10
Eaton 93E External Battery Cabinet Installation Manual P-164000057—Rev 05
Table 1. EBC Cabinet Weights
Model
Weight kg (lb)
Strings
Shipping
Installed
Point Loading
Eaton 93E 30EBC
2
561 (1237)
536 (1182)
8 at 77 (170)
3
744 (1640)
719 (1585)
8 at 100 (220)
Eaton 93E 60EBC
4
779 (2788)
1231 (2713)
12 at 165 (363)
6
1448 (3192)
1414 (3117)
12 at180 (397)
The EBC cabinet uses convection cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the back of the cabinet. Allow clearance in front of and in back of the cabinet
for proper air circulation. The clearances required around the EBC cabinet are shown in
.
Table 2. EBC Cabinet Clearances
From Top of Cabinet
304.8 mm (12") working space
From Front of Cabinet
914.4 mm (36") working space
From Back of Cabinet
914.4 mm (36") working space
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
The basic environmental requirements for operation of the EBC are:
•
Recommended Operating Range: 15–25°C (59–77°F)
•
Maximum Relative Humidity: 5–95%, noncondensing
CAUTION
Operating temperatures above the recommended range will result in decreased battery life and performance,
and will reduce or void the battery warranty. Refer to Eaton's Terms and Conditions of Sale with Battery
Replacement Coverage and the Battery Replacement Price Book for more information. These documents can
be found at
www.eaton.com/powerquality
or contact your service representative for information on how to
obtain copies.