Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 02
39
66..44
R
Reeppllaacciinngg tthhee U
UP
PS
S EEqquuiippppeedd w
wiitthh aa H
HoottS
Sw
waapp M
MB
BP
P
The
HotSwap MBP
module makes it
possible to service or even replace
the UPS without affecting the connected
loads.
1. Set switch
33
to Bypass position.
The red LED on the
HotSwap MBP
module goes ON, indicating that the
load is supplied directly with AC input
source power.
2. Stop the UPS by pressing the
button on the UPS control panel.
LED
31
"UPS ON - OK to switch"
goes OFF, the UPS can now be
disconnected and replaced.
Return to normal operation
1. Check that the UPS is correctly
connected to the
HotSwap MBP
module.
2. Start the UPS by pressing the
button on the UPS control panel.
LED
31
"UPS ON - OK to switch" on
the
HotSwap MBP
module goes ON
(otherwise, there is a connection error
between the
HotSwap MBP
module
and the UPS).
3. Set switch
33
to Normal position.
The red LED on the
HotSwap MBP
module goes OFF.
MBP-120
LOAD
15
28
1
8
2
4
3
5
6
9
10
11
7
29
33
34
35 36
Maintenance
66..55
R
Reeccyycclliinngg TThhee U
Usseedd EEqquuiippm
meenntt
Contact your local recycling or hazardous waste center for information on proper disposal of the used
equipment.
RISK OF ELECTRIC SHOCK
- Observe the warning associated with the risk of electric shock symbol.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This
product contains sealed, Lithium-Ion batteries and must be disposed of properly. For more information,
contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in
the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Summary of Contents for 9PX2000RT-L
Page 20: ...14 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 User Settings ...