background image

Routine Testing

7

5. Routine Testing

Under BS5839 it is the responsibility of the Premises 
Management to undertake periodic tests to ensure the fi re 
alarm system is operational. These tests are as follows:

5.1 Daily Testing (Premises Management)

• To be conducted by the Premises Management.

• Check that the panel shows no fi re or fault indications.

•  If there are any fault conditions indicated then follow

instructions in section 2.3.

5.2 Weekly Testing (Premises Management)

• To be conducted by the Premises Management.

•  Each week perform a Lamp Test to check that all visual

and audible indicators on the panel are functioning
correctly (refer to section 6.8).

•  Each week a different zone should be tested. Testing with

a manual call point is the simplest method as these can be
easily triggered with the key provided. Testing with a fi re
detection device is more complex as it requires specialist
equipment and may not be possible for all premises. At a
minimum a different manual call point should be tested
each 

week.

•  Place the zone to be tested into test mode using

“Individual Zone Test” (refer to 6.7 for more details)

• Record the weekly test results in the log book.

IT IS THE RESPONSIBILITY OF THE PREMISES 
MANAGEMENT TO DEFINE A FIXED DAY AND TIME OF 
WEEK THAT THE WEEKLY TEST IS PERFORMED. THIS 
MUST BE COMMUNICATED TO ALL OCCUPANTS OF 
THE PREMISES SO THEY KNOW NOT TO EVACUATE 
DURING A WEEKLY TEST. IF AN AUTO-DIALLER OR 
ALARM RECEIVING CENTRE (ARC) IS CONNECTED 
TO THE FIRE SYSTEM THEN THE WEEKLY TEST 
SCHEDULE MUST BE COMMUNICATED TO THEM AS 
WELL.

5.3 Quarterly Testing (Competent Person)

•  To be conducted by the Competent Person. Included as

reference for the Premises Management.

•  Check all previous log book entries and verify that any

corrective actions had been taken.

•  Carry out the weekly test and record the results in the log

book.

• Visually inspect the batteries and their connections.

•  Disconnect the mains supply and check that the fi re

system is capable of supplying the fi re alarm devices by
operating a call point.

5.4 Yearly Testing (Competent Person)

•  To be conducted by the Competent Person. Included as

reference for the Premises Management.

•  Carry out the weekly test and record the results in the log

book.

• Carry out the Quarterly testing.

• Test ALL fi re detection devices and manual call points.

IMPORTANT

March 2016

 

  www.eaton.com 

EATON BiWire Flexi User Manual   (

PR215-216-519-03 15-03-16

, PINSTFLEXIUSER)

Summary of Contents for BiWire Flexi

Page 1: ...Conventional Fire System BiWire Flexi Fire Panel EFBW8ZONE FLEXI EFBW4ZONE FLEXI EFBW2ZONEFLEXI User Manual...

Page 2: ...vel 2 5 4 WHAT TO DO INSTRUCTIONS 6 4 1 What To Do In The Event Of a Fire Alarm Condition 6 4 2 What To Do In The Event Of a Fault Condition 6 4 3 What To Do When Re Enabling Zones With Latching Detec...

Page 3: ...ine testing and filling in the log book as required by BS5839 part 1 After the system has been installed and commissioned by a Competent Person the Premises Management for the site must ensure that al...

Page 4: ...e failure of the panel the service company must be contacted immediately Repeater Fault Communication with a repeater panel has been lost 3 Battery Fault Battery voltage missing Mains Fault Mains supp...

Page 5: ...are available for this level Silence Fire Alarm Devices BiWire Zones and Conventional Sounder Circuits Sound Fire Alarm Devices BiWire Zones and Conventional Sounder Circuits Reset System Mute Buzzer...

Page 6: ...o silence the fire alarm devices and reset the system Note the time the fire alarm occurred and log the fire event in the log book If the fire alarm was a false activation i e there was no fire then t...

Page 7: ...details Record the weekly test results in the log book IT IS THE RESPONSIBILITY OF THE PREMISES MANAGEMENT TO DEFINE A FIXED DAY AND TIME OF WEEK THAT THE WEEKLY TEST IS PERFORMED THIS MUST BE COMMUNI...

Page 8: ...buzzer will continue sounding This function will immediately exit back to Access Level 1 6 3 Sound Fire Alarm Devices This function is only available at access level 2 and when the alarms are silent E...

Page 9: ...ts will have their associated disabled indicator lit and all enablements will have their associated disabled indicators unlit The function always starts at Zone 1 When an item is selected for disablem...

Page 10: ...emain lit When a fire detection device or manual call point is activated in the zone under test it will sound all fire alarm devices for 3 seconds and then will automatically silence Any fire conditio...

Page 11: ...escription of where the zone is on the site and or what rooms are in the zone This defines the mode configuration of the zone which dictates the type of devices that can be fitted Quantities of each d...

Page 12: ...YES NO Auxiliary Relay 6 YES NO Auxiliary Relay 7 YES NO Auxiliary Relay 8 YES NO Circled if connected to external equipment Explains what happens when these outputs are activated in the event of a fi...

Page 13: ...work false alarms in accordance with BS5839 part 1 and any other event this includes genuine fires and faults SITE DETAILS Premises Management Names Mr P Manager Company Name of Premises Site Address...

Page 14: ...maintenance visit if required UNWANTED FALSE FIRES Date Time Zone Cause if Maintenance Maintenance Category Further Signed Location Known Visit Needed Findings Further Action YES NO Alarm Required 07...

Page 15: ...ders Short or Open circuit condition on the sounder circuit FRE Fault ON ON SLOW SLOW Short or Open circuit condition on the FRE FPE Fault ON ON SLOW SLOW Short or Open circuit condition on the FPE Zo...

Page 16: ......

Reviews: