Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 02
Table 6. User Settings (Continued)
Submenu
Available Settings
Default settings
Output mode
Mode: [Industrial] [IT]
[Custom] Overload: [Inv>Stop]
[Inv>BP] [Inv>BP>Inv]
[IT] [Inv>BP>Inv] [Inv>Stop]
Short-circuit: [Inv>Stop]
[Inv>BP]
[Inv>BP>Inv]
Input volt hysteresis
Sets input voltage hysteresis
from [1] to |10V]
[10V]
High Efficiency mode
[Enabled] [Disabled] Power the
output from Bypass for high
efficiency
[Disabled]
Bypass settings
[Volt low]
[80V] LV; [160V] HV;
[Volt high]
[144V] LV; [276V] HV;
[Qualify]
[In spec];
[Hz synch]
[5%];
[Unsynch]
[Half cycle]
Load segments
[Auto start delay]
UPS: [0s]; Group1: [3s];
Group2: [6s] UPS: [Disabled];
[Auto shutdown delay]
Group1: [Disabled]; Group2:
[Disabled]
Overload prealarm
[10%] … [102%] Load %
when overload alarm occurs
[102%]
On/Off Settings
Start/Restart
[Cold start] [Auto restart]
[Auto start] [Start on bypass]
[Cold start] [Auto restart] are
Enabled
[Auto start] [Start on bypass]
are Disabled
Forced reboot
[Enabled] [Disabled]
[Enabled]
[Timer] [10s] … [180s]
[10s]
When mains recover during a
shutdown sequence: If set to
Enabled, shutdown sequence
will complete and wait 10
seconds prior to restart, If set
to Disabled, shutdown
sequence will not complete,
UPS stays on.
Energy saving
[Enabled] [Disabled]
[Disabled]
[Timer] [1min] … [15min]
[5min]
[Level] [100W] … [1000W]
[100W]
Summary of Contents for 9PX2000RT-L
Page 20: ...14 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 User Settings ...
Page 36: ...30 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 UPS Remote Control Functions ...
Page 46: ...40 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 Recycling The Used Equipment ...
Page 50: ...44 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 CE Compliance Contact ...
Page 56: ...P 16400100602 P 164001006 02 ...