24
Flameproof module series, GHG 61. .... R....
10.17.4
Maximum rating current for short-circuit back-up fuse for max. 50 kA, if Icc > Ics * for Manual motor starters
Short circuit protection and max. back-up fuse
Setting range
240 V AC
Ics gL, aM
400 V AC
Ics gL, aM
500 V AC
Ics
gL, aM
690 V AC
Ics
gL, aM
0,10 A ........... 0,16 A
0,16 A ........... 0,25 A
Short circuit proof
no back-up fuse required, up to Icc = 50 kA
0,25 A ........... 0,40 A
0,40 A ........... 0,63 A
0,63 A ........... 1,00 A
1,00 A ........... 1,60 A
1,60 A ........... 2,50 A
40 kA
25 A
2,50 A ........... 4,00 A
10 kA
40 A
4,00 A .......... 6,30 A
40 kA
50 A
7 kA
40 A
6,30 A ........... 9,00 A
30 kA
80 A
5 kA
50 A
9,00 A ........... 12,50 A
27 kA
80 A
4,5 kA
50 A
12,50 A .......... 16,00 A
25 kA
100 A
4 kA
50 A
16,00 A ........... 20,00 A
22 kA
100 A
3,5 kA
50 A
20,00 A .......... 25,00 A
20 kA
125 A
3 kA
50 A
Einstellbereich
240 V AC
Ics gL, aM
400 V AC
Ics gL, aM
500 V AC
Ics
gL, aM
690 V AC
Ics
gL, aM
0,10 A ........... 0,16 A
0,16 A ........... 0,25 A
Short circuit proof
no back-up fuse required, up to Icc = 100 kA
0,25 A ........... 0,40 A
0,40 A ........... 0,63 A
0,63 A ........... 1,00 A
1,00 A ........... 1,60 A
1,60 A ........... 2,50 A
40 kA
25 A
2,50 A ........... 4,00 A
60 kA
35 / 40 A
10 kA
40 A
4,00 A .......... 6,30 A
40 kA
50 A
7 kA
40 A
6,30 A ........... 9,00 A
30 kA
80 A
5 kA
50 A
9,00 A ........... 12,50 A
75 kA
80 A
27 kA
80 A
4,5 kA
50 A
12,50 A .......... 16,00 A
60 kA
100 A
25 kA
100 A
4 kA
50 A
16,00 A ........... 20,00 A
55 kA
100 A
22 kA
100 A
3,5 kA
50 A
20,00 A .......... 25,00 A
50 kA
125 A
20 kA
125 A
3 kA
50 A
10.17.5
Maximum rating current for short-circuit back-up fuse for max. 100 kA, if Icc > Ics * for Manual motor starters
Short circuit protection and max. back-up fuse
* Icc = prospective short-circuit current at installation location
Ics = Rated short-circuit breaking capacity