4.  The liquid level inside the tank must be checked (see 

Insulating Liquid Maintenance section of this manual). 

On transformers equipped with a liquid level gauge, 

the liquid level may be read directly from the gauge. 

On transformers that are not gauge equipped, the tank 

liquid level must be determined by removing the liquid 

level plug (see Figure 2). At 25 °C liquid temperature, 

the liquid level should be at the bottom edge of the 

liquid level plug hole.
If the tank temperature is greater than ambient air tem-

perature, the transformer tank must be vented to zero 

pressure before the liquid level plug is removed. Failure 

to do so may cause hot oil to be sprayed from the plug 

hole and may result in severe personal injury.

5.  Special procedures must be followed when 

energizing a transformer in ambient temperatures 

below -20 °C. Contact your Eaton representative for 

further instructions. Failure to follow special start-

up procedures may cause premature failure of the 

transformer and its components. Also, note warning 

and caution statements in 

Switches and Protective 

Devices

 section of this manual for further precautions 

when operating under-oil loadbreak accessories in 

insulating liquid temperatures below 0 °C.

Pre-service inspection (interior)

Pre-service interior inspection may not be required if 

exterior inspection reveals no evidence of damage.

If interior inspection is required, the transformer must be 

opened by removing the manhole/handhole or tank cover. 

See the 

Tank Cover Removal and Installation

 section of 

this manual.
Pre-service interior inspections should be restricted to 

noting defects or damage that may prevent proper operation 

of the transformer.

Inspect for:

1.  Moisture on underside of the tank cover or man-hole 

cover.

2.  Loose, shifted, or damaged parts (bushings, fuse 

holders, etc.).

3.  Broken or loose connections.
4.  Contaminated insulating liquid (sediment or foreign 

objects on the tank bottom, dirt or air bubbles 

suspended in the liquid).

Internal damage

If concealed internal damage is suspected, it may be 

necessary to lower the insulting liquid level to complete the 

inspection. Refer to the 

Insulating Liquid Maintenance

 

section of this manual.

Contaminated insulating liquid

If moisture is found inside the tank, or there is evidence 

that the insulating liquid may be otherwise contaminated, a 

liquid sample should be taken for analysis. Samples should 

be drawn from the bottom of the tank. For instruction on 

sampling the insulating liquid please see the 

Insulating 

Liquid Maintenance

 section of this manual.

If moisture is present in the liquid, the transformer must 

be dried out. Contact your Eaton representative for special 

instructions on dry-out or other decontamination processes.

CAUTION 

Elevated Pressure. Can cause severe personal injury. 

Do not remove liquid level plug (see Figure 2) before 

venting transformer to zero pressure. Pull ring on 

pressure relief valve to relieve pressure.

Figure 2.  Liquid level plug.

WARNING 

Fire Hazard. Energizing transformer in ambient 

temperatures below -20 °C can result in fire and cause 

severe personal injury or death. Contact your Eaton 

representative for further instructions on energizing 

transformer in ambient temperatures below -20 °C.

CAUTION 

Before opening the transformer tank for Pre-Service 

Inspection, read the Insulating Liquid Maintenance 

section in this manual. This section explains safety 

precautions that should be taken and gives instructions 

on how to prevent insulating liquid contamination.

3

Three-phase pad-mounted compartmental type installation and maintenance instructions

   

MN202001EN   August 2015

Summary of Contents for COOPER POWER SERIES

Page 1: ...ER POWER SERIES Distribution Transformers MN202001EN Effective August 2015 Supersedes S210 12 1 August 2013 Three phase pad mounted compartmental type transformer installation and maintenance instruct...

Page 2: ...NTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES In no event will Ea...

Page 3: ...Loadbreak Switches 11 Tap Changer 12 Dual Voltage and Delta Wye Switch 14 Vacuum Fault Interrupter VFI 15 Air Switches Arc Strangler 16 Surge Arresters 17 MAINTENANCE Exterior Maintenance 19 Cabinet I...

Page 4: ...ions when working around high voltage lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe...

Page 5: ...er capacity When using a forklift lift with the transformer tank closest to the mast of the forklift since most of the transformer weight is in the tank Pallet mounted equipment may also be moved by c...

Page 6: ...abinet the installation will not provide the security needed to prevent tampering by the public Add a permanent mortar seal to fill the gaps Pre service inspection exterior New transformers or transfo...

Page 7: ...e on underside of the tank cover or man hole cover 2 Loose shifted or damaged parts bushings fuse holders etc 3 Broken or loose connections 4 Contaminated insulating liquid sediment or foreign objects...

Page 8: ...ransformer nameplate Transformer neutrals must be connected to system neutrals Leads and connections that are not used must be insulated from ground and all other leads Livefront transformer connectio...

Page 9: ...furnished with the transformer Liquid temperature gauge Transformers may be furnished with a temperature gauge as optional equipment to indicate the top liquid temperature in the tank in degrees Cels...

Page 10: ...sformer Pressure relief device Transformers may have a cover mounted pressure relief device PRD in addition to the faceplate mounted pressure relief valve PRV standard on all three phase pad mounted d...

Page 11: ...minals following industry accepted safe grounding practices Grounding secondary terminals protects against situations such as a standby generator energizing transformer from the secondary circuit Foll...

Page 12: ...valve to open valve Hold the valve open for 30 seconds after pressurized air can no longer be heard hissing through the valve 2 Close pressure relief valve and wait 30 seconds 3 Pull pressure relief...

Page 13: ...from fuse cartridge 1 Use 3 4 inch and 1 2 inch wrenches to remove end plug see Figure 13 2 Use screwdriver or other tool to straighten tulip tip end of fuse link and push fuse link out of fuse cartri...

Page 14: ...facturer s product literature for maximum interrupting ratings Internal cartridge fuse replacement 1 Verify that tank is grounded De energize transformer from a remote upstream source Ground all bushi...

Page 15: ...n cause an explosion or fire Use a hotstick to operate transformer loadbreak equipment After operating transformer loadbreak equipment check that voltages at transformer terminals are the expected val...

Page 16: ...clockwise to loop thru transformer open The transformer is now OPEN and the loop conductor is electrically connected 3 Move index plate between loop thru transformer open and line b only 4 Rotate swit...

Page 17: ...e handle to desired position and allow pointer to drop into slot of index plate 5 Secure handle in its new position by tightening lock screw through index plate until it bottoms 6 Padlocking may be ac...

Page 18: ...position as follows 1 Verify that tank is grounded De energize transformer from a remote upstream source Ground all bushings and terminals before operating dual voltage or delta wye switch 2 Back out...

Page 19: ...Do not operate loadbreak equipment if a fault condition is suspected Doing so can cause an explosion or fire Use a hotstick to operate transformer loadbreak equipment After operating transformer load...

Page 20: ...erly and that electrical circuit conditions are as expected Before servicing transformer secondary connected equipment verify that all transformer secondary terminals have zero voltage and ground the...

Page 21: ...blished maximum continuous operating voltage MCOV values The transformer should not be tested impulse or applied potential with the arrester connected If connected during impulse tests the arrester wi...

Page 22: ...by rotating handle 3 4 to 1 turn after handle has come in contact with seal gland Under oil arrester disconnection during test with out arrester disconnect switch To disconnect arresters without a dis...

Page 23: ...nt dirt or moisture from entering the opened transformer tank Contamination of the insulating liquid will prevent the transformer from operating properly and may cause serious damage to the transforme...

Page 24: ...aks Test pressure should not exceed 7 psig Established pressure should be main tained for at least four hours to insure that all seals are proper 4 Re install the nutguard using 25 ft lbs torque to ti...

Page 25: ...t cover weld 10 Thoroughly clean tank cover to help prevent contamination of insulating liquid when removing cover Remove all dirt grease and moisture 11 Remove tank cover from tank Weld on tank cover...

Page 26: ...ntenance on cabinet 2 Place one 1 4 to 3 8 inch shim directly below faceplate on both sides of tank at points A and A see Figure 28 3 Place one 1 1 2 inch wedge under each side of cabinet at points B...

Page 27: ...nventional transformer oil mixed with R Temp fluid Conventional transformer oil content of 3 in R Temp fluid lowers the fire point below 300 C Measure the ASTM flash and fire points if the presence of...

Page 28: ...uld be clean and dry large mouth glass bottles Make sure that the liquid being sampled is representative of the liquid in the unit Sufficient liquid must first be drawn off to ensure that the sample w...

Page 29: ...y Cleveland Open Cup 2 ASTM D877 Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes 3 ASTM D923 Standard Practices for Sampling Electrical Insulating Liq...

Page 30: ...reported and investigated Annual Cabinet Interior Maintenance Items to Inspect Points to be checked Remedial Action Frequency Gauges and Controls Check for proper operation Repair or replace damaged o...