background image

24

Flameproof module series, GHG 61. .... R....

10.17.4 

Maximum rating current for short-circuit back-up fuse for max. 50 kA, if  Icc > Ics * for Manual motor starters

Short circuit protection and max. back-up fuse

Setting range 

240 V AC 
Ics                            gL, aM

400 V AC 
Ics                            gL, aM

500 V AC 
Ics                            

 
gL, aM

690 V AC 
Ics                            

 
gL, aM

 0,10 A     ...........       0,16 A

 0,16 A     ...........       0,25 A

Short circuit proof

no back-up fuse required, up to Icc = 50 kA

 0,25 A     ...........       0,40 A

 0,40 A     ...........       0,63 A

 0,63 A     ...........       1,00 A

 1,00 A     ...........       1,60 A

 1,60 A     ...........       2,50 A

40 kA

25 A

 2,50 A     ...........       4,00 A

10 kA

40 A

 4,00 A      ..........       6,30 A

40 kA

50 A

 7 kA

40 A

 6,30 A     ...........       9,00 A

30 kA

80 A

 5 kA

50 A

 9,00 A     ...........     12,50 A

27 kA

80 A

 4,5 kA

50 A

12,50 A     ..........     16,00 A

25 kA

100 A

 4 kA

50 A

16,00 A     ...........    20,00 A

22 kA

100 A

 3,5 kA 

50 A

20,00 A     ..........     25,00 A

20 kA

125 A

 3 kA

50 A

Einstellbereich

240 V AC 
Ics                            gL, aM

400 V AC 
Ics                        gL, aM

500 V AC 
Ics                            

 
gL, aM

690 V AC 
Ics                            

 
gL, aM

 0,10 A     ...........       0,16 A

 0,16 A     ...........       0,25 A

Short circuit proof

no back-up fuse required, up to Icc = 100 kA

 0,25 A     ...........       0,40 A

 0,40 A     ...........       0,63 A

 0,63 A     ...........       1,00 A

 1,00 A     ...........       1,60 A

 1,60 A     ...........       2,50 A

40 kA

25 A

 2,50 A     ...........       4,00 A

60 kA

35 / 40 A

10 kA

40 A

 4,00 A      ..........       6,30 A

40 kA

50 A

 7 kA

40 A

 6,30 A     ...........       9,00 A

30 kA

80 A

 5 kA

50 A

 9,00 A     ...........     12,50 A

75 kA

80 A

27 kA

80 A

 4,5 kA

50 A

12,50 A     ..........     16,00 A

60 kA

100 A

25 kA

100 A

 4 kA

50 A

16,00 A     ...........    20,00 A

55 kA

100 A

22 kA

100 A

 3,5 kA 

50 A

20,00 A     ..........     25,00 A

50 kA

125 A

20 kA

125 A

 3 kA

50 A

10.17.5 

Maximum rating current for short-circuit back-up fuse for max. 100 kA, if  Icc > Ics * for Manual motor starters

Short circuit protection and max. back-up fuse

* Icc = prospective short-circuit current at installation location

   Ics = Rated short-circuit breaking capacity

Summary of Contents for Crouse-Hinds GHG 61 R Series

Page 1: ...jos i verstos J su gimt j kalb galite pareikalauti atsakingoje Cooper Crouse Hinds CEAG atstovyb je savo alyje LV o ekspluat cijas instrukciju valsts valod varat piepras t j su valsts atbild gaj Coope...

Page 2: ...ng 5 10 Technische Daten kompletter Bausteine 6 14 Ausl sekennlinien 39 Konformit tsaussage separat beigelegt Contents Contents 2 Dimensional drawings 2 1 Technical details 15 2 Safety instructions 16...

Page 3: ...nausf hrung AbweichendeTemperaturen sind bei Sonderversionen m glich Zul Lagertemperatur in Originalverpackung 50 C bis 60 C Anschlussquerschnitt Hauptklemmen Bausteingr e 0 max 2x 4 0 mm feindr htig...

Page 4: ...Betriebsmittels zu beachten Pr fkriterium f r die Eigenerw rmung ist eine berlastung um 10 Die Temperaturklasse der kompletten Anlage oderVerteilung wird durch dieVerlustleistung aller eingebauten Bau...

Page 5: ...rteiler kann zum Verlust der Garantie f hren 7 Instandhaltung Wartung Die f r dieWartung Instandhaltung von elektrischen Betriebsmitteln in explosionsgef hr deten Bereichen geltenden Bestimmungen der...

Page 6: ...n Bei anderen Einbauten sind technische Datenbl tter bzw die Daten auf demTypenschild zu beachten Ausl sekennlinien siehe letzte Seite Leistungsschalter mit Signalkontakt werden in das n chst gr ere K...

Page 7: ...Hilfskontakt S2 S H Bemessungsspannung bis 250V Bemessungsstrom 5A Anschlussquerschnitt 2x 2 5mm 1 5 Nm Signalkontakt S2 S H Hilfskontakt S2 S H 10 6 Stromstossschalter EG Baumusterpr fbescheinigung...

