Maximum Input Amps

Range

Maximum Amps
6 sec.

1 sec.

0-2 A

125 A

250 A

0-5 A

125 A

250 A

0-10 A

125 A

250 A

0-20 A

150 A

300 A

0-50 A

215 A

400 A

0-100 A

300 A

600 A

0-150 A

450 A

800 A

0-200 A

500 A

1,000 A

Troubleshooting

Problem

Solution for Current

Output Models

Sensor has no output.

Power supply is not properly sized.  Check power supply volt-

age and current rating.
Polarity is not properly matched.  Check and correct wiring 

polarity.
The core contact area may be dirty.  Open the sensor and 

clean the contact area.

Output signal is too 

low.

The range may be too high for the current being monitored.  

Select a difference EACF Series model with lower range.

The load current is not sinusoidal.
Monitored current is below minimum required.  Loop the 

monitored wire several times through the aperture until the 

“sensed” current rises above minimum.  (‘Sensed Amps’ is 

equal to ‘Actual Amps’ multiplied by the ‘Number of Loops.’)

Output signal is 

always at maximum 

frequency.

The range may be too low for the current being monitored.  

Select a different EACP Series sensor with a higher range.

Output signal is 

always at minimum 

frequency.

Monitored load is not AC or is not on.  Check that the moni-

tored load is AC and that it is actually on.

Specifications

Specification

Value

Power Supply

24 VAC/DC

Power Consumption

< 1 VA

Output

Open Collector Transistor; Opto-Isolated PWM

On: 40 ms; Off: Variable

Current: 2 mA @ 8 VDC min.; 15 mA @ 24 VDC max.

Voltage: 5-27 VDC

Response Time

100 ms (90% of Step Change)

Accuracy

1% FS

Bandwidth

5K: 90-100 ms

10K: 45-50 ms

Isolation Voltage

5,000 VAC (Tested)

Frequency Range

10-400 Hz

Housing

UL 94V-O Flammability Rated

Environmental

5 to 158°F (-15 to 70°C), 0-95%, Non-Condensing

3

EATON 

www.eaton.com

 

Instructions Publication 

P52087

Effective July 2017

CurrentWatch™ EAC Series Current Sensors 

Powered AC Current Sensors, 24 VAC/DC, 

Proportional Frequency Output

Summary of Contents for CurrentWatch EAC Series

Page 1: ...euraavat työt Nebezpečí úrazu elektrickým proudem Níže uvedené práce smějí provádět pouze osoby s elektrotechnickým vzděláním Eluohtlik Elektrilöögioht Järgnevalt kirjeldatud töid tohib teostada ainult elektriala spetsialist vői elektrotehnilise instrueerimise läbinud personal Életveszély az elektromos áram révén Csak elektromos szakemberek és elektrotechnikában képzett személyek végezhetik el a k...

Page 2: ...nment as motors contactors heaters pull boxes and other electrical enclo sures Mounting can be done in any position or hung directly on a wire with a wire tie Be sure to leave at least one in 2 54 mm distance between sen sor and other magnetic devices Press the tab in the direction shown in the diagram to the right After placing the wire in the aper ture press the hinged portion firmly downward un...

Page 3: ...ove minimum Sensed Amps is equal to Actual Amps multiplied by the Number of Loops Output signal is always at maximum frequency The range may be too low for the current being monitored Select a different EACP Series sensor with a higher range Output signal is always at minimum frequency Monitored load is not AC or is not on Check that the moni tored load is AC and that it is actually on Specificati...

Page 4: ...s 2017 by Eaton All Rights Reserved Printed in USA Publication No P52087 003 July 2017 CurrentWatch EAC Series Current Sensors Powered AC Current Sensors 24 VAC DC Proportional Frequency Output Instructions Publication P52087 Effective July 2017 Eaton Industries GmbH Hein Moeller Straße 7 11 53115 Bonn Germany Eaton W126 N7250 Flint Drive Menomonee Falls WI 53051 USA Eaton Electrical Sector Sensor...

Reviews: