March 2008
12
For more information visit:
www.eaton.com
CA04801001E
Operator Interface Products
HM
i
Operator Interface
Software and Accessories
Table 12. HMIEC0806/HMIEC1612 Function Specifications
M1000, M1001, M1002, M1003, M1020, M1021, M1022, M1067, M10068, and M1161 are the
special auxiliary relays (special M).
Item
Specifications
Remark
Control Method
Stored program, cyclic
scan system
—
I/O Processing Method
Batch I/O (refresh)
Immediate refresh command available only
with I/O of the MPU
Execution Speed
Basic command (30 us)
Application command (30 ~ hundreds us)
Program Language
Co Ladder
D SFC
Step commands included
Program Capacity
999 Steps
Built-in EEPROM
Commands
Basic commands: 32
(including the STL
commands)
Application commands: 59
Step Relay
(Latched)
General Step
Point
128 Points
S0 ~ S127
Auxiliary
Relay
General
1024 Points
M0 ~ M511, M768 ~ M999, 744 points;
M1000 ~ M1279, 280 points
Latched
256 Points
M512 ~ M767
Timer
Digital
64 Points
T0 ~ T63 (100 ms time base)
63 Points
T64 ~ T126 (10 ms time base)
1 Points
T127 (1 ms time base)
Counter
General
112 Points
C0 ~ C111
Latched
16 Points
C112 ~ C127
32 bit
13 Points
C235,C236,C237,C238,C241,C242,
C244,C246,C247,C249,C251,C252, C254
(all of them are latched type)
Data
Register
General
408 Points
D0 ~ D407
Latched
192 Points
D408 ~ D599
Pointer
P
64 Points
P0 ~ P63
Index
Register
E / F
2
E, F
Constant
Decimal K
16 bit: -32768 ~ +32767
32 bit: -2147483648 ~ +2147483647
Hexadecimal H 16 bit: 0000 ~ FFFF
32 bit: 00000000 ~ FFFFFFFF
Self Diagnosis / Protection
I/O check, system execution timeout check, invalid command check,
program check and password settings
Monitor / Debug
Program execution time display, bit / word, device settings