19
10.4 Signal contact S2-S/H
Rated voltage:
up to 250V
Rated current:
5A
Min. switching capacity:
0,1VA / 24V
Terminal cross section:
2x 2,5mm²
1.5 Nm
Flameproof module series, GHG 61. .... R....
10.3 Circuit breaker, with ELCB (RCD)
EC-Type Examination Certificate:
PTB 98 ATEX 1087U
Explosion protection:
Ex de IIC/IIB Gb
Rated voltage:
Main contact
Aux. contact
up to 440V AC
up to 250V AC
Rated current:
ELCB
up to 63A
Circuit breaker
from 1.0A up to 32A (40A)
Aux. contact
max. 5A
Short-circuit protection:
up to 10 kA depend on circuit breaker
Back-up fuse:
ELCB
max. 100 A gL
Circuit breaker
dep. on rated current up to 100 A gL
Tripping current ELCB:
30mA (300mA on request)
Terminal cross section:
Main contact
Aux./Signal contact
max. 2x 10mm²
max. 2x 2.5mm²
Test torques:
3.5 Nm
1.5 Nm
Component size:
2*
3*
4
Weight:
approx. 0.95kg approx. 1.27kg approx. 1.6kg
1-pole + N
2-pole
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
* ELCB with circuit breakers and signal contacts are built into component enclosures in the next size.
Contact arrangement
ELCB with circuit breaker
1-pole + N
Contact arrangement
10.5 Aux. contact S2-S/H
Rated voltage:
up to 250V
Rated current:
5A
Terminal cross section:
2x 2,5mm²
1.5 Nm
Signal contact S2-S/H
Aux. contact S2-S/H
10.6 Current surge switch
EC-Type Examination Certificate:
PTB 98 ATEX 1087U
Explosion protection:
Ex de IIC/IIB Gb
Rated voltage:
up to 400V AC
Rated operating voltage:
8V to 275V* AC
8V to 220V DC
(*further operating voltages on request)
Rated current:
16A
Rated switching capacity:
16A / 250V AC
10A / 400V AC
Terminal cross section:
Switching contacts 1, 2, 3, 4
max. 2x 10mm²
/ 3.0 Nm
Control contacts A1, A2
max. 2x 2.5mm²
/ 1.5 Nm
Komponent size:
0
Weight:
approx. 0.55kg
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
Contact arrangement
Current surge switch
10.7 20 A installation contactor
EC-Type Examination Certificate:
PTB 98 ATEX 1087U
Explosion protection:
Ex de IIC/IIB Gb
Rated voltage:
up to 250V AC
Control voltage:
24V to 250V AC
Rated current:
20A
Rated switching capacity:
AC 1 230V / 4,0kW AC 3 230V / 1,3kW
Back-up fuse:
20A gL
Terminal cross section:
Switching contacs 1, 2, 3, 4
max. 2x 10mm²
/ 3.0 Nm
Control contacs A1, A2
max. 2x 2.5mm²
/ 1.5 Nm
Component size:
0
Weight:
approx. 0.55kg
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
Contact arrangement
20A installation contactor
1NO + 1NC
2NO
2NC
2-pole