Eaton BLR-ACX
Quick commissioning guide
EATON
www.eaton.com
Menu structure
The following table provides an overview about the basic and advanced programming parameters of BLR-ACX .
Menu 100 is the Basic Menu . Menu 200 through 600 is for advanced users only and requires a PIN access (242) . The settings in these
submenus should only be accessed and changed after consulting with Eaton
Table 1. Programming mode detailed menu map
Menu Function
Default
Customer
settings
100
Quick start setup
Un
Nominal voltage (phase-phase)
208 V / 240 V /
480 V / 600 V
Ct
CT-ratio
600 (corresponds to
3000:5 CT ratio)
Pt
VT-ratio
1.7 (240 V unit)
3.7 (480 V unit)
4.7 (600 V unit)
Ai
Start automatic initializing
N
PFC
Start/Stop/Hold PF-control
On
CP1
Target-PF 1
0.95i
St
Switching time delay
60 s
Out
Type of each step (1,2...14)
Auto (for each step
installed in unit),
Fixed Off (for unused
controller outputs)
200
Setup measuring system
201
Nominal voltage (phase-phase)
208 V / 240 V /
480 V / 600 V
202
CT-ratio
600 (corresponds to
3000:5 CT ratio)
203
VT-ratio
1.7 (240 V unit)
3.7 (480 V unit)
4.7 (600 V unit)
204
Tolerance nominal voltage
20%
205
Voltage measuring
Y = L–L
206
Phase-offset
90
207
Start automatic initializing
N
208
Activate Ai by every start
of BLR-ACX-V
N
209
Synchronization to frequency
60 (60 Hz unit)
210
Temperature offset
0 °C
300
Setup control system
301
Switching threshold 55%
302
Target-PF 1
0.95i
303
Target-PF 2
0.95i
304
Target-PF 2 at KW-export
N
305
Switching time delay
60 s
306
Switching time delay for fine control
10 s
307
Fine control active
N (for units with
equal stage sizes),
Y (for units with
multiple stage sizes)
308
Stop automatic capacitor
size detection
Y
309
Blocking of defective capacitors
N
310
Start/Stop/Hold PF-control
On
311
Control algorithm
1
312
Reactive-power offset
0
313
Asymmetrical switching time delay
1
314
Switch-off capacitors in
leading condition
N
Menu Function
Default
Customer
settings
400
Setup capacitor database
401
Discharging time
60 s
402
Capacitor size: step 1...max. 14
Varies (see equipment
drawings for step size,
typically 25, 50, or
100 kvar capacitive)
403
Type of exit: step 1...max. 14 ,
Auto (for each step
installed in unit),
Fixed Off (for unused
controller outputs)
404
Switching operations: step 1...max. 14 0
500
Setup alarm system
501
Disable automatic alarm reset
N
502
THD alarm
Y
503
Threshold THD
6%
504
Disconnect capacitors when THD >
N
505
Delay time THD Alarm / Temp.
threshold 2
120 s
506
Freeze exits when I = 0
N
507
Service alarm
N
508
Max. operations per step
262 k
509
Max. operation hours of BLR-ACX-V
65.5 k
510
Use temp. sensor as digital input
N
511
Digital input active at high signal
N
512
Temperature alarm active
Y
513
Temp. threshold level 1 (fan control, type
of exit: AL)
40 °C
514
Temp. threshold level 2, disconnect
capacitors
55 °C
515
Control alarm (target cannot be reached) Y
516
Defective steps alarm
Y
517
Loss of capacitor reactive power alarm Y
600
Reset
601
Reset to default values
602
Reset capacitor database to default
603
Reset operation hours
604
Reset average PF
605
Reset max. temperature
606
Reset alarm
607
Display software version