Maximum Input Amps
Range
Maximum Amps
6 sec.
1 sec.
0-2 A
125 A
250 A
0-5 A
125 A
250 A
0-10 A
125 A
250 A
0-20 A
150 A
300 A
0-50 A
215 A
400 A
0-100 A
300 A
600 A
0-150 A
450 A
800 A
0-200 A
500 A
1,000 A
Troubleshooting
Problem
Solution for Current
Output Models
Sensor has no output.
Power supply is not properly sized. Check power supply volt-
age and current rating.
Polarity is not properly matched. Check and correct wiring
polarity.
The core contact area may be dirty. Open the sensor and
clean the contact area.
Output signal is too
low.
The range may be too high for the current being monitored.
Select a difference EACF Series model with lower range.
The load current is not sinusoidal.
Monitored current is below minimum required. Loop the
monitored wire several times through the aperture until the
“sensed” current rises above minimum. (‘Sensed Amps’ is
equal to ‘Actual Amps’ multiplied by the ‘Number of Loops.’)
Output signal is
always at maximum
frequency.
The range may be too low for the current being monitored.
Select a different EACP Series sensor with a higher range.
Output signal is
always at minimum
frequency.
Monitored load is not AC or is not on. Check that the moni-
tored load is AC and that it is actually on.
Specifications
Specification
Value
Power Supply
24 VAC/DC
Power Consumption
< 1 VA
Output
Open Collector Transistor; Opto-Isolated PWM
On: 40 ms; Off: Variable
Current: 2 mA @ 8 VDC min.; 15 mA @ 24 VDC max.
Voltage: 5-27 VDC
Response Time
100 ms (90% of Step Change)
Accuracy
1% FS
Bandwidth
5K: 90-100 ms
10K: 45-50 ms
Isolation Voltage
5,000 VAC (Tested)
Frequency Range
10-400 Hz
Housing
UL 94V-O Flammability Rated
Environmental
5 to 158°F (-15 to 70°C), 0-95%, Non-Condensing
3
EATON
www.eaton.com
Instructions Publication
P52087
Effective July 2017
CurrentWatch™ EAC Series Current Sensors
Powered AC Current Sensors, 24 VAC/DC,
Proportional Frequency Output