Sync Control for Eaton 9395P and 93PM
21
User’s and Installation Guide
Table 3-6 Customer Remote Monitoring System Wiring Interconnections
Function
From Sync
Control
Wire Size
[mm
2
]
Note
UPS System A – Active Master Source
TB1-63
1,5
Twisted pair
Common Return
TB1-62
1,5
UPS System B – Active Master Source
TB1-64
1,5
Twisted pair
Common Return
TB1-62
1,5
UPS System-A – Synchronized to Load B
TB1-65
1,5
Twisted pair
Common Return
TB1-62
1,5
UPS System-B – Synchronized to Load A
TB1-66
1,5
Twisted pair
Common Return
TB1-62
1,5
Load Sync Enabled
TB1-68
1,5
Twisted pair
Common Return
TB1-67
1,5
Figure 3-6 Eaton Sync Control Typical Control Wiring Termination Locations
TB1
Ground Terminal