Page 8: ...te Bausteine Serie GHG 61 R Anschlussbild Installationssch tz 24A Hilfskontakte 4S 1S 1 2S 10 9 Installationssch tz 32A EG Baumusterpr fbescheinigung PTB 98 ATEX 1087U Explosionsschutz Ex de IIC IIB G...

Page 9: ...inbauten angegeben Bei anderen Einbauten sind technische Datenbl tter bzw die Daten auf demTypenschild zu beachten Anschlussbild Luftsch tz20A Hauptkontakte Hilfskontakte 3S 1S 1S 1 10 12 Stern Dreiec...

Page 10: ...e bis 20A Hilfskontakte bis 6A Bemessungsschaltleistung Hauptkontakte AC 3 230V 2 2kW 400V 690V 4kW Bemessungsschaltleistung Hilfskontakte AC15 230V 4A Anschlussquerschnitt Schaltkontakte 1 2 3 4 5 6...

Page 11: ...usterpr fbescheinigung PTB 99 ATEX 1007 U Bemessungsspannung 690 V 50 60 Hz 440V DC Bemessungsstrom bis 25A Kurzschlussvorsicherung siehe Punkt 10 17 4 und 10 17 5 Schaltverm gen AC 3 690V 25A Thermis...

Page 12: ...20 00 A 25 00 A 20 kA 125 A 3 kA 50 A Einstellbereich 240 V AC Ics gL aM 400 V AC Ics gL aM 500 V AC Ics gL aM 690 V AC Ics gL aM 0 10 A 0 16 A 0 16 A 0 25 A Kurzschlussfest keine Vorsicherung notwen...

Page 13: ...1 92 A 15 0 s 9 0 s 6 5 s 4 8 s 3 2 s 0 16 A 0 25 A 3 00 A 16 0 s 10 0 s 6 8 s 5 2 s 3 6 s 0 25 A 0 40 A 4 80 A 16 0 s 9 7 s 6 5 s 5 0 s 3 3 s 0 40 A 0 63 A 7 56 A 17 0 s 10 2 s 7 3 s 5 7 s 3 9 s 0 63...

Page 14: ...ontakte max 2x 2 5 mm 1 5 Nm Komponentengr e 3 Gewicht ca 0 210 kg Anschlie bare Betriebsmittel Gas Ex Zone 1 und Zone 2 EN IEC 60079 10 1 Staub Ex Zone 21 und Zone 22 EN IEC 60079 10 2 II 2 GD Eigens...

Page 15: ...le size 3 IIC 20 C 60 C 110 C module size 3 IIB 55 C 60 C 110 C module size 3 4 IIC IIB 20 C 60 C 110 C standard version Other temperatures possible with special versions Perm storage temperature in o...

Page 16: ...ules depends on the respective encapsulated switch unit Important When using these modules the technical data and the connection diagram on the type label shall be observed When circuit breakers and E...

Page 17: ...ng The valid national regulations for the servicing maintenance of electrical apparatus for use in potentially explosive atmospheres shall be observed the IEC EN 60079 17 Prior to opening the enclosur...

Page 18: ...r built in apparatus is used the technical data sheets or the data on the type label shall be observed Tripping characteristic of circuit breaker last page Circuit breakers with signal contacts are bu...

Page 19: ...o 250V Rated current 5A Terminal cross section 2x 2 5mm 1 5 Nm Signal contact S2 S H Aux contact S2 S H 10 6 Current surge switch EC Type Examination Certificate PTB 98 ATEX 1087U Explosion protection...

Page 20: ...series GHG 61 R Main contacts Aux contacts 4NO 1NO 1NC 2NO 10 9 32A installation contactor EC Type Examination Certificate PTB 98 ATEX 1087U Explosion protection Ex de IIC IIB Gb Rated voltage up to 4...

Page 21: ...built in apparatus is used the technical data sheets or the data on the type label shall be observed Contact arrangement 20A air break contactor Main contacts Aux contacts 3NO 1NC 1NO 1NC 10 12 Star d...

Page 22: ...60h Control functions 11 delayed pick up 12 delayed reset 16 delayed pick up and reset 21 cut in wiping 22 cut off wiping 42 blinking Terminal cross section Main contacts max 2x 10mm 3 0 Nm Control c...

Page 23: ...on certificate PTB 99 ATEX 1007 U Rated voltage 690 V 50 60 Hz 440V DC Rated current up to 25 A Short circuit back up fuse see point 10 17 4 and 10 17 5 AC 3 switching capacity 690 V 25 A Thermal trip...

Page 24: ...0 A 25 00 A 20 kA 125 A 3 kA 50 A Einstellbereich 240 V AC Ics gL aM 400 V AC Ics gL aM 500 V AC Ics gL aM 690 V AC Ics gL aM 0 10 A 0 16 A 0 16 A 0 25 A Short circuit proof no back up fuse required u...

Page 25: ...old 5 fold 6 fold 8 fold 0 10 A 0 16 A 1 92 A 15 0 s 9 0 s 6 5 s 4 8 s 3 2 s 0 16 A 0 25 A 3 00 A 16 0 s 10 0 s 6 8 s 5 2 s 3 6 s 0 25 A 0 40 A 4 80 A 16 0 s 9 7 s 6 5 s 5 0 s 3 3 s 0 40 A 0 63 A 7 56...

Page 26: ...ntacts max 2x 10 mm 3 0 Nm Aux contacts max 2x 2 5 mm 1 5 Nm Component size 3 Weight appr 0 210 kg Applicatable devices Gas Ex Zone 1 and Zone 2 EN IEC 60079 10 1 Dust Ex Zone 21 und Zone 22 EN IEC 60...

Page 27: ...odul s 3 IIC 20 C 60 C 110 C Modul s 3 IIB 55 C 60 C 110 C Modul s 3 4 IIC IIB 20 C 60 C 110 C standard d autres valeurs sont possibles avec des mod les sp ciaux Temp rature de stockage dans l emballa...

Page 28: ...modules d pend de chaque appareil de commande encapsul Important lors de l utilisation des modules il faut respecter les caract ristiques tech niques et le plan de connexion sur la plaque signal tique...

Page 29: ...llation compl te ou des distributeurs 7 Maintenance Entretien Les prescriptions relatives la maintenance et l entretien d appareils lectriques install s en atmosph res explosibles CEI EN 60079 17 doiv...

Page 30: ...standard Pour les autres les donn es des fiches techniques et des tiquettes type sont respecter Courbe de d clenchement du disjoncteur voir dernier c t Les disjoncteurs avec contact de signalisation...

Page 31: ...S2 S H Tension d essai jusqu 250V Courant d essai 5A Diam tre de connexion 2x 2 5mm 1 5 Nm Contacts de signalisation S2 S H Contacts auxiliaires S2 S H 10 6 Interrupteur de coupure impulsion Attestati...

Page 32: ...principaux Contacts auxiliaires 4NO 1NO 1NF 2NO 10 9 Contacteur d installation 32A Attestation d examen type CE PTB 98 ATEX 1087U Mode de protection Ex de IIC IIB Gb Tension d essai jusqu 415 V AC Ten...

Page 33: ...s et des tiquettes type sont respecter Sch ma de raccordement Contacteur Contacts principaux Contacts auxiliaires 3NO 1NO 1NO 1NF 10 12 Relais temporis toile triangle Attestation d examen type CE PTB...

Page 34: ...nde 11 r action retard e 12 r p tition retard e 16 r action et r p tition retard es 21 avec retour marche 22 avec retour arr t 42 clignotant Diam tre de connexion Contacts de coupure 2x 10mm maxi 3 0...

Page 35: ...V DC Courant nominal jusqu 25 A Fusible de court circuit voir point 1 4 et 1 5 page 4 Puissance de coupure AC 3 jusqu 690 V 25 A Caract ristique du d clenchement thermique T II Temp s de d clenchement...

Page 36: ...A 25 00 A 20 kA 125 A 3 kA 50 A Einstellbereich 240 V AC Ics gL aM 400 V AC Ics gL aM 500 V AC Ics gL aM 690 V AC Ics gL aM 0 10 A 0 16 A 0 16 A 0 25 A R sistant aux courts circuits fusible plac en a...

Page 37: ...cit du r glage du 3 fois 4 fois 5 fois 6 fois 8 fois 0 10 A 0 16 A 1 92 A 15 0 s 9 0 s 6 5 s 4 8 s 3 2 s 0 16 A 0 25 A 3 00 A 16 0 s 10 0 s 6 8 s 5 2 s 3 6 s 0 25 A 0 40 A 4 80 A 16 0 s 9 7 s 6 5 s 5...

Page 38: ...rseur O F Section des conducteurs Contacts de puissance max 2x 10 mm 3 0 Nm Contacts auxiliaires max 2x 2 5 mm 1 5 Nm Taille des composants 3 Poids env 0 210 kg Utilisation Gaz Ex Zone 1 and Zone 2 EN...

Page 39: ...20 30 10 3 5 7 5 1 Grenzkennlinie aus dem kalten Zustand 1 1 S 280 UC UC B Charakteristik S280 AC DC I1 I2 I 1 13xI I 1 45xI J 30 C 1 2 r n n 0 01 0 02 0 04 0 06 0 1 0 2 0 4 0 6 1 2 4 6 10 20 40 1 2 4...

Page 40: ...ct to prior approval by Eaton The same applies to Trademarks especially Eaton Moeller and Cutler Hammer The Terms and Conditions of Eaton apply as referenced on Eaton Internet pages and Eaton order co...

Reviews: