Device window – Web-Controller
16
Manual Touchscreen Controller
ZNO2038000 A www.eaton.com
GB
To h) Configuration (device)
d) Inputs
In the “Inputs” menu the two digital inputs can be programmed freely.
e) Outputs
In the “Outputs” menu the two relay contacts can be programmed freely.
Inputs 1 and 2 must be activated
via a tick so that they can be con-
figured.
Name:
Free name with max. 20 digits.
Configuration:
Closing = active when input short-
circuited
Opening = active when input open
Rest mode:
Activate rest mode (see Web-
Controller user manual).
Switch off continuous lighting:
The luminaires can be switched off
by strand via “Switch off continuous
lighting”.
Start FT:
Starts function test for all lumi-
naires.
Stop FT:
Stops active FT for all luminaires.
Ext. Monitor:
Displays externally connected con-
tact, e.g. error message from an
alarm system.
Relays 1 and 2 must be activated
via a tick so that they can be con-
figured.
Name:
Free name with max. 20 digits.
Configuration:
Closing = active when input short-
circuited
Opening = active when input open
Communication error:
Communication malfunction of min.
1 luminaire to controller.
Battery operation:
Min. 1 luminaire is battery operated.
Function test:
Min. 1 luminaire is in FT.
Battery life test:
Min. 1 luminaire is in BT.
Charge fault:
Min. 1 luminaire has a charge fault.
Test error:
Min. 1 luminaire has an OT or FT
error.
Luminaire fault:
Min. 1 luminaire has an LED fault.
3 luminaires faulty:
Min. 3 adjacent luminaires have
a fault.