Instruction Leaflet 

IL157002EN

Effective July 2019

Eaton BLR-ACX 

Quick commissioning guide 

  

EATON

 www.eaton.com

Screen legends

INFO Capacitor database
AUTO 

Automatic mode

MANUAL  Manual mode
SETUP 

Setup mode

ALARM 

Blinking during alarm

NT 

Second target-pf is active

EXPORT  Export of active energy
1-14 

Capacitor stage number indication

Figure 1. Digital display

Operation

Operation of BLR-ACX is done by 4 keys .

Figure 2. Operational keys

Submenus are scrolled through by pushing the 

 (up) key  

or 

 (down) key .

Pressing 

 (  right / Enter) key allows selection, entering the 

edit mode or accepts the edited values .
In edit mode, the 

 (left / esc) key or 

 (  right / Enter) key scroll 

left and right to allow setting of the appropriate digit .
Outside of edit mode, the 

 (left / esc) key exits to the next 

higher level .
Press and hold the 

 (left / esc) key for approximately 3 seconds 

to silence any alarms .

Commissioning

Step 1

Upon power on the controller displays the existing power factor 

value “X.XX i” and enters the Automatic Control mode.

The “i” at the end indicates an inductive power factor and would 

be appropriate for most installations . A “c” at the end indicates 

capacitive power factor and suggests reactive power export and 

may not be appropriate . Refer to the troubleshooting section for 

resolution steps .

Step 2

Next step is to set up the basic parameters in the controller .
Press the 

 (down) key to step through the “INFO”, “MANUAL”  

and to “SETUP” mode . Press the 

 (  right /Enter) key to enter  

the Menu 100 and program and or verify the following values .
Un  Nominal voltage (factory programmed, customer may verify)

Ct 

CT-ratio (Factory set to 600, Customer to program if  

 

measurement feature is desired. Refer to Step 3). Note  

 

that this ratio is NOT needed for PF correction and is  

 

only required for accurate measurement values. Changing  

 

the CT ratio will change the capacitor step sizes in 402  

 

and those values will have to be re-programmed.

Pt   PT-ratio (factory programmed)
Ai   Start of automatic initialization (factory programmed)
PFC   PF-control ON/OFF/ HOLD (factory programmed)

CP1   Target-PF (customer to program)

St   Switching time delay (factory programmed, customer  

 

may verify)

Out  Type of each stage (Auto/ Alarm/ Foff/ Fon) (factory  

 

programmed, customer may verify)

Once the Menu 100 is programmed, press the 

 (left / esc)  

key to return to the main screen that displays the existing PF .

Summary of Contents for BLR-ACX

Page 1: ...EN Effective July 2019 Contents Description Page Screen legends 2 Operation 2 Commissioning 2 Overview 3 Menu structure 5 Troubleshooting 6 Retrofit installations with BLR ACX controller 7 Eaton BLR A...

Page 2: ...would be appropriate for most installations A c at the end indicates capacitive power factor and suggests reactive power export and may not be appropriate Refer to the troubleshooting section for res...

Page 3: ...PF should change in the right direction For example 0 70 i 0 78 i 0 85 i If the PF changes in the right direction the capacitor bank has been correctly commissioned If not please refer to the troubles...

Page 4: ...Step 14 ON OFF Basic Programming Mode 100 level menu Un nominal voltage ULL CT CT ratio PT PT or VT ratio Ai automatic initializing PFC power factor control on off CP1 target power factor St switchin...

Page 5: ...2 at KW export N 305 Switching time delay 60 s 306 Switching time delay for fine control 10 s 307 Fine control active N for units with equal stage sizes Y for units with multiple stage sizes 308 Stop...

Page 6: ...it is within its operating parameters The controller will show I LO alarm if there is no measured current or the magnitude sensed is less than 15 mA If the current is greater than 6 A the controller w...

Page 7: ...ase Front instrument case PC ABS UL94 VO Rear metal Protection class Front IP50 IP54 by using a gasket Rear IP20 Retrofit installations with BLR ACX controller Please retain and follow all instruction...

Page 8: ...019 Eaton All Rights Reserved Printed in USA Publication No IL157002EN Z23003 July 2019 Eaton is a registered trademark All other trademarks are property of their respective owners Eaton BLR ACX Quick...

Reviews: