Eaton 93PM Integrated Accessory Cabinet-Tie (50 kW and 100 kW IAC-T) Installation and Operation Manual P-164000371—Rev 05
35
6.
Remove the hardware loosened in
7.
Pull the pallet skids out from under the metal angle supports without disturbing the jacking bolts. Recycle
the pallet skids and hardware in a responsible manner.
CAUTION
CABINET MAY FALL. Do not loosen the hardware attaching the front supports to the cabinet base. The cabinet
must be lowered by the jacking bolts before the supports can be removed.
8.
Carefully and evenly
lower the cabinet by turning each jacking bolt consecutively two full turns
(maximum)
until the casters contact the floor and the cabinet is no longer supported by the jacking bolts.
9.
After the IAC-T is resting on the floor, remove the jacking bolts and floor protectors. Recycle them in a
responsible manner.
10. Remove the cabinet support bolts fastening the front, rear, and side cabinet supports together and remove
the side supports (see
).
11. Remove the cabinet mounting bolts holding the front and rear supports to the cabinet base (see
).
12. Recycle the bolts along with the support brackets in a responsible manner.
13. Close the door and secure the latch.
14. If the leveling feet are not retracted, turn all four leveling feet until they are retracted as far into the cabinet
as possible.
15. If line-up-and-match installation, remove the rectangular knockout on the bottom front side of the UPS and
the IAC-T (see
).
NOTE
In line-up-and-match installations, the IAC-T and UPS cabinets should be located as
shown in
, or
CAUTION
To prevent tipping when rolling the cabinet and damage to the front door, push the cabinet from the rear
whenever possible. Do not push the cabinet from the sides.
16. Roll the cabinet to the final installation location.
17. Lower the cabinet feet and using a level, adjust the cabinet height accordingly until the cabinet is level.
18. Locate the top splice bracket shipped with the IAC-T.
19. Remove the screws along each adjacent cabinet top panel securing the top panels. Retain the hardware
for later use.
20. Install the top splice bracket between the adjacent cabinet and secure the tie strap with retained hardware.
NOTE
Optional front and back floor mounting brackets are available to order for permanently
mounting the IAC-T. Left and right side floor mounting brackets and mounting hardware
to permanently mount the IAC-T are customer-supplied.
21. If permanently mounting the IAC-T using the left and right side floor mounting brackets, proceed to
; if using the front and rear floor mounting brackets, proceed to
; otherwise, proceed to
22. Using customer-supplied mounting bolts, install the customer-supplied floor mounting brackets to the left
and right side of the UPS with the angle facing outward.