background image

 

3

Wire Combination 

Torque 

#12 with #14 

12 in-lbs 

#14 with #16 

12 in-lbs 

#16 with #18 

12 in-lbs 

#16 with #20 

12 in-lbs 

#16 with #22 

12 in-lbs 

#18 with #22 

10-12 in-lbs 

#18 with #20 

10-12 in-lbs 

#20 with #22 

7-12 in-lbs 

 

 

                  Table C 

 

Follow the schematic (Figure 6) to wire the 2 and 3-wire 
control modules.    

 
Note:  For 2-wire control, ensure the two wires coming from 
the control module are connected across a NC auxiliary 
contact. 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 6 

5 COIL 

KITS 

 

5.1  Description 

A wide range of coils is available for both electrically held and 
mechanically held lighting contactors.  Refer to the 

Ordering 

Detail 

section for more information about the coil kit catalog 

numbers and voltages available. 

 

Note:  For mechanically held lighting contactor, only use coil 
rated up to 277 VAC maximum.  Use control power 
transformer for higher voltages.

 

 

5.2 Installation 

1.  Disconnect all power. Replace and mount the coil on the 

contactor as shown in Figure 7. 

2.  For mechanically held contactors, remove all wires from 

the control module and remove the coil cover 

along with 

control module

 

 

 

 

 
5.3  Wiring

 

Coil terminal can accept wires from #18 AWG to #14 AWG 
(either solid or stranded) as single or combination of two wires 
(Refer to Table D below for valid wire combination).  Wire 
material must be copper with a temperature rating of 60 or 75 
degrees C.   Maximum tightening torque is 15 in-lbs. 

 

                           

Table D

 

 

Ordering Details 

 
 Coil Kits: 

9-3242-7 

24V 60Hz / 20V 50Hz Coil 

9-3242-8 

28V 60Hz / 24V 50Hz Coil 

9-3242-1 

115-120V 60Hz / 110V 50Hz Coil 

9-3242-5 

200-208V 60Hz Coil 

9-3242-2 

230-240V 60Hz / 220V 50Hz Coil 

9-3242-6 

265-277V 60Hz / 240V 50Hz Coil  

9-3242-9 

347V 60Hz Coil 

9-3242-3 

460-480V 60Hz / 440V 50Hz Coil 

9-3242-4 

575-600V 60Hz / 550V 50 Hz Coil 

 

 

Control Module Kits: 

C320MH2WT0 

2 wire 24 VAC 60/50 Hz 

C320MH2WA0 

2 wire 110-120 VAC 60/50 Hz 

C320MH2WH0 

2 wire 200-277 VAC 60/50 Hz 

C320MH2WT1 

2 wire 12-24 VDC  

C320MH3WT0 

3 wire 24 VAC 60/50 Hz 

C320MH3WA0 

3 wire 110-120 VAC 60/50 Hz 

C320MH3WH0 

3 wire 200-277 VAC 60/50 Hz 

C320MH3WT1 

3 wire 12-24 VDC  

 

Power Pole Kits: 

C320PRP1 

Single Power Pole 

C320PRP2 

Double Power Pole 

 
Auxiliary Contact Kits: 

Auxiliary Contact Block 1 NO when 

mounted on left side of contactor. 

C320AMH1 

Auxiliary Contact Block 1 NC when 

mounted on right side of contactor. 

Auxiliary Contact Block 2 NO when 

mounted on left side of contactor. 

C320AMH2 

Auxiliary Contact Block 2 NC when 

mounted on right side of contactor. 

 
Note

:

 

These instructions do not purport to cover all details or variations in 

equipment nor provide for every possible contingency to be met in connection 
with installation, operation, or maintenance. Should further information be 
desired or should particular problems arise which are not covered sufficiently 
or the Purchase’s purpose, the matter should be referred to Eaton e-Com 
Technical Support.  Toll free telephone (800) 356-1243. 
 
 

                               Figure 7 

 

# 14 AWG 

# 16 AWG 

# 18 AWG 

Size Type 

Solid Stranded Solid  Stranded  Solid  Stranded 

Solid X  X X  X  X  X 

# 14 AWG 

Stranded X  X  X  X  X  X 

Solid X  X X  X  X  X 

# 16 AWG 

Stranded X  X  X  X  X  X 

Solid X  X X  X  X  X 

# 18 AWG 

Stranded X  X  X  X  X  X 

Instruction Sheet                       Pub50765

Revision A                                            Page 3 of 4

     

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEH-41043

ECR LT#10001

Reviews: