Maintenance information

Maintenance requirements

All Eaton’s Cooper Power series reclosers require routine 

inspection and maintenance to ensure proper operation. If 

the equipment is not adequately maintained, it may fail to 

operate properly.

Maintenance manuals

Maintenance instruction manuals for single-phase reclosers 

are listed in Table 6 by their Service Information Number.

Frequency of maintenance

To assure proper and trouble-free operation, oil interrupting 

reclosers must be maintained when they have operated 

the equivalent of a rated duty cycle (see Table 2). Vacuum 

interrupting reclosers must be maintained when they 

have operated the equivalent of twice the rated duty cycle 

(see Table 2).

otee:

N

ANSI Guide C37.61-1973, “

Guide for the Application, 

Operation and Maintenance of Automatic Circuit 

Reclosers

”, provides a procedure for converting 

the rated standard duty cycle into an equivalent 

duty cycle based on the actual operating duty of 

the recloser.

Recloser maintenance intervals

In the absence of specific operating experience, use the 

following guideline(s) to establish maintenance intervals for 

single-phase reclosers:

Oil interrupting reclosers should be maintained 

at 

minimum

 every three (3) years.

Vacuum interrupting reclosers should be maintained 

at 

minimum 

of fifteen (15) years.

For additional information and specific maintenance 

requirements, including periodic routine inspection 

procedures, refer to the appropriate maintenance manual as 

indicated in Table 6.

Replacement parts

Replacement parts for Eaton’s Cooper Power series 

reclosers are available through the factory service 

department. To order replacement parts, refer to the 

applicable maintenance manual. Contact your Eaton 

representative for additional information and ordering 

procedures.

Factory-authorized service centers

Factory-authorized service centers are located throughout 

the continental United States to provide maintenance, 

repair and testing services for Eaton's Cooper Power 

series reclosers. For further information, contact your 

Eaton representative.

Factory maintenance classes

The factory service department offers recloser 

maintenance-training classes. These classes, taught by 

experienced service technicians, are held at the factory 

in-house training facility.
The courses provide hands-on instruction and factory 

recommended procedures for the routine maintenance, 

troubleshooting, repair, and testing of Eaton’s Cooper 

Power series switchgear. It is strongly recommended that 

all personnel who service and maintain Eaton’s Cooper 

Power series switchgear attend the appropriate classes. For 

additional information, contact your Eaton representative.

Instructional video programs

Two DVD video maintenance-training programs, 

KSPV1A, 

General Maintenance and Inspection Procedures For Kyle 

Reclosers and KSPV2A, Mechanical Operation Service and 

Testing For Kyle Single-Phase Reclosers

, are available as 

supplemental training aids for maintenance personnel.
These video programs, developed for use in factory 

maintenance classes, are to be used in conjunction with 

existing service literature. For additional information, contact 

your Eaton representative.

Table 1 .  Maintenance Instructions for Single-Phase 

Reclosers

Recloser type

Service information number

E

S280-25-5

4E

S280-25-4

H, 4H, V4H

S280-10-9

L

S280-15-1

V4L, V4E

S280-15-7

 CAUTION 

This equipment requires routine inspection and 

maintenance to ensure proper operation . If it is not 

maintained, it can fail to operate properly . Improper 

operation can cause equipment damage and possible 

personal injury . 

G105 .1

 CAUTION 

This equipment relies on dielectric fluid to provide 

electrical insulation between components . The dielectric 

strength of the fluid must be checked on a regular basis, 

as part of the routine maintenance inspection, to ensure 

that it is at or above minimum dielectric requirements . 

Use of this equipment with dielectric fluid that does 

not meet minimum requirements can result in internal 

flashovers that will damage the equipment and can 

cause personal injury . 

G107 .3

9

Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions

OPERATION INSTRUCTIONS

   MN280051EN   May 2017

Summary of Contents for COOPER POWER E

Page 1: ...Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions COOPER POWER SERIES Reclosers MN280051EN Effective May 2017 Supersedes April 2014 S280 10 8 ...

Page 2: ...POSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES In no event will Eaton be responsible to the purchaser or user in contract in tort including negligence strict liability or other wise for ...

Page 3: ...haracteristics 2 Data plates 3 Manual operating levers and indicators 3 Manual operating handle 3 Non reclosing lever 3 Operations counter 3 RATINGS AND SPECIFICATIONS 4 DIMENSIONS AND WEIGHTS 6 INSTALLATION PROCEDURE 7 Line installation 7 OPERATION 8 Initial operation 8 Manual operation 8 Non reclosing operation 8 MAINTENANCE INFORMATION 9 Maintenance requirements 9 Maintenance manuals 9 Frequenc...

Page 4: ... Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around high and low voltage lines and equipment G103 3 WARNING Before installing operating maintaining or testing this equipment carefully read and understand the contents of this manual Improper operation han...

Page 5: ...imize the possibility of mechanical damage particularly to the bushings Standards Eaton s Cooper Power series reclosers are designed and tested in accordance with the following standards ANSI IEEE C37 60 1981 and IEEE Std C37 85 1989 standard and ANSI Guide C37 61 1973 Quality standards ISO 9001 Certified Quality Management System Description of operation Reclosers in the E H and L groups see cove...

Page 6: ... maximum of four operations When a recloser is programmed for both fast and delayed operations the fast operations involving no intentional time delay occur first in the sequence according to the recloser s A curve time current characteristic Delayed operations are according to the recloser s B or C time current curve B C or D curves for Types E 4E V4E L and V4L See Time Current Curves R280 91 10 ...

Page 7: ... located under the sleet hood See Figure 3 WARNING Hazardous voltage This device is not a substitute for a visible disconnect Follow all locally approved safety practices Failure to follow proper safety practices can result in contact with high voltage which will cause death or severe personal injury G112 1 WARNING Hazardous voltage Do not rely on the open position of the yellow operating handle o...

Page 8: ...5 280 V4L 14 4 15 5 110 50 45 280 Table 2 Rated interruptions Recloser type Interrupting rating Maximum circuit X R ratio Number unit operations Total unit operations E 15 20 2 40 72 45 55 5 20 90 100 12 12 4E 15 20 3 32 64 45 55 6 20 90 100 13 12 V4E 15 20 3 96 248 45 55 7 120 90 100 15 32 H 15 20 2 40 100 45 55 4 40 90 100 8 20 4H 15 20 2 32 68 45 55 5 24 90 100 10 12 V4H 15 20 2 128 272 45 55 5...

Page 9: ...0 2000 70 140 2800 2500 2000 100 200 3000 2500 2000 V4H 5 10 200 200 200 10 20 400 400 400 15 30 600 600 600 25 50 1000 1000 1000 35 70 1400 1400 1400 50 100 2000 2000 2000 70 140 2800 2500 2000 100 200 3000 2500 2000 140 280 3000 2500 2000 200 400 3000 2500 2000 Recloser type Trip coil continuous current amps Minimum trip current amps Interrupting current rms symmetrical amps L 4 8 8 32 14 4 25 5...

Page 10: ... POLE BOLT A G Figure 7 Dimensions of types E 4H and L reclosers Table 5 Recloser dimensions Description Recloser type E mm in 4E V4E mm in 4H V4H mm in L mm in V4L mm in A 380 15 380 15 355 14 380 15 380 15 B 405 16 405 16 355 14 405 16 405 16 C 1050 41 5 1240 49 900 35 5 940 37 1140 45 D 505 20 570 22 5 430 17 480 19 480 19 E 230 9 368 14 5 175 7 150 6 368 14 5 F 254 10 254 10 230 9 254 10 254 1...

Page 11: ...ayed operations a short time elapses between opening of contacts and placement of the operating handle in the OPEN position 5 Check data plates Make sure the ratings and settings on the recloser data plates are correct for the planned installation 6 Mount the recloser 7 Ground the recloser Make the ground connection to the recloser ground connector located 4 from the bottom of the tank Line instal...

Page 12: ... recloser operation The recloser can be opened or closed manually regardless of the position of the non reclosing lever Figure 8 Connection diagram with switches to facilitate maintenance and complete surge protection BYPASS SWITCH RECLOSER GND SOURCE LOAD SURGE ARRESTER SURGE ARRESTER DISCONNECT SWITCH DISCONNECT SWITCH LOAD SOURCE MULTIGROUNDED NEUTRAL WARNING This equipment is not intended to p...

Page 13: ...ers For further information contact your Eaton representative Factory maintenance classes The factory service department offers recloser maintenance training classes These classes taught by experienced service technicians are held at the factory in house training facility The courses provide hands on instruction and factory recommended procedures for the routine maintenance troubleshooting repair ...

Page 14: ...This page is intentionally left blank 10 Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions OPERATION INSTRUCTIONS MN280051EN May 2017 ...

Page 15: ...This page is intentionally left blank 11 Types E 4E V4E H 4H V4H L and V4L single phase recloser installation and operation instructions OPERATION INSTRUCTIONS MN280051EN May 2017 ...

Page 16: ...ates Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN280051EN May 2017 KA2048 0348 REV03 Eaton is a registered trademark All trademarks are property of their respective owners For Eaton s Cooper Power series product information call 1 877 277 4636 or visit www eaton com cooperpowerseries SAFETY FOR LIFE ...

Reviews: