RPO connections:
RPO
Comments
Connector type
Terminal, 14 AWG maximum wires
External breaker specification
60 V DC/30V AC 20mA max
RPO
11
ROO
Remote On/Off (ROO)
•
Remote On/Off allows remote action of button to switch On/Off the UPS.
•
When contact changes from open to closed, the UPS is switched-on (or stays On).
•
When contact changes from closed to open, the UPS is switched-off (or stays Off).
•
On/Off control via button has priority over the remote control.
RPO
Comments
Connector type
Terminal, 14 AWG maximum wires
External breaker specification
60 V DC/30V AC 20mA max
RPO
11
ROO
Remote Control Connection and Test
1.
Check the UPS is shut down and the electrical supply network disconnected.
2.
Remove RPO connector from the UPS by unfitting the screws.
3.
Connect a normally closed volt-free contact between the two pins of connector.
RPO
11
Normally Closed
Contact open: shut down of UPS
To return to normal operation, deactivate the external remote
shut down
contact and restart the UPS from the front panel.
4.
Plug the RPO connector into the back of the UPS and fix the screws.
5.
Connect and restart the UPS according to the previously described procedures.
Summary of Contents for 9PX2000RT-L
Page 20: ...14 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 User Settings ...
Page 36: ...30 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 UPS Remote Control Functions ...
Page 46: ...40 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 Recycling The Used Equipment ...
Page 50: ...44 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 CE Compliance Contact ...
Page 56: ...P 16400100602 P 164001006 02 ...