Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 02
11
Table 6. User Settings (Continued)
Submenu
Available Settings
Default settings
If Enabled, UPS will shut-
down after defined duration.
of back-up time, if load is less
than set value.
Sleep mode
[Enabled] [Disabled]
[Enabled]
[Timer] [10min] … [120min]
If Disabled, LCD and
communication will turn OFF
immediately after UPS is OFF.
[90min]
If Enabled, LCD and
communication stays ON 1h30
min after UPS is OFF.
Site wiring fault
[Enabled] [Disabled]
[Disabled]
Prevents from starting the
UPS in case of phase vs
neutral wires swapping.
Power Off alert
[Enabled] [Disabled]
[Enabled]
If Enabled, activates a
confirmation screen that
requires user confirmation
after pressing the power
button, before the UPS
shutdown occurs.
Battery settings
Low battery warning
[Capacity] [0%] … [100%]
[0%]
[Runtime] [0min] … [60min]
[3min]
The alarm triggers when the
set percentage of battery
capacity or remaining back-up
time is reached.
Restart bat. level
[0%] ... [100%]
[0%]
If set, automatic restart will
occur only when percentage
of battery charge is reached.
Com settings
Input signals
Sets Input signals parameters
(function, delay, operation)
through external contact
connectors or RS232.
ROO port:
- [Function]: [No] [ROO] [RPO]
[Building alarm] [Forced
bypass] [On generator]
[Remote shutdown]
[No]
Summary of Contents for 9PX2000RT-L
Page 20: ...14 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 User Settings ...
Page 36: ...30 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 UPS Remote Control Functions ...
Page 46: ...40 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 Recycling The Used Equipment ...
Page 50: ...44 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 CE Compliance Contact ...
Page 56: ...P 16400100602 P 164001006 02 ...