. 

If the circuit breaker is carrying current,

 check that the cur-

rent is not more than 50% of the Long Delay Current Setting (

I

r

); 

because the 

Trip Unit will not execute your test instructions 

when it senses that the current through the breaker exceeds 

the 50% level.  If the current through the circuit breaker 

increases to a value greater than 50% of the Long Delay 

Current Setting, 

Ir

, the Trip Unit will automatically abort any 

Trip Unit Test that may be in progress.  Should an actual 

overload or fault condition occur during an in-service, test 

sequence, the protection function will override the test func-

tion, and the circuit breaker will trip automatically in accor-

dance with the actual Time-Current settings.

3. 

When performing tests on the Long Delay element, be aware 

that in addition to the standard protection element, the 

Digitrip RMS 610 Trip Unit also has a Long Time Memory 

function (LTM)

, which serves to protect load circuits from 

the effects of repeated overload conditions (see Note 1 under 

Section 3 .3 Long Delay Time Setting) .  The action of the 

LTM 

during primary injection tests and during tests initiated from the 

Trip Unit Test Panel under the "TEST AMPS" setting of "6T", will 

advance the Long Delay Trip Time if multiple Long Delay Time 

tests are performed repeatedly - as one might do in making 

single-phase tests on each pole of a breaker in succession, for 

example .  If there is any question, you may simply wait about 

ten (10) minutes after a Long Delay Trip for the 

LTM

 to reset .  

The 

LTM

 is not active during tests initiated from the Trip Unit Test 

Panel under the "TEST AMPS" settings of "1", "2", "3", "8", or "10" .
To reset the LTM immediately:

• 

Set the "TEST AMPS" to "1" .

• 

Press and release the (Black) "TEST" push-button (timer will be 

running in the display window), and then

• 

Quickly press and release the "TRIP RESET" push-button 

before the Trip Unit operates .

• 

Now the 

LTM

 will be reset .

4. 

When performing tests on the Ground Fault element, be 

aware that in addition to the standard protection, the 

Digitrip RMS 610 Trip Unit also has a Ground Time Memory 

function (GTM)

, which serves to protect load circuits from the 

effects of repeated (sputtering) ground arcs (see Note under 

Section 3 .9 Ground Fault Time Delay Setting) .  Because the 

GTM

 

resets quickly, it will not normally affect ground fault test results, 

but if Ground Fault tests are repeated quickly, the 

GTM

 can 

make the breaker appear to trip too soon .

otee:

N

To STOP a TEST initiated via the integral test panel PRESS and 

RELEASE the "TRIP RESET" push-button .

4.4.1  Not Tripping the Breaker

1 .  Place the "TEST AMPS" selector switch (see Figure 19) in one of 

the six "No Trip" test settings, i .e ., 1, 2, 3, 8, or 10 x I

n

, or GF .

2 .  Press and release the (Black) "TEST push-button - the test starts 

when the push-button is released, and the 

elapsed time will 

be displayed

 in the window .  When the timer stops, the lighted 

"RED" cause of trip LED indicates the protection function which 

operated .

3 .  Should any of the various protection settings be less than the 

selected "No Trip" test value, then the LED related to that func-

tion will turn on signifying successful completion of the test 

action .

otee:

N

During the long delay tests the Long Delay LED flashes "RED" .

4 .  Reset the Trip Unit by pressing and releasing the "TRIP RESET" 

push-button; all LEDs lighted by the "No Trip" test action should 

turn "OFF, and the display will again show the value of the cur-

rent through the breaker .  In the event that no one resets the Trip 

Unit after a test, it will wait for about three (3) hours, and then it 

will automatically revert back to its pretest status .

4.4.2  Tripping the Breaker

WARNING

CIRCUIT BREAKER OPERATING MECHANISMS OPEN AND CLOSE THE MOVING 

PARTS VERY FAST, AND WITH VERY HIGH ENERGY.  TOUCHING THE MOVING PARTS 

DURING TEST OPERATIONS CAN CAUSE INJURY.  KEEP CLOTHING, HANDS, FEET, 

AND OTHER PARTS OF YOUR BODY WELL AWAY FROM ALL MOVING PARTS DURING 

TESTING.  FOLLOW THE INSTRUCTIONS GIVEN FOR TESTING YOUR SPECIFIC TYPE 

OF CIRCUIT BREAKER, FOUND IN THE APPROPRIATE INSTRUCTION LEAFLET LISTED 

IN SECTION 5.

1 .  Make sure that the circuit breaker is carrying no current (see 

CAUTION notes under Section 4 .1) .

otee:

N

In the event it is decided to perform a "Breaker Trip Test" while load cur-

rent is flowing, make sure the circuit breaker is carrying no more than 50% of 

the Long Delay Current Setting 

I

r

 .  The Trip Unit will NOT execute your instruc-

tions to Test itself, when the load current exceeds 50% of 

I

r

 .

2 .  Place the "TEST AMPS" selector switch (see Figure 19) in either 

the "6T (or "GFT) position .

3 .  Press and release the (Black) "TEST" push-button (see Figure 19) - 

the test starts when the push-button is released and the elapsed 

time is displayed in the window .

4 .  At least one of the various protection settings will be less than 

"6x I

n

", and the circuit breaker will trip, the LED related to that 

function will light "RED", and the reason for TRIP code will appear 

in the display window (see Table 3 for Code meanings) .  If the 

"STEP" push-button is pressed and released at this point, the 

"TEST" current value will be shown in the display window, not the 

actual current flowing in the breaker .

5 .  Reset the Trip Unit by pressing and releasing the "Trip Reset" 

push-button (see Figure 19) .  All LEDs lighted by the "Trip" test 

action should turn "OFF, and the display window will again show 

the value of current flowing in the breaker .

Summary of Contents for Cutler-Hammer Digitrip RMS 610

Page 1: ...Effective August 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 886B Instructions for Digitrip RMS 610 Trip Unit...

Page 2: ...Replacing the Back up Battery 20 5 References 20 5 1 Digitrip RMS Trip Assemblies 20 5 2 Type DS Low Voltage AC Power Circuit Breakers 20 5 3 Type DS II Low Voltage AC Power Circuit Breakers 20 5 4 Ty...

Page 3: ...considered to be all inclusive or covering every application or circumstance which may arise If you have any questions or need further information or instructions please contact your local representa...

Page 4: ...rs provide the correct input information for the protector func tions as well as tripping power whenever the circuit breaker is carrying current These signals develop analog voltages across the approp...

Page 5: ...ate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 610 Trip Unit is availab...

Page 6: ...1 1 Ground Fault Protection Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1...

Page 7: ...Effective August 2011 Instructions for Digitrip RMS 610Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 610 Type Ll Figure 4 Digitrip RMS 610 Type LS Figure 5 Digitrip RMS 610 Type LSI...

Page 8: ...current exceeds approximately 10 of the circuit breaker frame or current sensor rating Whenever the load current falls below 10 the discriminator is rearmed The release once rearmed will remain enabl...

Page 9: ...the other breaker F can not cause breaker M to trip caution IF ZONE INTERLOCKING IS NOT TO BE USED I E STANDARD TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECT...

Page 10: ...Phase B Current lb kA Phase C Current lc kA X X X X X X X X X X X X X X X X X X Ground Current lg kA Neutral Current ld kA n n n X X X 1 2 1 1 Local Messages Table 3 DISC DISCriminator GNDT GrouND Tri...

Page 11: ...mory error Protection functions still operate but may be up to 12 out of tolerance Replace trip unit at first opportunity 1 2 2 1 SDT Short Time Delay Trip Breaker tripped because phase current exceed...

Page 12: ...still function to protect the circuit but the calibration may be degraded by a few percent The Time Current Curve tolerances may be exceed ed in some cases by as much as 12 It is not necessary to tri...

Page 13: ...60 640 680 720 760 800 A Plug In 1600 A LDPU Ir 800 960 1120 1280 1360 1440 1520 1600 A Note N Rating plugs from Digitrip models 500 600 700 800 CANNOT be used with model 610 Trip Units The connection...

Page 14: ...as appli cable Even without available external control power once the load cur rent through the circuit breaker exceeds approximately 20 40 if single phase of the frame current sensor rating the green...

Page 15: ...Rating of the cir cuit breaker Instantaneous and ground current settings are defined in multiples of In To illustrate the effect of each protection curve setting simulated Time Current curves are pict...

Page 16: ...Curve referenced in Section 5 Figure 14 Short Delay Current Settings Available Settings 12 15 20 24 I Seconds at 6 Times 6 x Long Time Delay Sec at 6 x Ir Ir 4 I r Long Delay Setting 2 4 7 10 S1 and...

Page 17: ...0 1200 5000 1200 1200 1200 1200 1200 1200 1200 1200 Tolerances on settings are 10 of values shown Refer to Type DS Type SPB or Series C R Frame supplemental instruction leaflets given in Section 5 for...

Page 18: ...ts of the Trip Unit and two settings GF and GFT are provided for testing the ground element Figure 19 Integral Test Panel Lower Right Corner of Trip Unit caution A SETTING OF EITHER 6T OR GFT WILL TRI...

Page 19: ...lly affect ground fault test results but if Ground Fault tests are repeated quickly the GTM can make the breaker appear to trip too soon Note N To STOP a TEST initiated via the integral test panel PRE...

Page 20: ...F THE 120 VAC CONTROL POWER TO THE POWER RELAY MODULE IS LOST THEN AFTER AN OVER CURRENT OR SHORT CIRCUIT TRIP NO LEDS WILL BE LIGHTED RED TO INDICATE THE REASON FOR THE TRIP The replacement battery s...

Page 21: ...the event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will init...

Page 22: ...power to the load circuit Note N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message wou...

Page 23: ...23 Instruction Leaflet I L 29 886B Effective August 2011 Instructions for Digitrip RMS 610Trip Unit eaton corporation www eaton com Notes...

Page 24: ...between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the con...

Reviews: