Eaton Crouse-Hinds nLLK 08 N Series Operating Instructions Manual Download Page 14

14

5.4  Connection Battery nLLK 08... N  1/6

The battery is cut of for delivering. Connect the 
battery before taking into operation.

Open the second reflector flap. (fig. 3)

fasten unplugged battery wire. (fig. 4-6) 
securely onto the connector.

Observe the polarity of the Battery. (fig 5)

5.5  Connection Battery  
 

nLLK  08... N   2/6

The battery is cut of for delivering. Connect the 
battery before taking into operation:

 Open the light fitting protective bowl 

before opening the battery compartment.  
This interrupts the emergency lighting circuit.

Unscrew the battery compartment cover 
(fig. 14).

Connect cables on the connectors.

Close battery-box in reverse order.

5.6  Fitting the lamps

Only use such lamps that have been 

certified for these light fittings, see Technical 
data and type label!

The bi-pin lamp (G13) is to be inserted to its stop 

into both holders so that both pins on either side 

of the lamp engage in the holder. Then turn the 

lamp to its  lock-in position, see fig. 19 and 20.

T12 lamps (Ø 38 mm) are supplied by the EOL 
circuit detected as faulty and switched off! 
Lights with T12 lamps (Ø 38 mm) must be 
installed with mechanical protection and 
marked accordingly.

6.  Taking into operation

-   Prior to operation, check the light fitting for 

its proper functioning and installation in 
compliance with these operating instructions 
and other applicable regulations!

Only carry out insulation measurements 
between PE and the external conductor 
L1(L,L2,L3) as well as between PE and N! 
- measuring voltage:   max. 1 kV AC/DC 
- measuring current:   max. 10 mA

Only operate the light fitting with complete 
closed protective bowl.

The battery is not complete full charged in 
delivery condition.

To balancing the LED display to the battery 
capacity, the battery have to be  charged 14 
h before the first operation.

After that, release a function test of the 
emergency light connection, see 7.1.1. 
Maintenance, function test.

7. Function

7.1 

Emergency operation

The duration of the emergency operation is 
factory side fixed and can not be adjusted.

The emergency operation will automatically 
stated when mains supply failed or the charging 
line L is switched off. The green marked 
emergency lamp will operate on battery mode.

7.1.1  Function test emergency light

Switch off the mains supply from light fitting.

The green marked emergency lamp will operate.

A function test should not exceed the following 

test periods:

Battery set for 1,5 h emergency light:   60 min.
Battery set for 3,0 h emergency light: 120 min.

Should the emergency lamp be extinguished 
within the test period though the battery is fully 
charged, the latter will have to be replaced by a 
new battery set.

7.2 Charging

At temperatures below  -5°C and above +35°C 
the battery will not be fully charged for 
electrochemical reasons.

Note: New batteries will reach their total useful 
capacity only after 3 charging/discharging cycles.

8.   Maintenance

Observe the national regulations 

applicable to the   maintenance, servicing and 
test of electrical apparatus as well as the 
general rules of engineering  
(e.g. IEC/EN 60079-17, IEC/EN 60079-19)!

8.1 Servicing

When servicing, in particular those components 
that affect the type of protection, will have to be 
checked, e.g.: 

-   Housing and protective bowl for any cracks 

or damages.

-   Gaskets for their perfect condition. 

-   Terminals and blanking plugs for their firm fit.

Because of the risk of an electrostatic 

charge, the light fitting shall only be cleaned 
with a damp cloth or sponge!  
Only use customary household washing-up 
liquid diluted in water as specified! The water 
temperature may be max. 50ºC. After that, 
rinse with clear water to prevent the risk of  
tension cracks in the protective bowl!

Lamp replacement: Keep replacement intervals 
as specified by the lamp manufacturer!

9. Repair

Prior to replacing or removing any 

components, observe the following: 
Disconnect the power supply to the equip-
ment before maintenance / repair. 
Disconnect the power supply to the equip-
ment before maintenance / repair.  
Only use certified genuine CCH / EATON spare 
parts! (See CCH / EATON spare parts list).

Lamp exchange must be carried out while 

energy is switched off. 

Option: automatic double-pole switch while 
opening the protective bowl.

9.1  Battery change general

 Transport the battery only in original 

packing through potentially  zones 2/22  with 
explosive atmospheres. 
Protect against shocks.

Prior to opening the enclosure, it is necessary 
to ensure that the voltage supply has been 
isolated.

Only use certified genuine CCH / EATON 
spare parts.

Explosion protected light fittings zone 2 and zone 21/22  
Series: nLLK N 08

GB

Summary of Contents for Crouse-Hinds nLLK 08 N Series

Page 1: ...otleuchten für Zone 2 und Zone 21 22 Serie nLLK 08 N Explosion protected emergency light fittings for zone 2 and zone 21 22 Series nLLK 08 N Betriebsanleitung Operating instructions CROUSE HINDS SERIES 3 3465 000 167 D GB K ...

Page 2: ...ertung 11 1 Safety instructions 12 2 Technical data 12 3 Conformity with standards 13 4 Special functional features 13 5 Installation 13 6 Taking into operation 14 7 Function 14 8 Maintenance 14 9 Repair 14 10 Disposal Recycling 15 Inhalt Contents B1 B3 Wichtige Hinweise zur Handhabung der Batterie 3 Schaltplan Montagebilder 5 B1 B3 Important notes for battery handling 4 Wiring diagram Illustratio...

Page 3: ...rung der Batte rie Kapazität erreicht eine neue Batterie auch mit diesen 90 Nennkapazität die eingestellte Notlicht Nennbetriebsdauervon 90 min bzw 180 min Bei einer Umgebungstemperatur von ca 0 C benötigt die Erstladung der Batterie in etwa die doppelte Zeit gegenüber einer Ladung bei über 10 C Bei der Erstinbetriebnahme empfiehlt sich eine ununterbrochene Ladezeit von 20 h Hierdurch wird eine vo...

Page 4: ...attery is over specified this 90 will be sufficient to provide a rated discharge for both a 90 minute and 180 minute setting Initial charging at 0 C ambient temperature might take double the time than at tempera tures of 10 C After first mains connection an uninterrupted charging time of 20 hours is recommended to avoid early ageing due to power on power off situations The battery set is only part...

Page 5: ...tions for mounting type nLLK 08 N 1 6 1 2 2 4 732 18W 1332 36W Sechskant Hexagon SW 13 400 18W 700 36W 760 18W 1360 36W M8 12mm tief deep profond 46 188 65 130 L L1 L2 L3 N PE L N L LED LED BAT BAT LA1 LA2 LA3 LA4 LA5 LA6 LA7 LA8 Lampe 2 Netzlampe Lampe 1 Netz und Notlampe VE EVG D GB ...

Page 6: ... BAT LA1 LA2 LA3 LA4 LA5 LA6 LA7 LA8 700 36W 400 18W 130 Sechskant Hexagon SW 13 900 18W 1500 36W 65 11 10 9 Schaltplan Montagebilder Typ nLLK 08018 18 N 2 6 nLLK 08036 36 N 2 6 Wiring diagram Illustrations for mounting type nLLK 08018 18 N 2 6 nLLK 08036 36 N 2 6 L L1 L2 L3 N PE M8 14 mm tief deep profond 188 46 12 13 14 15 16 D GB ...

Page 7: ... Dc Ex tb IIICT80 C Db 2 22 21 25 C 45 C 2 x 36W X VE EVG 2 x 36W 220 240 V AC 50 60 Hz 1 5 h D II 3G D II 3D D II 2D Ex nA eb db eb IICT4 Gc Ex tc IIICT80 C Dc Ex tb IIICT80 C Db 2 22 21 25 C 45 C nLLK 08 N externe Battery external Battery 4 Ah 2 x 18W X VE EVG 2 x 18W 220 240 V AC 50 60 Hz 1 5 h D II 3G D II 3D D II 2D Ex nA eb db eb IICT4 Gc Ex tc IIICT80 C Dc Ex tb IIICT80 C Db 2 22 21 25 C 45...

Page 8: ...ehe Tabelle 1 Db Bemessungsspannung sieheTabelle 1 cos ϕ 0 95 cap Lampenbestückung Leuchtstofflampen mit Zweistiftsockel G13 nach 18W IEC 60081 2220 36W IEC 60081 2420 Schutzart nach EN IEC 60529 IP 66 Schutzklasse nach EN IEC 61140 I zulässige Umgebungstemperatur 1 sieheTabelle 1 Lagertemperatur in der Originalverpackung 25 C bis 45 C Klemmvermögen Steck Anschlu ssklemme 2 x 2 5 mm Klemmvermögen ...

