Instruction Manual 

IM00414001E

Effective July 2014

Surge Protective Devices

 

2

EaTon 

www .eaton .com

Figure 1. Surge Protective Device

GREEN

PROTECTED

NO LIGHT

REPLACE

GREEN

PROTECTED

NO LIGHT

REPLACE

LED’s

WHITE WIRE LEAD

Series

Description

Compatibility List

Country of  

Approved Use

BRSURGECSA

CSA Listed for 

Eaton Type BR 

Loadcenters

Intended for Use in  

all Eaton Type BR /  

Westinghouse, 

Cutler-Hammer Type 

BR, and Commander 

Loadcenters

Canada

CHSA

UL and CSA Listed 

for Eaton Type CH 

Loadcenters

Intended for Use in  

all Eaton Type CH /  

Cutler-Hammer Type 

CH Loadcenters

U.S. and 

Canada

Introduction

This manual describes how to install a Surge Protective Device 

(SPD) in parallel (shunt) across the AC supply of a 120/240V Single 

Split-Phase electrical system. The SPD is suitable for use on a  

circuit capable of delivering no more than 10,000 rms symmetrical 

amperes. The SPD resembles a 2-pole circuit breaker with a white 

lead that is connected to the panel bus (Figure 1).
The SPD is designed to be installed on service entrance, branch 

panels, and / or individual equipment disconnects, and functions to 

protect the electrical system from damaging voltage transients.
These instructions do not cover all details, variations, or  

combinations of the equipment, its storage, delivery, installation, 

checkout, safe operation, or maintenance. If you require further 

information regarding a particular application or installation that is not 

covered in this manual, please contact Eaton’s Technical Resource 

Center at 1-877-ETN-CARE, option 2, option 1.

Safety Precautions

A licensed / qualified electrician must complete all instructions 

described in this manual in accordance with the U.S. National 

Electrical Code and Canadian Electric Code, state and local codes,  

or other applicable country codes. All electrical codes supersede 

these instructions.

 

wArning! ShoCk hAzArDS

Improper installation can cause death, injury and / or  

equipment damage.

 Follow all warning and cautions. Completely 

read and understand the information in this instruction manual 

before attempting to install or operate this equipment.

Improper wiring could cause death, injury, and / or equipment 

damage.

 Only licensed / qualified electricians who are trained in the 

installation and service of electrical devices are to install and service 

this equipment.

During normal operation, hazardous voltages are present inside 

the SPD.
When servicing the SPD, follow all safe work practices to avoid 

electrical shock

.

   CAUTion!

Do not perform a high-pot test with the SPD connected to the  

electrical system. Failure to disconnect the SPD during a high-pot 

test will result in damage to the SPD.

Installation and operating Guide

Refer to Table 1, and look at the label on the SPD to verify that  

the appropriate SPD will be installed in a compatible loadcenter and  

in a country of approved use. Refer to Table 2 to verify that the 

SPD’s voltage, rating, and wiring configuration matches that of the 

electrical system and to identify product specifications.

Table 1. Catalog Numbering System

imporTAnT!

 

• 

For maximum protection, locate the surge protective device  

so that the white lead can be cut as short as possible. When  

connected to the neutral, coiling or splicing the white lead will 

reduce protection.

• 

Be sure to follow all U.S. National Electrical Code and Canadian 

Electric Code, state and local codes, or other applicable country 

codes.

• 

To avoid fire, shock, or death, turn OFF power at main circuit 

breaker or fuse and test that power is OFF before wiring.

Installation

1. Turn OFF power supplying this equipment.
2. Remove the cover from the panel.
3. Plug the surge protective device into the selected location.
4. Cut white lead to shortest required length.
5. Connect the surge protective device white lead to the panel  

  neutral bus.
6. Remove two twistouts from the panel cover at the location of  

  the surge protective device.
7. Reinstall the panel cover.

operation

Power Up and System Checkout

Apply system power. The LED’s should light.
If the connected LED’s do not light, remove power, check  

connections, and test again. If the LED’s still do not light, contact 

Eaton’s Technical Resource Center at 1-877-ETN-CARE, option 2, 

option 1.

Routine Operation

After system power has been applied, the SPD automatically begins 

to protect downstream electrical devices from damaging voltage 

transients.
With all phase voltages present, the LED indicators report the status 

of the protection elements and is active when all of them are intact 

and providing protection. Any loss of protection is signaled when 

either LED extinguishes.
The device is 

not repairable

 and contains no user serviceable parts. 

If the unit fails, as evidenced by either LED turning OFF, the unit 

must be replaced.

Summary of Contents for BRSURGECSA Series

Page 1: ...ront Side Back Side Material Instructional Leaflet IM00414001E This page is not a printable document it s only for reference information Printed on 11 x 17 Sheet of Paper Instruction to be folded to 4...

Page 2: ...structions d installation et d emploi 4 Installation 4 Utilisation 4 Garantie 5 Caract ristiques 5 Introducci n 6 Gu a de instalaci n y operaci n 6 Instalaci n 6 Operaci n 7 Garant a 7 Especificacione...

Page 3: ...cal devices are to install and service this equipment During normal operation hazardous voltages are present inside the SPD When servicing the SPD follow all safe work practices to avoid electrical sh...

Page 4: ...Warranty Claim Contact EatonCare 1 877 ETN CARE option 1 option 4 You will be requested to send at minimum the following information a Your full name b Complete address including Zip no PO boxes allow...

Page 5: ...3 Branchez le parasurtenseur dans l emplacement choisi 4 Coupez le c ble blanc pour le raccourcir le plus possible 5 Raccordez le c ble blanc du parasurtenseur au bus neutre du tableau 6 Retirez les d...

Page 6: ...autre d pense engag e pour la r paration ou le remplacement de l appareil Eaton ne saurait en aucun cas tre tenue responsable des dommages int r ts sp ciaux cons cutifs ou fortuits LA PR SENTE GARANTI...

Page 7: ...obretensi n Al reparar el SPD siga todas las pr cticas de seguridad para evitar descargas el ctricas PRECAUCI N No realice una prueba de sobretensi n Hi Pot con el SPD conectado al sistema el ctrico S...

Page 8: ...UNA JURISDICCI N A OTRA Esta garant a es no transferible y se aplica s lo al comprador por menor original o al usuario original Esta garant a no cubre fallas o da os que sean producto de fuerza mayor...

Page 9: ...Devices Eaton 1000 Eaton Boulevard Cleveland OH 44122 United States 877 ETN CARE 877 386 2273 Eaton com 2014 Eaton All Rights Reserved Publication No IM00414001E 001 July 2014 Eaton is a registered tr...

Reviews: