Eaton 93PM Integrated Accessory Cabinet-Tie (50 kW and 100 kW IAC-T) Installation and Operation Manual P-164000371—Rev 05
87
C
Chhaapptteerr 88 P
Prroodduucctt S
Sppeecciiffiiccaattiioonnss
This section provides the following specifications:
•
Model Number
•
Input specifications
•
Output specifications
•
Environmental and safety specifications
88..11
M
Mooddeell N
Nuum
mbbeerrss
The Integrated Accessory Cabinet-Tie (IAC-T) is available in the model listed below to meet the needs of the
Eaton 93PM UPS product line.
Integrated Accessory Cabinet Models
Description
Eaton 93PM 50 kW IAC-T
IAC-T for the Eaton 93PM 50 kW UPS
Eaton 93PM 100 kW IAC-T
IAC-T for the Eaton 93PM 100 kW UPS
88..22
S
Sppeecciiffiiccaattiioonnss
The following sections detail the input, output, and environmental and safety specifications for the IAC-T.
88..22..11
IInnppuutt
Operating Input Voltage and Frequency
480 Vac, 50/60 Hz
Input Wiring
3 wire+ ground – No neutral
Operating Input Current
See
through
88..22..22
O
Ouuttppuutt
Operating Output Voltage and Frequency
480 Vac, 50/60 Hz
Output Wiring
3 wire+ ground – No neutral
Output Current
See
through
88..22..33
EEnnvviirroonnm
meennttaall aanndd S
Saaffeettyy S
Sppeecciiffiiccaattiioonnss
Operating Temperature
5 to 40°C (41 to 104°F) without derating. The recommended
operating temperature is 25°C (77°F)
Storage Temperature
-25 to +55°C (-13 to +131°F)
Operating Altitude
Maximum 1500m (5000 ft) at 40°C without derating
Transit Altitude
15000m (49213 ft)
Ventilation
Natural Convection
Summary of Contents for 93PM IAC-T Series
Page 98: ...P 16400037105 P 164000371 05 ...