Page 42
8-11kVA EU_EN
9. Specifications
Table 6. Electrical output
All models
Normal mode
Battery mode
Voltage regulation
±1%
±1%
Efficiency
> 98% (High Efficiency mode)
> 94.5% for 8kVA models
> 95% for 11kVA models
> 91%
Frequency regulation
Sync with line ±5% of nominal line
frequency (outside this range: ±0.5%
of auto-selected nominal frequency)
±0.5% of auto-selected nominal
frequency
Nominal output
200V*, 208V*, 220V*, 230V, 240V, 250V* (voltage configurable)
8000/11000VA* 7200/10000W*
Frequency
50 or 60Hz, autosensing or configurable as a frequency converter
Output overload
100-102% : no alarm
102-110% : load transfers to Bypass mode after 2 minutes
110-125% : load transfers to Bypass mode after 1 minute
125-150% : load transfers to Bypass mode after 10s
> 150%
: load transfers to Bypass mode after 500ms
Output overload
(Bypass mode)
100-125% : no alarm
125-150% : UPS shuts down after 1 minute
> 150%
: UPS shuts down after 1s
Voltage waveform
Sinewave
Harmonic distortion
< 2% THDV on linear load
< 5% THDV on non-linear load
Transfer time
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
Power factor
0.9
Load crest ratio
3 to 1
* 200/208/250V are derated at 10000VA 9000W, 220V is derated at 9900W for 11kVA models.
Table 7. Electrical output connections
Model
Output connection
Output cable
9SX8KiPM
Hardwired
Not provided
9PX8KiPM
9SX11KiPM
9PX11KiPM
Table 8. Environmental and safety
EMC certifications
IEC/EN 62040-1: 2008
IEC/EN 62040-2: 2006 Cat. C2
IEC/EN 62040-3: 2011
IEC 60950-1
UL 1778 4
th
CSA 22.2
EMC (Emissions)*
CISPR22 Class A
AS/NZS 22 Class A
IEC 61000-3-2 (-3-12)
IEC 61000-3-3 (-3-11)
FCC part 15 Class A
EMC (Immunity)
IEC 61000-2-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports)
IEC 61000-4-5, Level 4, Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
*
for output cable < 10m.