background image

Installation procedure

When untanking the recloser for inspection prior to 

installation, remove the four bolts that secure the tank 

and head casting. Trip the recloser and carefully lift the 

mechanism out of the tank.
1. 

Check oil level .

 Before installing the recloser, check for 

proper oil level. With the mechanism removed from the 

tank, the oil level should be up to the fill line marked on 

the tank liner.

2. 

Test oil dielectric strength .

 If the recloser has 

been stored for some time or is being relocated, 

perform a dielectric test on the oil in accordance with 

ASTM-  approved testing procedures.

A.  On new equipment, the oil must have a minimum 

dielectric strength of 26 kV.

B.  If the dielectric strength of the oil is less than 26 

kV, filter the oil to restore its dielectric strength to 

an acceptable minimum level.

3. 

Replace head casting and mechanism in tank .

A.  Wipe clean the O-ring type gasket, the gasket 

recess in the recloser head, and the tank gasket.

B.  Position and tighten the four head bolts alternately. 

The cover can be rotated to accommodate 

installation. Torque each head bolt to 11-16 ft-lbs.

C.  Operate the unit manually eight times to ensure 

that no air remains in the hydraulic mechanism.

4. 

Test mechanical operation .

 An effective test can be 

performed as follows:
A.  Move the yellow manual operating handle to the 

CLOSED position and wait at least 4 minutes.

B.  Move the manual operating handle to the OPEN 

position and listen for opening of the main 

contacts. (A dull “clunk” will be audible.) Then 

quickly move the lever back to the CLOSED 

position.(A metallic “click” can be heard.)

C.  Continue opening and closing the recloser manually 

until lock-out is achieved. This can be determined by 

listening for unlatching of the lock-out mechanism 

and also by noting that the recloser mechanism 

will not latch when the operating handle is moved 

to the CLOSED position. This test can be used to 

determine the number of operations to lock-out. 

The number of fast and delayed operations can 

also be identified. With fast operations, the main 

contacts will open almost instantaneously when the 

operating handle is moved to the OPEN position, 

while, with delayed operations, a short time elapses 

between opening of contacts and placement of the 

operating handle in the OPEN position. 

5. 

Check data plates .

 Make sure the ratings and 

settings on the recloser data plates are correct for the 

planned installation.

6. 

Mount the recloser .

7. 

Ground the recloser .

 Make the ground connection to 

the recloser ground connector (located 4” from the 

bottom of the tank).

Line installation

Provide the recloser with bypass switches and surge 

protection as shown in Figure 8. Surge protection on both 

sides of the recloser is advisable. If surge protection is 

provided on only one side,though, it should be located on 

the 

source side for line installations 

and on the 

load side 

for substation installations .

Connect the primary leads to the recloser. The source-side 

bushing is located above the sleet hood. To facilitate 

connection, rotate the cover of the recloser in 90-degree 

increments, as required. The universal clamp-type terminals 

accept No. 6 through 350-mcm conductors (No. 8 through 

2/0 for Type H reclosers).

 WARNING 

This equipment is not intended to protect human 

life . Follow all locally approved procedures and safety 

practices when installing or operating this equipment . 

Failure to comply can result in death, severe personal 

injury and equipment damage . 

G102 .1

 CAUTION 

This equipment relies on dielectric fluid to provide 

electrical insulation between components . The dielectric 

strength of the fluid must be checked on a regular basis, 

as part of the routine maintenance inspection, to ensure 

that it is at or above minimum dielectric requirements . 

Use of this equipment with dielectric fluid that does 

not meet minimum requirements can result in internal 

flashovers that will damage the equipment and can 

cause personal injury . 

G107 .3

 CAUTION 

Falling equipment . Use the lifting lugs provided and 

follow all locally approved safety practices when lifting 

and mounting the equipment . Lift the unit smoothly 

and do not allow the unit to shift . Improper lifting 

can result in severe personal injury, death, and/or 

equipment damage .

 G106 .3

 WARNING 

Hazardous voltage . Solidly ground all equipment . Failure 

to comply can result in death, severe personal injury, 

and equipment damage . 

T223 .2

7

Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions

OPERATION INSTRUCTIONS

   MN280051EN   May 2017

Summary of Contents for COOPER POWER E

Page 1: ...Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions COOPER POWER SERIES Reclosers MN280051EN Effective May 2017 Supersedes April 2014 S280 10 8 ...

Page 2: ...POSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES In no event will Eaton be responsible to the purchaser or user in contract in tort including negligence strict liability or other wise for ...

Page 3: ...haracteristics 2 Data plates 3 Manual operating levers and indicators 3 Manual operating handle 3 Non reclosing lever 3 Operations counter 3 RATINGS AND SPECIFICATIONS 4 DIMENSIONS AND WEIGHTS 6 INSTALLATION PROCEDURE 7 Line installation 7 OPERATION 8 Initial operation 8 Manual operation 8 Non reclosing operation 8 MAINTENANCE INFORMATION 9 Maintenance requirements 9 Maintenance manuals 9 Frequenc...

Page 4: ... Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around high and low voltage lines and equipment G103 3 WARNING Before installing operating maintaining or testing this equipment carefully read and understand the contents of this manual Improper operation han...

Page 5: ...imize the possibility of mechanical damage particularly to the bushings Standards Eaton s Cooper Power series reclosers are designed and tested in accordance with the following standards ANSI IEEE C37 60 1981 and IEEE Std C37 85 1989 standard and ANSI Guide C37 61 1973 Quality standards ISO 9001 Certified Quality Management System Description of operation Reclosers in the E H and L groups see cove...

Page 6: ... maximum of four operations When a recloser is programmed for both fast and delayed operations the fast operations involving no intentional time delay occur first in the sequence according to the recloser s A curve time current characteristic Delayed operations are according to the recloser s B or C time current curve B C or D curves for Types E 4E V4E L and V4L See Time Current Curves R280 91 10 ...

Page 7: ... located under the sleet hood See Figure 3 WARNING Hazardous voltage This device is not a substitute for a visible disconnect Follow all locally approved safety practices Failure to follow proper safety practices can result in contact with high voltage which will cause death or severe personal injury G112 1 WARNING Hazardous voltage Do not rely on the open position of the yellow operating handle o...

Page 8: ...5 280 V4L 14 4 15 5 110 50 45 280 Table 2 Rated interruptions Recloser type Interrupting rating Maximum circuit X R ratio Number unit operations Total unit operations E 15 20 2 40 72 45 55 5 20 90 100 12 12 4E 15 20 3 32 64 45 55 6 20 90 100 13 12 V4E 15 20 3 96 248 45 55 7 120 90 100 15 32 H 15 20 2 40 100 45 55 4 40 90 100 8 20 4H 15 20 2 32 68 45 55 5 24 90 100 10 12 V4H 15 20 2 128 272 45 55 5...

Page 9: ...0 2000 70 140 2800 2500 2000 100 200 3000 2500 2000 V4H 5 10 200 200 200 10 20 400 400 400 15 30 600 600 600 25 50 1000 1000 1000 35 70 1400 1400 1400 50 100 2000 2000 2000 70 140 2800 2500 2000 100 200 3000 2500 2000 140 280 3000 2500 2000 200 400 3000 2500 2000 Recloser type Trip coil continuous current amps Minimum trip current amps Interrupting current rms symmetrical amps L 4 8 8 32 14 4 25 5...

Page 10: ... POLE BOLT A G Figure 7 Dimensions of types E 4H and L reclosers Table 5 Recloser dimensions Description Recloser type E mm in 4E V4E mm in 4H V4H mm in L mm in V4L mm in A 380 15 380 15 355 14 380 15 380 15 B 405 16 405 16 355 14 405 16 405 16 C 1050 41 5 1240 49 900 35 5 940 37 1140 45 D 505 20 570 22 5 430 17 480 19 480 19 E 230 9 368 14 5 175 7 150 6 368 14 5 F 254 10 254 10 230 9 254 10 254 1...

Page 11: ...ayed operations a short time elapses between opening of contacts and placement of the operating handle in the OPEN position 5 Check data plates Make sure the ratings and settings on the recloser data plates are correct for the planned installation 6 Mount the recloser 7 Ground the recloser Make the ground connection to the recloser ground connector located 4 from the bottom of the tank Line instal...

Page 12: ... recloser operation The recloser can be opened or closed manually regardless of the position of the non reclosing lever Figure 8 Connection diagram with switches to facilitate maintenance and complete surge protection BYPASS SWITCH RECLOSER GND SOURCE LOAD SURGE ARRESTER SURGE ARRESTER DISCONNECT SWITCH DISCONNECT SWITCH LOAD SOURCE MULTIGROUNDED NEUTRAL WARNING This equipment is not intended to p...

Page 13: ...ers For further information contact your Eaton representative Factory maintenance classes The factory service department offers recloser maintenance training classes These classes taught by experienced service technicians are held at the factory in house training facility The courses provide hands on instruction and factory recommended procedures for the routine maintenance troubleshooting repair ...

Page 14: ...This page is intentionally left blank 10 Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions OPERATION INSTRUCTIONS MN280051EN May 2017 ...

Page 15: ...This page is intentionally left blank 11 Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions OPERATION INSTRUCTIONS MN280051EN May 2017 ...

Page 16: ...ates Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN280051EN May 2017 KA2048 0348 REV03 Eaton is a registered trademark All trademarks are property of their respective owners For Eaton s Cooper Power series product information call 1 877 277 4636 or visit www eaton com cooperpowerseries SAFETY FOR LIFE ...

Reviews: