6.7 Individual Zone Test

• This function is only available at access level 2.

•  This function will allow individual zones to be placed in the

zone test mode.

• Enter the access code 3112

• Press “Test” button (2).

•  The zone currently in test mode will have its associated

disabled indicator lit and all zones not in test mode will
have their associated disabled indicators unlit.

• The function always starts at Zone 1.

•  When an item is selected for test mode its disable

indicator will change from unlit to lit.

•  When an item is selected for normal operation its disable

indicator will change from lit to unlit.

•  Press the following button sequences for the required test

 mode/normal operation:

• Pressing “Select” button (3) will accept the selected test

zone and exit back to Access Level 1. The Test indicator
will remain lit and the zone disabled indicator will also
remain 

lit.

•  When a fi re detection device or manual call point is

activated in the zone under test it will sound all fi re alarm
devices for 3 seconds and then will automatically silence.

• Any fi re condition detected in any other zone will place the

system into full alarm condition and the fi re alarm devices
will activate continuously.

•  To end the individual test mode the above selection

instructions should be carried out and the zone disabled
indicator changed to the unlit state.

6.8 Lamp Test

• This function is available at access level 2.

• Enter the access code 3112.

• Press “Indicator Test” button (3).

•  Each indicator on the front of the panel will turn on in turn

and then turn off in turn (excluding the Power On indicator).

•  This function will immediately exit back to Access Level 1.

Item  

2-Zone

4-Zone

8-Zone

Zone 1

3

3

3

Zone 2 

2 + 3 

2 + 3 

2 + 3 

Zone 3 

2 (2 times) + 3 

2 (2 times) + 3 

Zone 4 

2 (3 times) + 3 

2 (3 times) + 3 

Zone 5 

2 (4 times) + 3 

Zone 6 

2 (5 times) + 3 

Zone 7 

2 (6 times) + 3 

Zone 8 

2 (7 times) + 3

March

 2016 

  www.eaton.com 

EATON BiWire Flexi User Manual   (

PR215-216-519-03 15-03-16

, PINSTFLEXIUSER)

Summary of Contents for BiWire Flexi

Page 1: ...Conventional Fire System BiWire Flexi Fire Panel EFBW8ZONE FLEXI EFBW4ZONE FLEXI EFBW2ZONEFLEXI User Manual...

Page 2: ...vel 2 5 4 WHAT TO DO INSTRUCTIONS 6 4 1 What To Do In The Event Of a Fire Alarm Condition 6 4 2 What To Do In The Event Of a Fault Condition 6 4 3 What To Do When Re Enabling Zones With Latching Detec...

Page 3: ...ine testing and filling in the log book as required by BS5839 part 1 After the system has been installed and commissioned by a Competent Person the Premises Management for the site must ensure that al...

Page 4: ...e failure of the panel the service company must be contacted immediately Repeater Fault Communication with a repeater panel has been lost 3 Battery Fault Battery voltage missing Mains Fault Mains supp...

Page 5: ...are available for this level Silence Fire Alarm Devices BiWire Zones and Conventional Sounder Circuits Sound Fire Alarm Devices BiWire Zones and Conventional Sounder Circuits Reset System Mute Buzzer...

Page 6: ...o silence the fire alarm devices and reset the system Note the time the fire alarm occurred and log the fire event in the log book If the fire alarm was a false activation i e there was no fire then t...

Page 7: ...details Record the weekly test results in the log book IT IS THE RESPONSIBILITY OF THE PREMISES MANAGEMENT TO DEFINE A FIXED DAY AND TIME OF WEEK THAT THE WEEKLY TEST IS PERFORMED THIS MUST BE COMMUNI...

Page 8: ...buzzer will continue sounding This function will immediately exit back to Access Level 1 6 3 Sound Fire Alarm Devices This function is only available at access level 2 and when the alarms are silent E...

Page 9: ...ts will have their associated disabled indicator lit and all enablements will have their associated disabled indicators unlit The function always starts at Zone 1 When an item is selected for disablem...

Page 10: ...emain lit When a fire detection device or manual call point is activated in the zone under test it will sound all fire alarm devices for 3 seconds and then will automatically silence Any fire conditio...

Page 11: ...escription of where the zone is on the site and or what rooms are in the zone This defines the mode configuration of the zone which dictates the type of devices that can be fitted Quantities of each d...

Page 12: ...YES NO Auxiliary Relay 6 YES NO Auxiliary Relay 7 YES NO Auxiliary Relay 8 YES NO Circled if connected to external equipment Explains what happens when these outputs are activated in the event of a fi...

Page 13: ...work false alarms in accordance with BS5839 part 1 and any other event this includes genuine fires and faults SITE DETAILS Premises Management Names Mr P Manager Company Name of Premises Site Address...

Page 14: ...maintenance visit if required UNWANTED FALSE FIRES Date Time Zone Cause if Maintenance Maintenance Category Further Signed Location Known Visit Needed Findings Further Action YES NO Alarm Required 07...

Page 15: ...ders Short or Open circuit condition on the sounder circuit FRE Fault ON ON SLOW SLOW Short or Open circuit condition on the FRE FPE Fault ON ON SLOW SLOW Short or Open circuit condition on the FPE Zo...

Page 16: ......

Reviews: