![Eaton 9SX Series Installation And User Manual Download Page 41](http://html1.mh-extra.com/html/eaton/9sx-series/9sx-series_installation-and-user-manual_4230144041.webp)
Page 41
614-20306-00 - 9SX 0-6 KVA EMEA_EN
5. Operation
Qualify Bypass
The default setting (“In spec”) allows a transfer to Bypass only when Bypass is within the following
speci
fi
cations:
• Bypass voltage is between the “Bypass Voltage Low Limit” and “Bypass Voltage High Limit” settings.
• Bypass frequency is within nominal frequency 5%.
You can prohibit Bypass (”Never”) or always allow Bypass with no speci
fi
cation checking (“Always”). For
“Always on UPS Fault,” transfer to Bypass is always made on UPS fault; otherwise, operation proceeds as
with the default setting.
Synchronization Window
The UPS tries to synchronize with Bypass when the Bypass frequency is less than the value set for the
“Synchronization Window” setting. When the Bypass frequency is more than the set value, the UPS goes to
nominal frequency.
Unsynchronized Transfers
When Qualify Bypass is set to “Always” or “Always on Fault” you can select the interruption time when
transferring to bypass, default setting is “Half Cycle” but can be changed to “Full cycle”.
5.8 Con
fi
guring battery settings
Automatic battery test
Automatic battery tests are done every week in constant charging mode and at each cycle in ABM
®
mode. The
tests frequency can be modi
fi
ed.
During the test, the UPS transfers to Battery mode and discharges the batteries for 10 seconds under load.
Battery mode is not displayed and battery low alarm does not activate during a battery test.
The battery test may be postponed due to bad conditions, or failed if battery is not ok.
Low battery warning
During discharge, the low battery alarm is activated if the remaining runtime goes below 3 minutes or less
than the setting capacity threshold (0% by default).
This threshold can be modi
fi
ed.
External battery setting
The number of Extended Battery Module is automatically detected, or can be set manually in number of EBM
or in Ah.
Deep discharge protection
This setting is recommended to avoid damaging the battery. Warranty is void if deep discharge protection is
disabled.
5.9 Retrieving the Event log
To retrieve the Event log through the display:
1.
Press any button to activate the menu options, then select Event log.
2.
Scroll through the listed events.
5.10 Retrieving the Fault log
To retrieve the Fault log through the display:
1.
Press any button to activate the menu options, then select Fault log.
2.
Scroll through the listed faults.