• Do not expose the UPS to overly aggressive environments, like salt mist or
corrosive gases. High relative humidity will accelerate the effects of
contaminants. The UPS should be installed in a G1 environment (based on
ANSI/ISA S-71.04 classifications). Use in a more aggressive environment
can lead to reduced product life and possibly early failure. If the installation
location does not meet the recommended environment, contact Eaton
service representative for further information.
• The UPS should not be placed near a source of dust or sand. Excessive
amount of dust or sand can cause damage or lead to malfunction.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements
.
Table 6: UPS cabinet weights
Model
Shipping (kg)
Weight (kg) installed Point loading
Eaton 93E G2
100/100 without bat-
teries
351
283
35 kg per wheel (to-
tal 8 wheels)
Eaton 93E G2
120/120 without bat-
teries
379
311
39 kg per wheel (to-
tal 8 wheels)
Eaton 93E G2
200/160 without bat-
teries
525
457
57 kg per wheel (to-
tal 8 wheels)
Eaton 93E G2
200/200 without bat-
teries
525
457
57 kg per wheel (to-
tal 8 wheels)
The UPS cabinet uses forced air cooling to regulate the internal component
temperature. Air inlets are in the front of the cabinet and outlets are in the back
of the cabinet. Allow clearance in the front and back of the cabinet for proper air
circulation. The clearances required around the UPS cabinet are listed in Table
Table 7: UPS cabinet clearances
Clearance
From top of cabinet
300 mm working space
From front of cabinet
900 mm working space
From back of cabinet
> 600 mm working space recommended
From right side of cabinet
> 50 mm working space recommended
From left of cabinet
> 50 mm working space recommended
The basic environmental requirements for operation of the UPS are:
Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
User's and installation guide
©
Eaton Corporation plc 2019. All rights reserved.
Revision: 002
Document ID: P-164000848
34 (118)