Page 26
614-20306-00 - 9SX 0-6 KVA EMEA_EN
3. Installation
B - Installation
• Rack mounting of UPS and accessory modules.
Follow steps 1 to 4 for module mounting on the rails.
C - UPS connection
Check that the indications on the name plate located on the back of the UPS meets to the AC-power source
and the true electrical consumption of the total load.
1. 9SX1000IR / 1500IR / 2000IR:
connect the
UPS input socket
1
to the AC-power
source using the cable of the protected
equipment.
9SX3000IR
: connect the supplied cable
15
(250 V - 16 A) to the socket
1
, then to
the AC-power source.
2.
Connect the loads to the UPS using the
cables
16
.
It is preferable to connect the priority
loads to the outlets marked
5
and the
non-priority loads to the outlets marked
6
7
that can be programmed (see 2.2
"Rear panels").
For the
9SX3000IR
model, connect any
high-power devices to the 16 A outlet.
To program shutdown of outlets
6
7
during operation on battery power and
thus optimise the available backup time,
please check the in/out settings.
Note
: The UPS charges the battery as soon as it is connected to the AC-power source, even if
button is not
pressed.
Once the UPS is connected to the AC-power source, 24 hours of charging are required before the battery can
supply the rated backup time.