Page 9: ...ierbar Schutzwanne zum Verschließen der Leuchte fest an das Leuchtengehäuse andrücken und den Zentralverschluss um 90º drehen 5 2 Montageabmessungen siehe Bild 2 und 10 Beachten Sie beim Befestigen des Montagezu behörs an der Leuchte die max Gewindetiefe der Montagebohrung von 14 mm Verwenden Sie keine zu langen Schrauben Zeigt der Lichtaustritt nach oben sind zusätzliche Schutzmaßnahmen gegen dau...

Page 10: ...trieb umgeschaltet 7 1 1 Funktionstest Notlicht Netzspannung der Leuchte ausschalten Die Notlichtlampe Fassung mit grüner Markierung muss leuchten Folgende Prüfzeiten sollten bei einem Funktions test nicht überschritten werden das sonst keine Notlichtreserve zur Verfügung steht Batteriesatz mit 1 5 h Notlicht 60 min Batteriesatz mit 3 0 h Notlicht 120 min Erlischt die Notlichtlampe bei vollgeladen...

Page 11: ...g LED blinkt Fehler im Lampenkreis z B EOL Abschaltung Beide Lampen sind außer Betrieb Notlichtfunktion ist deaktiviert Fehlerbehebung Lampenwechsel Nach der Fehlerbehebung muss die Leuchte durch Abschalten des Ladestromkreises zurückgesetzt werden Ersatzteile Leuchte EVG Typ Identnummer nLLK 08 N 2x 18W 4 Ah VE EVG 2x18W 230 V 50 60 Hz 3 h kompl verpackt 2 2804 218 601 nLLK 08 N 2x 18W 4 Ah VE EV...

Page 12: ...plication Zone 21 Ex tb see table 1 Db Rated voltage see table 1 cos ϕ 0 95 cap Lamps to be fitted Fluorescent lamps with G13 bi pin cap to 18W IEC EN 60081 2220 36W IEC EN 60081 2420 Protection acc to IEC EN 60529 IP 66 Insulation class to IEC EN 61140 I max permissible ambient temperature 1 see table 1 Storage temperature in original packing 25 C to 45 C Supply terminal clamping capacity per cla...

Page 13: ...e bowl can at option be hinged on either side To close the light fitting press the protective bowl tightly onto the luminaire housing and turn the central locking device through 90 5 2 Mounting dimensions see fig 2 and 10 When fixing the mounting accessories onto the light fitting observe the max depth of thread of 14 mm Do not use too long screws Installing the light output upwards additional pro...

Page 14: ...ery mode 7 1 1 Function test emergency light Switch off the mains supply from light fitting The green marked emergency lamp will operate A function test should not exceed the following test periods Battery set for 1 5 h emergency light 60 min Battery set for 3 0 h emergency light 120 min Should the emergency lamp be extinguished within the test period though the battery is fully charged the latter...

Page 15: ...e nLLK 08 N 2 x 18W 1 6 Battery 6 V 4 Ah 1 5 and 3 h compl packed 2 3468 236 902 nLLK 08 N 2 x 36W 1 6 Battery 6 V 4 Ah 1 5h compl packed 2 3468 236 902 nLLK 08 N 2 x 18W 2 6 Battery 6 V 4 Ah 1 5 and 3 h compl packed 2 3468 236 903 nLLK 08 N 2 x 36W 2 6 Battery 6 V 4 Ah 1 5h compl packed 2 3468 236 903 nLLK 08 N 2 x 36W 2 6 Battery 6 V 7 Ah 3 h compl packed 2 3468 236 904 9 1 2 Battery change nLLK...

Page 16: ...16 ...

Page 17: ...17 ...

Page 18: ...18 Notizen Notes ...

Page 19: ...19 Notizen Notes ...

Page 20: ...ciju valsts valod varat piepras t j su valsts atbild gaj Cooper Crouse Hinds CEAG p rst vniec b M Jistg u jitolbu dan il manwal fil lingwa nazzjonali tag hom ming and ir rappre entant ta Cooper Crouse Hinds CEAG f pajji hom NL Indien noodzakelijk kan de vertaling van deze gebruiksinstructie in een andere EU taal worden opgevraagd bij Uw Cooper Crouse Hinds CEAG vertegenwoordiging P Se for necessár...

Reviews: