Eaton Cutler-Hammer Digitrip RMS 610 Instruction Leaflet Download Page 13

13

Instruction Leaflet 

I. L. 29-886B

Effective August 2011

 Instructions for Digitrip RMS 610 Trip Unit

 

 

eaton corporation

 www.eaton.com

CAUTION

BEFORE YOU FIT THE RATING PLUG INTO THE TRIP UNIT, BE SURE TO CHECK THAT 

THE BREAKER TYPE AND FRAME RATING (OR SENSOR RATING IF APPLICABLE), 

MATCH THOSE PRINTED ON THE RATING PLUG COVER.  INSTALLING A RATING PLUG 

THAT DOES NOT MATCH THE BREAKER TYPE AND FRAME RATING (OR SENSOR 

RATING, IF APPLICABLE), CAN PRODUCE SERIOUS MIS-COORDINATION AND/OR 

FAILURE OF THE PROTECTION SYSTEM.

After installing the Rating Plug, press and release the "TRIP RESET" 

push-button to turn off any illuminated LEDs .  The purpose of the 

rating plug is to set the value of I

n

, the basis for the Trip Unit protec-

tion function current settings (see Section 3 for details) .  Each circuit 

breaker frame rating represents the maximum current it can carry 

continuously .  However for proper coordination of over-current pro-

tection, it is often desirable to choose different levels of I

n

 for differ-

ent circuit breakers of the same frame rating .  An assortment of rat-

ing plugs with different I

n

 values is available for each breaker frame 

rating (see circuit breaker instruction leaflet supplements listed in 

Section 5) to give the user flexibility to change the value of I

n

 with-

out having to change the primary current sensors on the breaker .  

By changing the rating plug, the User can easily change the range 

of current protection settings without having to remove the circuit 

breaker from its enclosure .
For example, if one expects a circuit to carry 600 A initially, but then 

increase to 1400 A in the future, one could initially install  

1600 A cables and a 1600 A breaker frame with the Trip Unit rating 

plug whose I

n

 = 800 A .  Then later on when the additional load is 

ready to come on line, the rating plug could be exchanged for one 

with I

n

 = 1600 A, without having to remove the breaker from its 

enclosure .  The available settings would give the following choices:
Long Delay Setting
  I

r

 = I

n

 x:  .5   .6   .7   .8   .85   .9   .95  1 .0

Plug I

n

 =800 A

LDPU I

r

 = : 400  480  560  640  680  720  760  800 A

Plug I

n

 = 1600 A

LDPU I

r

 = : 800  960  1120  1280  1360  1440  1520  1600 A

otee:

N

Rating plugs from Digitrip models 500 / 600 / 700 / 800 CANNOT be 

used with model 610 Trip Units .  The connection pins are located in different 

positions, so one cannot accidentally use the incorrect type of plug .

Rating Plugs for the Digitrip RMS 610 Trip Units are marked for, and 

may be applied on both 50 and 60 Hz systems .
Rating plugs have two current ratings listed on their covers (see 

Figure 9) .

• 

The "Must Use With Frame Rated" current value (or "Sensor 

Rated", if applicable),

and

• 

" I

n

 (rated I)=" current value .

This latter value (I

n

) is the basis for the Trip Unit current settings:

• 

The instantaneous and Ground Current Settings (if applicable) are 

multiples of (I

n

) (see Sections 3 .6 and 3 .8 .) .

• 

The Long Delay Current Setting, 

I

r

  is a multiple of (I

n

) .  Long 

Delay Current Setting = 

I

r

 = LD x (I

n

) (see Section 3 .2 .) .

• 

The Short Delay Current Setting (if provided) is a multiple of 

I

r

 

which in turn is a multiple of (I

n

) .  Short Delay Current Setting = 

SD x 

I

r

 = SD x LD x (I

n

) (see Section 3 .4) .

If the rating plug is missing or not well connected, then the display 

will show "PLUG" and the instantaneous / override LED will be 

lighted .  If the circuit breaker is closed, it will trip; if it is open, it will 

remain trip-free, as long as 120 Vac control power is available to the 

Power / Relay Module .  Even if control power is lost, and the rating 

plug condition is not corrected, as soon as the three-phase current 

through the circuit breaker reaches 20% (40% if single-phase cur-

rent) of the frame / current sensor rating, the Trip Unit will trip the 

breaker again .
As indicated in Figures 2 and 9, a back-up battery is provided to 

maintain the mode of trip LED indication in the Digitrip RMS 610 Trip 

Unit when external control power to the Power / Relay module is not 

available .  The back-up battery is located in the rating plug along with 

a battery check push-button and a green battery check LED .  The bat-

tery in the rating plug is "OK" if the LED lights "Green" when the "bat-

tery check" button next to it is pushed (see Section 4 .5) .

otee:

N

The battery is used only to maintain the cause of TRIP LED indication .  

It has NO part in the PROTECTION FUNCTION of the Trip Unit, and, it does 

NOT light the display window .

Summary of Contents for Cutler-Hammer Digitrip RMS 610

Page 1: ...Effective August 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 886B Instructions for Digitrip RMS 610 Trip Unit...

Page 2: ...Replacing the Back up Battery 20 5 References 20 5 1 Digitrip RMS Trip Assemblies 20 5 2 Type DS Low Voltage AC Power Circuit Breakers 20 5 3 Type DS II Low Voltage AC Power Circuit Breakers 20 5 4 Ty...

Page 3: ...considered to be all inclusive or covering every application or circumstance which may arise If you have any questions or need further information or instructions please contact your local representa...

Page 4: ...rs provide the correct input information for the protector func tions as well as tripping power whenever the circuit breaker is carrying current These signals develop analog voltages across the approp...

Page 5: ...ate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 610 Trip Unit is availab...

Page 6: ...1 1 Ground Fault Protection Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1...

Page 7: ...Effective August 2011 Instructions for Digitrip RMS 610Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 610 Type Ll Figure 4 Digitrip RMS 610 Type LS Figure 5 Digitrip RMS 610 Type LSI...

Page 8: ...current exceeds approximately 10 of the circuit breaker frame or current sensor rating Whenever the load current falls below 10 the discriminator is rearmed The release once rearmed will remain enabl...

Page 9: ...the other breaker F can not cause breaker M to trip caution IF ZONE INTERLOCKING IS NOT TO BE USED I E STANDARD TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECT...

Page 10: ...Phase B Current lb kA Phase C Current lc kA X X X X X X X X X X X X X X X X X X Ground Current lg kA Neutral Current ld kA n n n X X X 1 2 1 1 Local Messages Table 3 DISC DISCriminator GNDT GrouND Tri...

Page 11: ...mory error Protection functions still operate but may be up to 12 out of tolerance Replace trip unit at first opportunity 1 2 2 1 SDT Short Time Delay Trip Breaker tripped because phase current exceed...

Page 12: ...still function to protect the circuit but the calibration may be degraded by a few percent The Time Current Curve tolerances may be exceed ed in some cases by as much as 12 It is not necessary to tri...

Page 13: ...60 640 680 720 760 800 A Plug In 1600 A LDPU Ir 800 960 1120 1280 1360 1440 1520 1600 A Note N Rating plugs from Digitrip models 500 600 700 800 CANNOT be used with model 610 Trip Units The connection...

Page 14: ...as appli cable Even without available external control power once the load cur rent through the circuit breaker exceeds approximately 20 40 if single phase of the frame current sensor rating the green...

Page 15: ...Rating of the cir cuit breaker Instantaneous and ground current settings are defined in multiples of In To illustrate the effect of each protection curve setting simulated Time Current curves are pict...

Page 16: ...Curve referenced in Section 5 Figure 14 Short Delay Current Settings Available Settings 12 15 20 24 I Seconds at 6 Times 6 x Long Time Delay Sec at 6 x Ir Ir 4 I r Long Delay Setting 2 4 7 10 S1 and...

Page 17: ...0 1200 5000 1200 1200 1200 1200 1200 1200 1200 1200 Tolerances on settings are 10 of values shown Refer to Type DS Type SPB or Series C R Frame supplemental instruction leaflets given in Section 5 for...

Page 18: ...ts of the Trip Unit and two settings GF and GFT are provided for testing the ground element Figure 19 Integral Test Panel Lower Right Corner of Trip Unit caution A SETTING OF EITHER 6T OR GFT WILL TRI...

Page 19: ...lly affect ground fault test results but if Ground Fault tests are repeated quickly the GTM can make the breaker appear to trip too soon Note N To STOP a TEST initiated via the integral test panel PRE...

Page 20: ...F THE 120 VAC CONTROL POWER TO THE POWER RELAY MODULE IS LOST THEN AFTER AN OVER CURRENT OR SHORT CIRCUIT TRIP NO LEDS WILL BE LIGHTED RED TO INDICATE THE REASON FOR THE TRIP The replacement battery s...

Page 21: ...the event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will init...

Page 22: ...power to the load circuit Note N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message wou...

Page 23: ...23 Instruction Leaflet I L 29 886B Effective August 2011 Instructions for Digitrip RMS 610Trip Unit eaton corporation www eaton com Notes...

Page 24: ...between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the con...

Reviews: