6.2 POWER LOSS (HEAT DISSIPATION)
When the ACE enclosure is not installed in a well ventilated area, provisions must
be made to account for heat generation and ensure proper operation of the device.
6.3 DE-RATING FACTORS AND CURVES (AMBIENT
TEMPERATURE, ALTITUDE, SWITCHING FREQUENCY)
The final drive output rating is a multiplication of all applicable de-rating factors.
Ambient temperature de-rating
Altitude de-rating:
At altitudes from 1,000 to 4,000m (3,280 to 13,123 ft.) above sea level, the
de-rating is 1% for every 100m (328 ft.).
NOTE:
If the installation site is higher than 2,000m (6,560 ft.) above sea level,
connection of the drive to an ungrounded (IT) or corner-grounded delta network is
not allowed.
Low motor noise (switch frequency) de-rating:
IF 1619 • 05/18
Copyright
©
2018, Eaton’s Crouse-Hinds Division Page 10
6. TECHNICAL DATA
6.1 TECHNICAL DATA CHART
7. CROUSE-HINDS DRIVE PARAMETERS
7.1 PARAMETER TABLE
*Adaptive program is not configurable through control panel parameter menu, and is loaded to the
drive at the factory. Adaptive program is critical for proper operation of the cooling system and
must not be disabled.
*Modified product designs may vary in terms of technical information. Contact factory for additional information.
Data shown is for standard catalog, 460 VAC drives. Refer to drive manufacturer’s manual for all other voltage and performance specifications.
Base Cat. #
Max.
disconnect
rating (amps)
Disconnect
fuse type
Enclosure size
Input rating
(amps)
Max. output
rating (amps)
Nominal
horsepower
Power loss
(watts)
Temp. rating
Temp.
de-rating
factor
ACE10 1
30
J
1
2.3
3.0
1.5
106
T6
Figure 1
ACE10 2
3.1
3.6
2
112
T6
Figure 1
ACE10 3
4.0
4.8
3
132
T6
Figure 1
ACE10 5
6.6
8.0
5
178
T6
Figure 1
ACE10 7
2
12.0
14.0
7.5
606
T4A
Figure 1
ACE10 10
16.0
18.0
10
674
T4A
Figure 1
ACE10 15
60
J
2
20.0
25.0
15
737
T4A
Figure 1
ACE10 20
26.0
30.0
20
847
T4A
Figure 1
ACE10 25
30.0
35.0
25
875
T4A
Figure 1
ACE10 30
42.0
50.0
30
1008
T4A
Figure 1
ACE10 40
100
55.0
58.0
40
1217
T4A
Figure 1
ACE10 50
65.0
72.0
50
1397
T4A
Figure 1
ACE10 60
82.0
81.0
60
1577
T4A
Figure 2
Base Cat. #
Enclosure
size
Input rating
(amps)
Max. output
rating (amps)
Nominal
horsepower
ACE10 1
1
1.6
2.1
1
ACE10 2
2.3
2.6
1
ACE10 3
2.8
3.4
2
ACE10 5
4.0
4.8
3
ACE10 7
2
9.0
10.0
5
ACE10 10
10.0
12.0
7.5
ACE10 15
2
11.0
14.0
10
ACE10 20
15.0
17.0
10
ACE10 25
18.0
21.0
15
ACE10 30
24.0
29.0
20
ACE10 40
31.0
32.0
25
ACE10 50
36.0
40.0
30
ACE10 60
45.0
45.0
40
Parameter number
Parameter description
Parameter value
10.24
RO1 SOURCE
ADAPTIVE PROGRAM*
11.05
DIO1 FUNCTION
OUTPUT
11.06
DIO1 OUTPUT SOURCE
FAULT
11.09
DIO2 FUNCTION
OUTPUT
11.10
DIO2 OUTPUT SOURCE
RUNNING
19.11
EXT1/EXT2 SELECTION
DI6
20.01
EXT1 COMMANDS
CONTROL PANEL
20.02
EXT1 START TRIGGER TYPE
EDGE
22.11
SPEED REF1 SOURCE
CONTROL PANEL
POTENTIOMETER OPTION (SUFFIX PT) ONLY
12.15
AI1 UNIT SELECTION
VOLTS
12.17
AI1 MIN
0.000V
12.18
AI1 MAX
10.000V
22.11
SPEED REF1 SOURCE
AI1 SCALED
8. REPLACEMENT PARTS
ACE systems are designed to provide years of reliable service. However, should
the need for replacement parts arise, they are available through your Eaton’s
Crouse-Hinds Division Distributor. Assistance may also be obtained through your
Eaton’s Crouse-Hinds Sales Representative or the Eaton’s Crouse-Hinds Customer
Service Department.
8.1 PRE-FILTER KIT
ACE KIT1: pre-filter and hardware (1 pc.)
8.1.1 PRE-FILTER INSTALLATION INSTRUCTIONS
1. Remove rubber caps from explosionproof filters.
2. Install wire guard using the bracket, screw and lock washer provided to the
bottom filter(s).
3. Align guard with notches within the bracket as shown.
4. Tighten screw.
5. Slip pre-filter mesh over guard.
Detailed view